CEP 6506GU/G, 8706GU/G
SPECIFICATION
These installation and operation instructions
apply to the following temporary power
branch distribution system components. Do
not discard these instructions, save for future
Reference.
PORATBLE POWER
DISTRIBUTION UNITS
These units are rated for 50 amps, 125/250
VAC, Single Phase. The max. ampacity for the
50 amp unit is 100A @ 120V. The 20 amp, 120
volt outlets are individually protected by circuit
breakers and GFCI circuit modules.
Model
Number
6506GU, 8706GU
6506G, 8706G
INTRODUCTION
CEP temporary power distribution units equipped
with GFCI products will protect you from
electrocution hazards resulting from ground
faults. Ground faults are current leaks and can
result in electric shock. Currents of only 60/1000
of an ampere can be fatal. The GFCI protection
provided by CEP temporary power distribution
units significantly minimizes shock hazards. CEP
temporary power distribution units,
Temporary branch power distribution unit
with Ground fault protection for personnel
Installation and Operating Instructions
20 Amp
Receptacle
U-Ground
Twist-Lock
which are UL listed as Class A, Group I
interrupters, respond to fault currents as low as
3-6 milliamperes, and will shut of the current
within 1/40
of a second. The temporary power
th
distribution unit is designed to provide protection
against electrical shock hazards due to line-to-
ground faults. Although the GFCI Module does
not eliminate the hazard of a shock, it does limit
the duration of the shock to a period considered
safe for normally healthy persons.
GFCI Modules will provide protection against
ground faults only. They will not protect against
overloads or short circuits. There is no known
device that will guard against the electrical shock
hazard resulting from contact with both the "hot"
and neutral wires of the electrical circuit.
ELECTRICITY IS DANGEROUS.
EVEN WHEN SAFETY DEVICES ARE
PRESENT, HANDLE WITH CARE AND USE
REASONABLE CAUTION.
LET CAUTION PREVAIL
The CEP temporary power distribution unit is
designed to be used on a grounded electrical
supply system. It will not operate when supplied
from a power source which is not grounded.
Over-current protection of the proper rating,
according to the National Electric Code, Article
240, must be used on the supply circuit feeding
the temporary power distribution units.

Advertisement

loading

Summary of Contents for CEP 8706GU

  • Page 1 CEP temporary power distribution units equipped LET CAUTION PREVAIL with GFCI products will protect you from The CEP temporary power distribution unit is electrocution hazards resulting from ground designed to be used on a grounded electrical faults. Ground faults are current leaks and can supply system.
  • Page 2 TEST PROCUDURE The module will trip when the faulted load is All Models reconnected. Inspect all tools, appliances and Connect the temporary power distribution unit to extension cords in the faulted load circuit, an appropriate power source. repairing or replacing any that are not in good CAUTION condition.
  • Page 3 MAINTENANCE & REPAIR CAUTION: Electrical power supply MUST BE OFF AND DISCONNECTED before and during any repair or maintenance. Repair and maintenance must be performed by a trained and competent electrician. WARNING: If any parts or components of this temporary distribution box appear to be missing, broken or show signs of damage, DISCONTINUE USE IMMEDIATLEY! Do not modify these devices in any way.
  • Page 4 Parts Breakdown for: 6506G/GU, 8706G/GU, 7506G/GU, 7706G/GU ID Part Number Description LID6G G BOX LID (Must have SN# for label) LEGG BOX LEG - PAINTED G SERIES FRAME7706G* RUGGED FRAME (for 8706 & 7706 Series) 6375H 50A 125/250V TL INLET- HUBBELL 6369H 50A 125/250V TL RECEPT- HUBBELL 7788...

This manual is also suitable for:

6506gu6506g8706g7506g7506gu7706g ... Show all