Specifi cations
Power Supply
24 VAC/VDC (18-28 V)
Power Consumption
160 mA
Output Operations
Isolated solid-state switch and
Analog signal output combination
Output Rating (Switch) 1 A @ 240 VAC maximum (general use)
Response Time
<500 ms for 5% over setpoint
(Switch Output)
<200 ms for 50% over setpoint
<150 ms for 100% over setpoint
Hysteresis
5%
Setpoint Range
ATS1: 1-50 A (adjustable)
ATS2: 4-200 A (adjustable)
Setpoint Adjustment
Single turn potentiometer
Setpoint displayed on sensor
Analog Signal
4-20 mA - 500 ohm max impedance
0-5 VDC -5K ohm min impedance
0-10 VDC -5K ohm min impedance
Response Time
Average responding
(Analog Output)
<250 ms 90% step change
<500 ms 99.5% step change
<2000 ms 100% step change
Accuracy
+/-1%, FS
Isolation Voltage
Tested to 1480 VAC
Frequency Range
40-100 Hz
Sensing Aperture
0.75" (19.1 mm)
Operating
-4 to122°F (-20 to 50°C)
Environmental
Surrounding air
0-95% RH, Non-condensing
Pollution Degree 2
Altitude to 6561 ft (2000 meters)
Listings
UL/cUL, CE
Know Your Power
3511 Charter Park Drive, San Jose, CA 95136
Phone: 800-959-4014 or 408-871-7510
Fax: 408-871-7515
sales@nktechnologies.com, www.nktechnologies.com
Model Number Key
ATS 1- 420 - NOAC - 24U - FL
CASE STYLE:
FL - Solid-Core
POWER SUPPLY:
24U - 24 VAC/VDC
OUTPUT:
NOAC -
Normally Open solid-state contact,
1 A @ 240 VAC maximum
NCAC -
Normally Closed solid-state contact,
1 A @ 240 VAC maximum
ANALOG OUTPUT:
420 - 4 to 20 mA
005 - 0-5 VDC
010 - 0-10 VDC
RANGE:
1 - 0-50 Amps AC (setpoint 1-50 A)
2 - 0-200 Amps AC (setpoint 4-200 A)
SENSOR TYPE:
ATS - AC current operated switch, LED display of the
adjustable trip point.
For products intended for the EU market, the following is ap-
plicable to the CE compliance of the product:
The ATS Series may comply with EN 61010-1 CAT III 300 V
max line-to-neutral measurement category. If insulated cable is
used for the primary circuit, the voltage rating of the measure-
ment category can be improved according to the characteristics
given by the cable manufacturer.
Use twisted pair for all connections.
24 Volt AC or DC Power Supply
Fuse at 5 amps maximum
Overvoltage Category I
Caution! Risk of danger
Safe operation can only be guaranteed if the
transducer is used for the purpose for which it was
designed and within the limits of the technical speci-
fi cations When this symbol is used, it means you
should consult all documentation to understand the
nature of potential hazards and the action required to
avoid them.
Caution! Risk of electrical shock
When operating the transducer certain parts may
carry hazardous live voltage (e.g. Primary conductor,
power supply). The transducer should not be put into
operation if the installation is not complete.
INSTRUCTIONS
ATS SERIES
AC Current Operated Relay
Single Range with Solid State Output and
Analog Signal
Quick "How To" Guide
1. Mount the sensor to a suitable surface if required.
2. Run the wire to be monitored through aperture.
3. Connect output wiring.
A. Use 30-12 AWG copper conductors only.
B. Ensure the power supply voltage matches the
model you are installing.
C. Energize the power to the sensor.
4. Adjust Setpoint.
A. LED will display the RMS value of AC current
which will cause the output to change state.
B. Turn the potentiometer until your target current
value is displayed.
5. Analog Signal Output
A. The analog outputs are powered from the sensor
power source.
B. The signal is proportional to the sensor range
selected.
893020010 Rev 3

Advertisement

loading

Summary of Contents for NK TECHNOLOGIES ATS Series

  • Page 1 CE compliance of the product: Pollution Degree 2 2. Run the wire to be monitored through aperture. The ATS Series may comply with EN 61010-1 CAT III 300 V Altitude to 6561 ft (2000 meters) max line-to-neutral measurement category. If insulated cable is...
  • Page 2 Ensure at least one inch clearance exists between sensor and other magnetic ATS Series setpoint is adjusted using a a single turn poten- 1. Sensor is always tripped devices.

This manual is also suitable for:

Ats 1-420-noac-24u-fl