FMX FTM-HT250-FA1 User Manual

Fan assisted heaters

Advertisement

Quick Links

E351779
FAN ASSISTED HEATERS
User Manual
WARNING
Read instructions before installing or operating
this device. Keep for future reference.
Installation should be done by qualified personnel
following all National, State, & Local Codes
Be sure to remove all power supplying this
equipment before connecting or disconnecting
wiring.
Only install the heater inside an electrical
enclosure, in vertical position with cables facing
down, and in the bottom half of cabinet.
FMX heaters are fitted with a dedicated ground
terminal, it must be connected with an adequate
ground circuit according to the local codes and
safety regulations.
A disconnection system must be installed upstream
of the heater.
Protection against access to live parts must be
covered by the installer.
Don't install in ambient conditions with excessive
moisture and dirt.
Installation position must be selected to ensure
good ventilation. Take care that any internal
components of enclosure do not obstruct air flow.
Do not mount near easily flammable materials.
Follow all technical data shown in this manual.
Customer is solely responsible for validating application, operation,
maintenance, and code compliance and other information and data
relating to the installation, operation, safety, and maintenance of all
components. There is no guarantee that this information is suitable for
your application, nor is there any manufacturer/supplier assumption of
responsibility for your product design, installation, testing, or operation.
Information herein is provided "as is" with no guarantee of any kind.
Every attempt has been made to ensure the accuracy and reliability of
the information provided in this document.
1 - DESCRIPTION
GENERAL DESCRIPTION
Fan assisted heaters are optimized to avoid
condensation or provide a minimum temperature
inside closed cabinets.
A green LED will illuminate when the heater is
turned on.
Heating
Model
Capacity
[W]
FTM-HT250-FA1
250
FTM-HT250-FA2
250
FTM-HT400-FA1
400
FTM-HT400-FA2
400
FTM-HT500-FA1
500
FTM-HT500-FA2
500
FTM-HT750-FA1
750
FTM-HT750-FA2
750
2 - DIN RAIL INSTALLATION
WARNING
Before installation, switch off the power
supply.
Keep a thermal safety clearance of 300
mm from the air outlet, 100mm from air
inlet, and 60mm from the sides.
Power
Current
Supply
Usage
[50-60Hz]
[A]
120VAC
2.4
240VAC
1.2
120VAC
3.8
240VAC
1.9
120VAC
4.8
240VAC
2.4
120VAC
7.2
240VAC
3.6

Advertisement

loading

Summary of Contents for FMX FTM-HT250-FA1

  • Page 1 2 - DIN RAIL INSTALLATION enclosure, in vertical position with cables facing down, and in the bottom half of cabinet. WARNING FMX heaters are fitted with a dedicated ground Before installation, switch off the power terminal, it must be connected with an adequate supply.
  • Page 2 3 - DIN RAIL REMOVAL WARNING Before removal, switch off the power supply. Heater surface is HOT. Allow heater to cool to a safe temperature before handling. Fan heaters feature a thermal cut out switch in case of fan failure. It prevents overheating which could damage the unit.

This manual is also suitable for:

Ftm-ht250-fa2Ftm-ht400-fa1Ftm-ht400-fa2Ftm-ht500-fa1Ftm-ht500-fa2Ftm-ht750-fa1 ... Show all