Broyce Control P50ELR Series Quick Start Manual

Earth leakage relay – type a

Advertisement

Quick Links

Terminal Protection
to IP20
FUNCTION DIAGRAM
SETTING DETAILS
1. Trip setting adjustment (I∆n) in Amps
2. Time delay adjustment (∆t) in seconds
3. "TEST" button
4. Green "Power On" (Normal) LED indication
P50ELR-10 shown in example
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com
The Information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user's own risk.
Panel (Flush) Mount enclosure
Adjustable side clips provide quick method of mounting (no fixing screws required)
6 models available (3A, 10A or 30A with either SPDT or 2 x N.O. relay outputs)
Designed to monitor and detect true RMS leakage current in conjunction with separate toroid
Adjustable Trip level (I∆ ∆ ∆ ∆ n) and Time delay (∆ ∆ ∆ ∆ t) settings
Separate "Test" and "Reset" push buttons
Toroid open and short-circuit detection forces unit to trip (Red LED flashes during this
condition)
Relay energises when fault current exceeds set Trip level
LED indication for Power Supply, Leakage Current and Trip status
SPDT relay output - 8A
2 x N.O. relay outputs - 3A
Single supply voltage option – 115V or 230V AC
Compliant with IEC 60755
5. Green "Leakage Current" LED indication
6. Red "Tripped" (Fault) LED indication
7. "RESET" button
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England
Type: P50ELR* & P50ELR*/2
(Part No. P50ELR-3, P50ELR-10 and P50ELR-30)
(Part No. P50ELR-3/2, P50ELR-10/2 and P50ELR-30/2)
INSTALLATION AND SETTING
BEFORE INSTALLATION, ISOLATE THE SUPPLY.
Remove the P50ELR from the packaging.
Lift the raised part of the side clip and slide towards the rear of the
housing to remove. Carry this out on both sides.
Insert the P50ELR in to the panel cut-out and fit the side clips back
on to the housing.
Slide the clips towards the front of the unit until they come in to
contact with the reverse side of the panel. The unit is now secured
in place.
Connect the wires to the rear terminals as required following the
diagram shown on the next page and for the relevant model shown.
Ensure the Auxiliary supply voltage to be connected to terminals 1
and 8 matches the rating of the product.
Setting up
The unit should be set according to the requirements of the
application.
Applying power
Apply power and the green "Power on"
Assuming no fault present, the output relay(s) will remain in the de-
energised state.
Prior to a fault occurring, the LED bargraph
I∆n being detected (the display is scaled between 25, 50, and 75%
of the actual trip level). After all 3 LED's have illuminated and the
unit trips due to an excessive fault current, the red "tripped"
will illuminate.
Fault simulation (Test mode)
The unit can be placed into a fault condition by pressing the "Test"
button
on the front of the unit. The output relay(s) will energise.
Press the "Reset" button
output relay(s) revert back to the de-energised state.
The unit can also be reset by interrupting the power supply.
To satisfy regulations, it is recommended that the device be tested
periodically to ensure correct operation.
Troubleshooting
If the unit fails to operate correctly check that all wiring and
connections are good.
Note:
The operating function of this unit is classed as a Type A
tripping is ensured for residual sinusoidal alternating currents and
residual pulsating direct currents, whether applied suddenly or slowly
rising. Additionally, this unit is protected against nuisance tripping.
This unit will also satisfy the requirements for Type AC devices which
only need to detect residual alternating currents.
Earth Leakage Relay – Type A
* -3, -10 or -30
LED will illuminate.
will indicate the % of
on the front to reset the unit. The
for which
P50ELR-4-A.DOCX
LED
Page 1 of 2
1806

Advertisement

loading

Summary of Contents for Broyce Control P50ELR Series

  • Page 1 This unit will also satisfy the requirements for Type AC devices which only need to detect residual alternating currents. P50ELR-10 shown in example Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England P50ELR-4-A.DOCX Page 1 of 2 Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com 1806 The Information provided in this literature is believed to be accurate (subject to change without prior notice);...
  • Page 2 Where * refers to product current rating, i.e. 3, 10 or 30 • CONNECTION DIAGRAM • DIMENSIONS Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England P50ELR-4-A.DOCX Page 2 of 2 Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com 1806...

This manual is also suitable for:

P50elr /2 seriesP50elr-3P50elr-10P50elr-30