Summary of Contents for Zeta Alarm Limited Fyreye MKII ZAZM-MI
Page 1
FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR INSTALLATION GUIDE General The Fyreye MkII Addressable Zone Monitor Module is supplied with a backbox for surface mounting. NOTE: The Zone Monitor Module is designed for indoor use only. This product is loop powered.
FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE Technical Specification Model ZAZM-MI Part Number 48-117 Operating Voltage 17 – 28V DC Quiescent Current 3.5mA Alarm Current (LED OFF) 12.6 mA Alarm Current (LED ON) 13.2 mA Isolating Current 7.3mA End of Line Resistor 6.2k...
Page 4
FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE Document No: GLT-235-7-1 Author: NRP Jones Page 4 Issue No: 010 Date: 10/05/2021...
Page 5
FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE Document No: GLT-235-7-1 Author: NRP Jones Page 5 Issue No: 010 Date: 10/05/2021...
Page 6
FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE Alternative Soft Addressing Option Using our hand held MkII programmer (Part No: 48-004), the unit can be addressed electronically. Step 1: Set all addresses to zero 0000000 Step 2: Connect leads to LOOP IN+ and LOOP IN- as shown below Step 3: Follow the procedure as described in the handheld programmer manual.
FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE Functional Test Data Command Bit Function Input Bit Function SELF TEST SELF TEST 0 = Normal 0 = Normal 1 = Test active 1 = Test active ENABLE ALARM LED ENABLE ALARM LED CONFIRMED 0 = Normal 0 = Normal...
FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE Faultfinding Problem Possible Cause No response or missing Incorrect address setting Incorrect loop wiring Fault condition reported Incorrect input wiring Capacitor not fitted with active EOL Detector removed Incorrect EOL Incorrectly fitted active EOL Analogue value unstable Dual address...