ELECTRICAL SPECIFICATIONS
MAXIMUM REPETITIVE SELF RESET SURGE:
3500 Volts,1750 Amps for 100 pulses using 2 V source.
per: EN61000-4-5 Specification (all lines common mode).
*MAXIMUM FAIL SAFE SURGE (all lines common mode):
4000 Volts 2000 Amps for 100 pulses using 2V source.
per EN61000-4-5 Specification. Exceeds EN6100-4-5, level 4.
CLAMPING VOLTAGES:
Common Mode - Line to line.
Differential Mode - Line to ground.
*CAPACITANCE:
Line/line: <40pF.
Line/Ground: <40pF.
COMPONENT RESPONSE TIME:
Less than 10 Nanoseconds.
OPERATING TEMPERTURE:
(-40ºC TO +85ºC).
*Applies to all devices except 62V and 260V.
PART NUMBER SELECTION:
FORMAT: HW4-18C
HW(# of wires)-(clamp voltage)(C for optional DIN Clip)
APPLICATION
MODEL
RS422, RS423,
HW(_)-7
RS232, RS485
DIGITAL
HW(_)-18
CURRENT LOOP
ANALOG
HW(_)-27
CURRENT LOOP
LEASED LINE,
HW(_)-62
ISDN, T-1, DDS
DIAL UP,
HW(_)-260
POTS LINE
Custom Surge protection is our specialty. Custom versions are available including mixed or
special voltages, different connectors or wiring options. Contact us for details.
OPERATION:
The Zap-Tech protector will repetitively protect and reset without
degradation up to it's maximum repetitive self-reset surge. If it is
subjected to more than it's maximum repetitive self-reset surge, the
device will remain in a clamped mode indicating that it should be
removedor replaced while keeping the equipment safe from
subsequent surges.
INSTALLATION:
Zap-Tech protectors should be installed in series with the incoming
communication line at the port of the equipment being protected. The
protector's grounding wire must be connected to the chassis ground
of the protected equipment.
MAX
CLAMP
OPERATING
VOLTAGE
VOLTAGE
5.5V
7V
16.0V
18V
25.5V
27V
62V
60.0V
260V
250V
HW SERIES SURGE PROTECTORS
MECHANICAL SPECIFICATIONS
1/4" GROUND BRAID, 8.0" (+/-0.25") INCH
LENGTH, GREEN W/ 10-32 RING TERMINAL.
HARDWIRED IN LINE PROTECTOR
SHOWN WITH OPTIONAL DIN RAIL MOUNTING CLIP
INSTALLATION
Just splice the HW series unit
in line with your existing cable.
PROTECTION PAIRING ASSIGNMENTS:
IMPORTANT!
It is important that the protector and the chassis of the equipment to be
protected are both properly grounded to a properly earthed electrical
safety ground via the equipment's 3-prong power cord and/or a ground
wire of 14 AWG or larger. Protectors should be installed at both ends of
communication lines to ensure equipment protection at each end.
All specifications are subject to change without notice.
Detailed specifications for specific versions available on request.
© Copyright 2013, Zap-Tech Corporation all rights reserved.
ATTACH GROUND WIRE TO GROUNDED
CHASSIS OF PROTECTED EQUIPMENT
HW SURGE ARRESTOR
MODEL HW8-18C
STRAIN RELIEF ZIP TIES
(BOTH ENDS)
UNIT WITH COVER REMOVED
TO SHOW WIRE INSTALLATION
PAIR A: 1,2
PAIR B: 3,4
PAIR C: 5,6
PAIR D: 7,8
PAIR E: 9,10
PAIR F: 11,12
888-727-1951
www.zap-tech.com
WIRE ENTRY GROMMET
(BOTH ENDS)

Advertisement

loading

Summary of Contents for Zap-Tech HW Series

  • Page 1 INSTALLATION: © Copyright 2013, Zap-Tech Corporation all rights reserved. Zap-Tech protectors should be installed in series with the incoming communication line at the port of the equipment being protected. The protector's grounding wire must be connected to the chassis ground of the protected equipment.
  • Page 2 IMPORTANT: MAKE SURE THE INCOMING AND OUTGOING CABLE SHIELD DRAIN WIRES ARE CONNECTED COMMON WITH THE PROTECTOR GROUND WIRE AND EQUIPMENT CHASSIS AND FACILITY EARTH GROUND. CAUTION: TO PROPERLY PROTECT THE GPS INTERFACE, ZAP-TECH PROTECTOR P/N: 40-422-001 MUST BE INSTALLED AT THE ANTENNA END OF THE INSTALLATION. STRAIN RELIEF ZIP TIES 14 AWG GROUND WIRE, 8.0”...