When using electrical equipment and this lighting device basic safety precautions should be followed at all times
WARNING: Risk of Electric Shock. Disconnect power at fuse or circuit breaker before installing or servicing
WARNING: AC power must be off before proceeding with assembly or installation of emergency driver.
IMPORTANT: For use with non-dimming LED fixtures up to 40W. For use with LED fixtures that utilize 0-10V dimming that are above 40W, but this inverter will be limited
to 40W (including driver).
IMPORTANT: An un-switched AC power source of 100Vac to 277Vac is required. This device is designed for use in fixtures listed for dry , damp and wet locations.
CAUTION: Make sure all electrical connections conform to the National Electrical Code and all applicable local regulations.
CAUTION: Do not let power supply cords touch hot surfaces.
CAUTION: Do not mount near gas or electric heaters.
CAUTION: Use within grounded, UL Listed, damp location rated fixtures and case should be grounding.
CAUTION: The equipment is intended for ordinary locations and for permanent installation into one or more Listed emergency luminaires.
CAUTION: Battery is rechargeable LiFePO4 type and must be recycled or disposed of properly.
Do not use this emergency driver with accessory equipment other than recommended by manufacturer; failure to follow these instructions may cause an unsafe
condition. Servicing should only be performed by qualified service personnel. Do not use this emergency driver for other than intended use. Not suitable for high-risk
task area lighting. Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
IMPORTANT: The output EM power will not exceed the max power rating of the battery.
IMPORTANT: Indicator (LED light) illuminated indicates battery in charge mode when AC power is applied. It is recommended and required by applicable code to test
emergency ballast to ensure proper function of the system; push the test switch every thirty (30) days to ensure the emergency driver is functioning by illuminating the
light source. Conduct a ninety (90) minutes discharge test one (1) time per year; LED light source should be illuminated for a minimum of ninety (90) minutes .
TESTING SYSTEM: The emergency battery requires a charge minimum of one (1) hour before testing the
circuit. A full charge requires twenty four (24 Hours) .
Make sure that the luminaire used meets the voltage and current requirements in the Product Information List and the
illumination requirements in NFPA101.
Ensure there will be sufficient light output in the end application. Estimate the egress lighting illumination levels by doing the following:
1.
Find the efficacy of the LED load. This can be provided by the luminaire manufacture. This number will be given in lumens per watt
(lm/w). It is the installer's responsibility to validate the luminaire manufacturer's efficacy data. This can be accomplished by direct
measurement, by review of independent 3rd party test data (UL, ETL, etc.), accessing a public database of 3rd party data (such as
Design Lights Consortium, www.designlights.org), or other comparable means.
2.
Lumens can be calculated by multiplying the output power of the backup nano inverter by the efficacy of the LED load. In many
cases the actual lumen output in emergency mode will be greater than this calculation gives, however it will provide a good
estimate for beginning the lighting design of the system.
3.
Using the results of this calculation and industry standard lighting design tools, calculate the anticipated illumination levels in the
path of egress.
Lumens In Emergency Mode = Lumens per Watt of Fixture * Output Power of Choosen Product
The following fixtures have been verified for use: NICOR HBC3 series
NOTE: This product has been designed to reliably interface with a wide selection of LED Drivers. However, compatibility cannot be
guaranteed with all current and future LED systems. Compatibility testing of the end-use system is suggested. Please contact the factory
with any questions.
PRODUCT INFORMATION LIST
Input Voltage :
Input Current :
Input Power :
Maximum Load Power :
Standby Power Draw :
Output Power :
NICOR, Inc. 2200 Midtown Place NE, Albuquerque, NM 87107 P: 800.821.6283 F: 800.892.8393 www.nicorlighting.com July 22, 2021 9:58 AM
PLEASE READ CAREFULLY AND FOLLOW ALL INSTRUCTIONS
SAVE THESE INSTRUCTIONS
_______________(Lumens) = __________________(lm/W) * 40(W)
100-277VAC 50/60Hz
0.2A Max
12W
300W
<0.8W
40W
EMB4001UNV**
INSTALLATION INSTRUCTIONS
IMPORTANT SAFEGUARDS
including but not limited to the following:
FOR YOUR OWN SAFETY

Advertisement

loading

Summary of Contents for NICOR LED EMB4001UNV Series

  • Page 1 Input Current : 0.2A Max Input Power : Maximum Load Power : 300W Standby Power Draw : <0.8W Output Power : NICOR, Inc. 2200 Midtown Place NE, Albuquerque, NM 87107 P: 800.821.6283 F: 800.892.8393 www.nicorlighting.com July 22, 2021 9:58 AM...
  • Page 2 DIM+ and discharge test. DIM- wires of the luminaire regardless of the use of any other sensors or control systems. Luminaire NICOR, Inc. 2200 Midtown Place NE, Albuquerque, NM 87107 P: 800.821.6283 F: 800.892.8393 www.nicorlighting.com July 22, 2021 9:58 AM...
  • Page 3 This limited warranty extends only to the first consumer purchaser, and is not transferable. A consumer wishing to invoke the terms of this warranty must first obtain a RGA number within 30 days of discovery of the defect, and return the product to NICOR for inspection. Once verified to be covered by this limited warranty, NICOR will, at its discretion, repair, replace or refund the purchase price of any product that does not conform to this limited warranty.

This manual is also suitable for:

Emb400Emb4001unvbk