Digital Input/Output Interface Card "OPC-DIO"
Thank you for purchasing the digital input/output interface card "OPC-DIO". By installing digital input/output interface card
"OPC-DIO" on the FRENIC series, frequency settings can be specified with binary codes and BCD codes, output frequency
and so on can be monitored with binary codes, and general-purpose input/output terminals can be expanded.
1. Applicable Inverters
Table 1 shows applicable inverter series.
2. Product Check
Check the following items.
(1) Ensure that the package contains the DIO
interface card and 2 screws (M3 x 8).
(2) Ensure that no damage such as abnormalities,
dents, or bending has occurred to the parts on the
DIO interface card during transport.
(3) Ensure that the "OPC-DIO" model name is
stamped on the top of the DIO interface card. (Fig.
2-1)
If you suspect the product is not working properly or if
you have any questions about your product, contact the
shop where you bought the product or your local Fuji
branch office.
3. Basic Connection Drawing
FRENIC-Series
L1/R
L2/S
L3/T
M1
(SEL)
I13
I12
(MSB)
I11
I10
I9
SW11
I8
I7
I6
I5
I4
I3
I2
I1
(LSB)
CM
Fig. 3-1 Basic Connection Drawing
Before starting installation and wiring, turn OFF the power and wait at least ten minutes. Mace sure that the LED monitor
and charging lamp are turned OFF. Further, make sure, using a multimeter or a similar instrument, that the DC link bus
voltage between the terminals P(+) and N(-) has dropped to the safe level (+25 VDC or below)
Otherwise, electric shock could occur.
Table 1 Applicable Inverter and ROM Version
Series
Inverter type
□□□
FRENIC-Ace
FRN
U
V
W
Ry
(MSB)
O8
Ry
O7
Ry
O6
Ry
O5
SINK
Ry
O4
SOURCE
Ry
O3
Ry
O2
Ry
(LSB)
O1
M2
Inverter capacity
□
□□□
E2
-
Full capacity
Screw attachment hole
Model
Fig. 2-1 Front of Card
4. Electrical Specifications
Table 4-1 Electrical Specifications List
Terminal
symbol
I1 - I13
O1 - O8
- 1 -
Instruction Manual
ROM version
0300 or later
Removal knob
SW11
Screw attachment hole
Fig. 2-2 Back of Card
Item
Operating
ON level
voltage
OFF level
(SINK)
Operating
ON level
voltage
OFF level
(SOURCE)
Operating current at ON
(when input voltage 0 V)
Allowable leakage current at
OFF
ON level
Operating
voltage
OFF level
Maximum current at ON
Leakage current at OFF
CN1
Specification
Min.
Max.
0 V
2 V
22 V
27 V
22 V
27 V
0 V
2 V
2.5mA
5mA
-
0.5mA
-
2 V
-
27 V
-
50mA
-