FlowCon GreEQ 15-40 mm (1/2"-1 1/2")
1B95093 - 01/2022
Installation and Operation Instruction
The FlowCon GreEQ - equal percentage -
inserts are for use with three different FlowCon
valve housings, either:
FlowCon A DN15-25 (1/2"-1")
FlowCon AB DN15-32 (1/2"-1 1/4")
FlowCon ABV DN15-40 (1/2"-1 1/2")
Insert Setting and Installation
Prior to installing the FlowCon GreEQ insert
(supplied from factory in setting 5.0 due to cali-
bration), the system should be properly flushed.
Blank valve covers are available to be installed
during flushing.
General Assembly Drawing
FlowCon GreEQ
A: Valve housing
B: GreEQ insert
C: Adjustment keys
D1: P/t plug (2 pcs.)
D2: Plug (2 pcs.)
E: Union end connections
F: FlowCon actuator
This paper is a supplement to the FlowCon General Instruction
Latest release of any FlowCon material is available on www.flowcon.com
Figure 1
It is recommended to grease the O-rings located
around the insert and headnut with silicone grease
before installing the insert in the valve housing.
The desired flow rate is set by ad-
justing the insert (turn counter-clock-
wise to setting 1.0 and then clock-
wise up) with a special adjustment
key. Range is between 1.0 and 5.0
⚠ Do not overturn. Scale setting is
located on top of the insert. The large
white digits, numbered 1 to 5, indica-
te full turns and red digits, numbered
0 to 9, indicate 1/10 of full turn. Flow
setting may be done either before or
after the insert is installed in the
valve housing. Once flow is set and
insert is fitted in the valve housing,
the required actuator may be applied. Please
see specific installation instruction for selected
actuator.
Turn to
higher
settings
C
D1
D2
E
A
Turn to
setting
1.0
F
B
E
C
Page 1 of 2