Installation Instructions for ELV/6M Range of Power Packs
Introduction
The ELV/6M range of Power Packs provides normal and/or emergency lighting via low voltage tungsten
halogen lamps. The range is designed to provide maintained or non-maintained emergency lighting to 12 Volt
low voltage tungsten halogen lamps. These can be used to convert low voltage downlighters or similar, to
provide maintained emergency lighting either by utilising the existing lighting transformer or their own integral
lighting transformer. The units use a 6 Volt battery, which will give 12% ballast lumen factor in emergency
mode. The pack is suitable for a maximum load of 50 Watts, with a choice of either VRLA (Valve Regulated
Lead Acid) or NiMH (Nickel Metal Hydride) battery packs.
General Instructions
1. Because of the low voltages and high wattage lamps used with tungsten halogen power packs the cable
sizes and runs must be selected to ensure that the volts drop is not excessive. In addition units using a
high frequency lighting transformer need to be mounted so as the run from the transformer to the lamp (via
the emergency lighting pack where appropriate) is kept short, which usually means within 2 metres.
Exceeding this length will result in reduced light output.
2. Maximum cable runs for non maintained operation, or where the lighting transformer is of the wire wound
style, can be obtained from the chart below.
MAXIMUM CABLE RUN (METRES) - EMERGENCY OPERATION ONLY
Lamp
1.0 mm²
Wattage
44 mV/A/m
10 W
10.9 m
20 W
5.5 m
35 W
3.1 m
50 W
2.2 m
3 When wiring to multiple luminaires from one unit, it is preferable to split the circuits as near as possible to
the ELV units, so as each cable is only carrying the load to one luminaire.
Installation Instructions
1. Position the unit close to the emergency luminaire by passing it through the luminaire aperture in the
ceiling. (NB all units can be mounted vertically or horizontally)
2. Connect the Unswitched (Battery Charging) 240V supply to the 'Unswitched 240V' terminals.
3. Connect the 12V lamp to the 'Output to 12V lamp' terminals. Ensure you do not exceed the maximum
Wattage rating of the unit.
4. For maintained use, either connect the supply from the Remote transformer to the 12V AC input terminals
for NM3 units, or connect the Switched (Lighting) 240V supply to the Switched supply terminals for M3
units. M3 units have their own inbuilt lighting transformer and do not need a remote lighting transformer.
5. Only connect the battery when the Unswitched supply is fully assured. Even though these units are
protected with a Deep Discharge Protection Circuit, the batteries can be damaged by being left in an
uncharged state for prolonged periods.
Sign and Date the Battery Commission Date when the battery is finally connected.
6. The LED indicator shows that the supply is healthy and the batteries are charging.
7. These ELV power packs have been tested in accordance with the relevant EMC regulations and are
declared to conform to CE requirements, when installed in accordance with these installation instructions
and the relevant European and British standards.
All the details and specifications shown in this leaflet are deemed correct at the time of print. The right to
modify equipment, change specifications and instructions at any time, without notice, is reserved as part of
Lite-Plan policy of continuous development and improvement.
Tel +44 (0) 1708 372 223
Issue 1208
CABLE SIZE (mm²) - VOLTS DROP (mV/A/m)
1.5 mm²
2.5 mm²
29 mV/A/m
18 mV/A/m
16.5 m
25.8 m
8.3 m
13.0 m
4.7 m
7.6 m
3.2 m
5.3 m
www.liteplan.com
4.0 mm²
6.0 mm²
11 mV/A/m
7.3 mV/A/m
43.5 m
65.6 m
22.0 m
33.3 m
12.5 m
19.0 m
8.7 m
12.9 m
Fax +44 (0) 1708 371 345
Page 1

Advertisement

loading

Summary of Contents for Liteplan ELV/6M Series

  • Page 1 Lite-Plan policy of continuous development and improvement. Tel +44 (0) 1708 372 223 www.liteplan.com Fax +44 (0) 1708 371 345 Issue 1208 Page 1...

This manual is also suitable for:

Elv/6m/mh/50 seriesElv/6m/50/nm3