Characteristics
Alarm verification up to 7 seconds for real fire confirmation and avoid false alarm form environment interference.
Zone test mode to perform alarm and fault functional test.
Each zone has a separate disable function.
Fault indications for wire disconnection, unstable AC power, battery short circuit or disconnection and internal
PCB unplug.
5-QA12 only 1 up to 5 zone detector
QA12 could 10 up to 80 zone detector
Specification
Model
Power
Battery Capacity
Charging voltage & current
Loop voltage & current
External resistance
# of heat detectors connected
# of smoke detectors connected
# of fire indicating lamp connected
# of bell connected
Relay output
End of Line Resistor
Material
Color
Dimensions (mm) H x W x D
CEMEN QA12 & 5-QA12 2021
5-QA12 & QA12
Model
Manufactured :
HORING LIH INDUSTRIAL CO.,LTD
MADE IN TAIWAN
QA12
QA12
5-QA12
220V AC, 50/60HZ *Others also available
24VDC; short circuit under 5V
30 / zone Except electronic - type (Horing Lih Product)
30 / zone Except Mechanical - type (Horing Lih Product)
30 / zone (Horing Lih Product)
Contact rating (24 VDC 3A)
Pearl gray *Others also available
5 zone : 320 x 250 x 100
FIRE ALARM EQUIPMENT
24V/4Ah
28VDC 100mA ~ 400mA
Max.50
# of zone x 1.5
# of zone x 1.5
10k *One per zone
1.2 mm steel plate
10
zone : 450 x 330 x 130
20
zone : 550 x 330 x 130
30
zone : 680 x 380 x 150
40 / 50 zone : 950 x 420 x 150
60 ~ 80 zone : 1300 x 420 x 170
QA12
FIRE ALARM SYSTEM