Liteplan CE1S/2W/M3 Series Assembly Instructions

Advertisement

Quick Links

CE1S/2W/M3/**
CE1S/2W/ST/**
CE1S/3W/DALI/**
Technical Specification:
-
Supply Voltage: 220-240V AC 50/60Hz
-
Insulation Class: II
-
Ingress Protection: IP41
-
Emergency Duration: 3 hours
-
Light Source: for M3 and ST version 2W LED
for DALI version 3W
-
Battery 6.4V 1.6Ah LiFEPO4 for M3 & ST
Battery 9.6V 1.5Ah LiFEPO4 for DALI
-
Battery Recharge Time: 12h
-
Max Battery Temperature: 55°C
-
Ambient Temperature: 0 - 40°C
-
Viewing Distance: 25m
-
Charge indicator: Green / Red LED
-
Deep Discharge Protection DDP
-
Self-Test & DALI versions available
-
Surface assembly (wall, ceiling)
-
Assembly indoors to flat surface
-
Polycarbonate body, Plexi Glass
-
Maintained or Non-Maintained Operation
Important:
It is recommended that the unit is installed by a competent person
ensuring the installation complies with the necessary standards. The
company accept no responsibility for incorrect installation, operation
or maintenance. The unit requires an unswitched supply for charging
the battery and a switched supply for a maintained unit. After
installation of the fitting, the battery must be charged for 24 hours.
LED indication Chart
Testing / Commissioning:
Ensure the load is connected
Enter the commissioning date on battery pack and connect the
battery
Switch on the unswitched supply – Check that the green charge LED
illuminates
Switch on the maintained supply – Check that the fitting illuminates as
normal
Switch off the maintained supply
Switch off the unswitched supply – Check that the green charge led
extinguishes and the fitting illuminates
Switch on the unswitched supply
It is recommended that the batteries are renewed every 6 years.
The fitting is equipped with non-replaceable LED.
Self-Test Function:
A Function Test automatically runs every 28 days. During this test the
fitting is switched into emergency mode for 1 minute. During the test
the battery discharge current is checked.
A Full Duration Test automatically runs every 364 days. During this
test the fitting is switched into emergency mode for 3 hours . During
the test the battery discharge current and battery voltage is checked
CE1S fitting
Disassembling the CE1S fitting

Advertisement

loading

Summary of Contents for Liteplan CE1S/2W/M3 Series

  • Page 1 CE1S fitting CE1S/2W/M3/** CE1S/2W/ST/** CE1S/3W/DALI/** Technical Specification: Testing / Commissioning: Supply Voltage: 220-240V AC 50/60Hz Ensure the load is connected Insulation Class: II Enter the commissioning date on battery pack and connect the Ingress Protection: IP41 battery Emergency Duration: 3 hours Switch on the unswitched supply –...
  • Page 2 Connections for DALI version Assembly instruction Connections for Maintained, Self-Test and Non-Maintained versions Dimensions Mounting details Additional guidelines Guidelines for installation Ensure a permanent supply to connection L Ensure a switched supply connection L1 For Non-Maintained use only L, do not connect to L1 Ensure correct polarity of the battery The drawing in the fitting may vary to the actual product, connect as per label on fitting.