1 - APPLICATION :
Temperature regulation or limitation for liquids, gases or solids.
2 - DESCRIPTION :
-
Liquid dilatation thermostat with bulb and capillary of copper for reference 9030-02 and stainless steel for
reference 9030-03.
-
Potential-free inverter contact.
-
Breaking capacity : 16 A / 400 VAC.
-
Maximum operating voltage : 400 V.
-
Differential : 2.5% of full scale.
-
Connection by 6.35 Faston terminals.
-
Façade mounting or on support (inside case or box for instance).
3 - PRECAUTIONS FOR USE :
-
Handle the capillary with care. It must never be pierced as this could cause the final destruction of the equipment.
Allow a forming radius in excess of 5 mm.
-
Check that the material of the bulb and capillary is compatible with the product being tested in the event of it
being in direct contact with it.
4 - ASSEMBLY AND ELECTRICAL CONNECTION :
4 - 1 - ASSEMBLY :
-
On the support which will be receiving the thermostat (façade or attaching lug), form an 7 mm Ø hole
for accommodating the shaft of the knob and two 4 mm Ø holes (diametrically opposed) on a 22 mm Ø
radius centered on the shaft of the knob, ensuring that the equipment is turned as required (see diagram
below).
-
Insert the shaft of the knob in the hole provided for the purpose.
-
Place the pierced tightening washer on the support receiving the equipment then install the dial, making
sure it is properly aligned.
-
Install the two attaching screws.
VULCANIC S.A. - 48, rue Louis Ampère
Tél. (33) 01.49.44.49.20 - Fax (33) 01.49.44.49.41
OWNER'S MANUAL
LIQUID DILATATION THERMOSTAT
REFERENCE 9030 - 02/03
REFERENCE
Range
(°C)
9030 - 02
0 +100
9030 - 03
+50 +300
Bulb Ø
Bulb L
Capillary length
(mm)
(mm)
6
160
6
90
UT 9030 - 02/03 - A - Issued 04/03/98
(mm)
1000
1000
1/3

Advertisement

loading

Summary of Contents for VULCANIC 9030-02

  • Page 1 1 - APPLICATION : Temperature regulation or limitation for liquids, gases or solids. 2 - DESCRIPTION : Liquid dilatation thermostat with bulb and capillary of copper for reference 9030-02 and stainless steel for reference 9030-03. Potential-free inverter contact. Breaking capacity : 16 A / 400 VAC.
  • Page 2 Place the knob in line with its shaft. Install the bulb, generally in a thermometer well (for liquids and gases) or in a cylindrical housing (for solids) having an inside diameter slightly greater than that of the bulb so as to preserve good thermal conduction.
  • Page 3 6 - SERVICING : Periodically (at least once each year) make sure that : The Faston terminals are tight and in place When testing a pollutant fluid, clean the bulb (and the thermometer well if necessary) without damaging it in the eventuality of their being a deposit in the well (fouling could distort the temperature measurement because of the obstruction of thermal exchange).