Zircon ZIRCONLC1 Installation, Operating, & Maintenance Instructions

1 & 2 zone fire alarm panels

Advertisement

Quick Links

To reset from alarm enter code
and press
SOUNDERS ON/OFF
followed by
RESET
LED flashing
LED Continuous
DISABLED
FAULT
These instructions cover the:
ZIRCONLC1 :
One-Zone Conventional Fire Panel
ZIRCONLC2 :
Two-Zone Conventional Fire Panel
The panels are designed to meet the requirements of EN54-2:1996 &
EN54-4:1996
¤
Technical helpline:
This publication is issued to provide outline information only and is not deemed to
form part of any offer or contract. Our policy is one of continual improvement and
we reserve the right to vary details without prior notice.
General Description
Options included that are covered by EN54
ÿ
Test Condition (10.0)
ÿ
Fire Alarm Devices (7.8)
Ancillary functions provided but not required by EN54
ÿ
Class change
ÿ
Repeater
Technical Specifications
Power Supply requirements
230Vac +10 - 15% 50Hz
Maximum Power consumption 50VA
Fuse rating - T125mA
The mains supply should be carefully wired using flat twin and earth of not
2
less than 1mm
between the mains connector block and an externally
mounted secure switched fused spur outlet with contact separation of at
least 3mm. The switched spur unit should be fused with a 2A fuse.
Battery
24 Hour standby
1 x 12 V 2.6 Ah (minimum)
Fuse rating - F1.6A
Weight
4.2 Kg (including 2.6 Ah battery & carton) approx.
61640610 issue 6_8/02
1 & 2 Zone Fire Alarm Panels
System installation, operating &
maintenance instructions
FIRE
POWER ON
GENERAL FAULT
FIRE
SYSTEM FAULT
FAULT / DISABLED
TEST
1
2
ZONE
DISABLE
POWER FAULT
SOUNDER
FAULT/DISABLE
1
2
3
4
5
SUPERVISOR
MODE
Sounders
Mute
Reset
Advance
Select /
ON/OFF
Panel
Lamp Test
+44 (0) 1268 56 3256
or 3.3Ah (maximum)
Detection Circuits
20 smoke or heat detectors maximum per zone. (A maximum quiescent
current of 1.2mA is allowed per zone circuit)
30 Call Points maximum per zone.
Alarm Sounder Circuits
300mA total through 2 circuits.
Nominal Voltage 25.3V (+2.7V / -1V)
Fuse rating - F315mA
Auxiliary 24V Supply
This is specifically not for fire protection devices.
50mA maximum.
Nominal Voltage 25.3V (+2.7V / -1V)
Fuse rating - F125mA
Auxiliary Relay
Volt free change over contacts rated at 1A 30VDC Fuse Rating 1A
Note, the Auxiliary relay is configured as a fault relay, as standard (EN54
requirement), however the relay can be configured as an auxiliary fire
relay, by moving a jumper link from the fault position to the fire position on
the back of the PCB.
AUXILIARY RELAY
FAULT
FIRE
The N/C and N/O contacts change position, when the jumper is moved to
the fire position.
Class Change
Activated by using volt free N/O contacts between the -ve of AUX 24V
output and the CLASS CHANGE output.
Cabling
Unless otherwise recommended, and taking into account voltage drop, not
2
less than 1mm
is recommended. Sounder circuits should use cable that
is fire proof. All cabling should be earthed to the metal back box via the
cable gland. Conductors carrying fire alarm power signals should be
separated from conductors used for carrying other systems.
Installation information
Installation of this product must be carried out using the information
given in this leaflet by a qualified electrician.
Warning: Before installation ensure the electrical supply is
isolated.
Installation of this product must be carried out in accordance with the
requirements of BS5839 Pt1 and EN54.
Mounting location considerations
The fire alarm control panel should be mounted near to a permanent, low
fire risk, Entry / Exit, for easy access by the Emergency Services. The
panel should not be mounted in direct sunlight, or in a place where the
ambient temperature is above 30 ºC (86 ºF).
Mains must not be capable of being accidentally disconnected and the
isolating switch should clearly state:
FIRE ALARM - DO NOT SWITCH OFF
Caution: Anti static precautions should be taken when
installing the panel.
1
2
3
NC
C
NO
NO
C
NC
1

Advertisement

Table of Contents
loading

Summary of Contents for Zircon ZIRCONLC1

  • Page 1 Volt free change over contacts rated at 1A 30VDC Fuse Rating 1A These instructions cover the: ZIRCONLC1 : Note, the Auxiliary relay is configured as a fault relay, as standard (EN54 requirement), however the relay can be configured as an auxiliary fire...
  • Page 2: Mounting Instructions

    1 & 2 zone - Fire alarm panels Mounting instructions Wiring mains and battery Configure the Auxiliary relay link for fire or fault operation. The factory default setting is activation on fault. PCB TERMINAL CABLE ENTRY BATTERY BLOCKS POINTS TOP AND REAR Battery Locating leads...
  • Page 3: External Wiring

    1 & 2 zone - Fire alarm panels External wiring red or orange The external wiring should now be connected to the fire panel. Fit an active end of line if detectors are also connected Active end of line to the zone circuit. The fire panel is supplied with End Of Line Resistors for the zone and black sounder circuits, these must be transferred to the last device in the circuit.
  • Page 4 1 & 2 zone - Fire alarm panels Operating instructions Red indicators Green indicator Amber indicators FI E To reset from alarm enter code and press POWER ON SOUNDERS ON/OFF followed by GENERAL FAULT FIRE RESET SYSTEM FAULT FAULT / DISABLED TEST ZONE DISABLE...
  • Page 5: Disable Sounders

    1 & 2 zone - Fire alarm panels Disable Zone Disable Sounders Repeat points 1-3 (from the Test zone procedure listed above). Repeat points 1-3 (from the Test zone procedure listed above), progressing through all the Test & Disable zones features until the “Sounder Fault / Disable”...
  • Page 6: Maintenance Information

    1 & 2 zone - Fire alarm panels Maintenance Information All the components of this panel have been selected for the intended purpose, and are expected to operate within their specification when the environmental conditions outside the panel comply with class 3k5 of IEC 721-3-3.
  • Page 7 1 & 2 zone - Fire alarm panels Fire panel event record Date Weekly Qtly. Event Action Required Completed Name 61640610 issue 6_8/02...
  • Page 8 1 & 2 zone - Fire alarm panels Date Weekly Qtly. Event Action Required Completed Name 61640610 issue 6_8/02...