FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE
FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR
General
The Fyreye MkII Addressable Zone Monitor Module is supplied with a backbox for surface
mounting.
NOTE: The Zone Monitor Module is designed for indoor use only.
This product is loop powered. A loop load claulation must be performed to determine the
permissable quantity of ZAZM-MI per loop.
Model No: ZAZM-MI
Surface Mounting
1.
Mount the backbox as required and install all cables for termination.
2.
Set the address of the unit as shown on page 3.
3.
Terminate all cables.
4.
Gently push the completed assembly towards the back box until the mounting
holes are aligned and secure with the two mounting screws provided. DO NOT
OVERTIGHTEN.
Isolator Module
The Zone Monitor Module is fitted with a bi-directional short-circuit isolator and will be
unaffected by loop short-circuits on either loop input or output.
Document No: GLT-235-7-1
Issue No: 010
INSTALLATION GUIDE
Fyreye MkII Addressable Zone Monitor Module With Isolator
Page 1
Author: NRP Jones
Date: 10/05/2021

Advertisement

Table of Contents
loading

Summary of Contents for Zeta Alarm Limited Fyreye MKII ZAZM-MI

  • Page 1 FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR INSTALLATION GUIDE General The Fyreye MkII Addressable Zone Monitor Module is supplied with a backbox for surface mounting. NOTE: The Zone Monitor Module is designed for indoor use only. This product is loop powered.
  • Page 2: Wiring Details

    FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE Wiring Details All wiring terminals will accept solid or stranded cables up to 2.5mm Typical Wiring Diagram Document No: GLT-235-7-1 Author: NRP Jones Page 2 Issue No: 010 Date: 10/05/2021...
  • Page 3: Technical Specification

    FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE Technical Specification Model ZAZM-MI Part Number 48-117 Operating Voltage 17 – 28V DC Quiescent Current 3.5mA Alarm Current (LED OFF) 12.6 mA Alarm Current (LED ON) 13.2 mA Isolating Current 7.3mA End of Line Resistor 6.2k...
  • Page 4 FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE Document No: GLT-235-7-1 Author: NRP Jones Page 4 Issue No: 010 Date: 10/05/2021...
  • Page 5 FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE Document No: GLT-235-7-1 Author: NRP Jones Page 5 Issue No: 010 Date: 10/05/2021...
  • Page 6 FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE Alternative Soft Addressing Option Using our hand held MkII programmer (Part No: 48-004), the unit can be addressed electronically. Step 1: Set all addresses to zero 0000000 Step 2: Connect leads to LOOP IN+ and LOOP IN- as shown below Step 3: Follow the procedure as described in the handheld programmer manual.
  • Page 7: Troubleshooting

    FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE Functional Test Data Command Bit Function Input Bit Function SELF TEST SELF TEST 0 = Normal 0 = Normal 1 = Test active 1 = Test active ENABLE ALARM LED ENABLE ALARM LED CONFIRMED 0 = Normal 0 = Normal...
  • Page 8: Fault Finding

    FYREYE MKII ADDRESSABLE ZONE MONITOR MODULE WITH ISOLATOR - INSTALLATION GUIDE Faultfinding Problem Possible Cause No response or missing Incorrect address setting Incorrect loop wiring Fault condition reported Incorrect input wiring Capacitor not fitted with active EOL Detector removed Incorrect EOL Incorrectly fitted active EOL Analogue value unstable Dual address...