Description
Description
Technical Data
Measurement method
Input current
12 V Model
24 V Model
CE-Conformance
EMV-noise emission
EMV-noise withstanding
Cable gland
Clamping area
Operating voltage chooseable:
Output
Housing
Dimensions (w x h x d)
Article
Rain Detector 12 V
Rain Detector 24 V
Combined wall/mast mounting
bracket
Features
• Safe operation, electrolytic measurement principle
• Deposition can be detected as rain or snow
• Operating voltage 12 or 24 V DC/AC
• Large, heated sensor area for fast drying and operation in winter season
• Potential free contact output (Relay) 30 V/4 A
• Sensitivity and switching mode adjustable
• Universal wall/mast mounting bracket as accessories
Technical changes reserved
0141 0316-212 20.07.2020
Electrolytic AC measurements
60 mA, Heater 80 - 300 mA (PTC)
50 mA, Heater 40 - 180 mA (PTC)
2014/30/EU
EN 61000-6-3:2011
EN 61000-6-1:2007
M16 x 1,5
6,0 - 9,5 mm
12 V AC/DC ± 10%
24 V AC/DC ± 10%
output (relay) 30 V / 4 A,
NO / NC selectable
ABS, ingress protection IP54
80 x 82 x 58 mm
Art.-No.
REGME-12V
REGME-24V
REGME-WAHA
B+B Thermo-Technik GmbH | Heinrich-Hertz-Straße 4 | D-78166 Donaueschingen
Fon +49 771 83160 | Fax +49 771 831650 | info@bb-sensors.com | bb-sensors.com
Applications
• Nurseries, Agriculture
• Control of Ventilation panels
• Automatic switch for Blinds and Rolling windows
• Building instrumentation
• Weather stations
Functional description
The large sensor area reacts to rain or snow. The switch polarity and sen-
sitivity are adjustable. The optionally switched heater prevents freezing or
dew formation and accelerates drying. In the maximum sensitivity setting, the
device is also suitable for recognizing fog.
Application
The rain guard is fitted with a relay contact for switching low voltages up
to 30 V DC/AC which can be used to operate any switching device e.g. a
marking control device. Sensitivity can be adjusted within a wide range. The
device is provided with a heater for faster drying and snow recognition.
Mounting
Installation of the rain sensor unit should be carried out by only authorised
personnel. The applicable safety regulations should be followed! The Rain
Sensor can be installed on a wall/mast mounting bracket. If such accessories
are not used, care should be taken that the mounting angle is approximately
30 ° from horizontal. Mounting of the Rain Sensor should be done at a place
which is freely accessible for rain. Dripping water can adversely delay swit-
ching back or can lead to a permanent ON/OFF of the contacts.
Connection
After removing the sensor cover, the control cable is to be inserted in the
cable gland M16.Supply voltage is to be connected to the terminals VCC and
GND. Terminals NC, COM, NO are the potential free changeover contacts for
switching.
Precautions:
• The device is suitable only for low voltages and should not be operated
on mains supply !
• The relay contact is only suitable for low value signals and should not
come in contact with mains supply !
• The protection type is valid only with an intact, complete casing, cover
1 / 2

Advertisement

loading

Summary of Contents for B+B Sensors REGME

  • Page 1 OPERATION MANUAL Rain Detector REGME model 12 V AC/DC or 24 V AC/DC Description Description Applications • Nurseries, Agriculture • Control of Ventilation panels • Automatic switch for Blinds and Rolling windows • Building instrumentation • Weather stations Functional description The large sensor area reacts to rain or snow.