Download Print this page
DANLERS CZ HB ND 10VDC Installation Notes

DANLERS CZ HB ND 10VDC Installation Notes

Controlzapp high bay controls for 1-10vdc ballasts

Advertisement

Quick Links

Variants
DANLERS design and manufacture other ControlZAPP high bay variants, coded by
the following order codes:
CZ HB (xx)
Suitable for mains switching
CZ HB (xx) 1DALI
Suitable for DALI ballasts
Troubleshooting
The load will not switch on:
• The LUX setting as specified by the ControlZAPP App is set too low and is
inhibiting the switch.
• The moving body is not emitting more IR than the background.
(Person wearing insulating clothing in a warm environment)
• Person is too far from the PIR switch, see detection diagram.
• Person is moving unusually slowly (perhaps when testing).
• The control unit battery is not engaged (ON).
Switch RED dip switch next to the telejack connector on the CZ HB (xx) 10VDC
control unit towards the centre of the control (see diagram D).
The load switches on when nobody is present:
• Heater causing infra-red variations in a small cold room.
Resite the CZ HB (xx) 10VDC control away from heater.
• Please contact DANLERS for further technical support.
Precautions and Warranty
This product conforms to BS EN 60669-2-1, BS EN 55015 and BS EN 60730.
Please ensure the most recent edition of the appropriate local wiring regulations are observed
and suitable protection is provided (protected with the appropriate MCB) 1kV over voltage.
Please ensure that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
Please call for more information or a free catalogue, or visit our website.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
E-mail: sales@danlers.co.uk
Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
15/09/16
INS315 CZ HB (xx) 10VDC
ControlZAPP high bay controls for 1-10VDC ballasts
CZ HB ND 10VDC
CZ HB SP 10VDC
ControlZAPP high bay passive infra-red occupancy switches (PIR) can be mounted
directly onto solid ceilings or onto a range of different mounting boxes (diagram
A). These PIR switches incorporate a passive infra-red quad sensor to detect
movement of a warm body within their detection zone (diagram B) and a photocell
to monitor the ambient light level.
ALL adjustments are made via a freely downloadable ControlZAPP App
available from the DANLERS website.
If the control is set as PIR with LUX input, upon detecting movement, if the ambient
light is dark enough, the ControlZAPP device will turn the load ON. The ambient
threshold can be set to between approximately 30 lux to 1000 lux and infinite lux
(photocell inactive) via the 'Respond to Daylight' settings on the ControlZAPP App.
If no more movement is detected within a pre-selected time as determined by the
ControlZAPP App, then the ControlZAPP device will turn the load off. This 'Time
Off Timeout' or time lag can be set via the ControlZAPP App adjuster between
10sec and 23hrs 59min 59sec.
These high bay controls are available in three types - each with a particular
detection pattern which is optimised for particular applications.
CZ HB ND 10VDC: Narrow Detection version is ideal for covering storage aisles.
CZ HB SP 10VDC Spot Detection version is ideal for smaller areas,
such as the entrances to storage aisles.
CZ HB WD 10VDC: Wide Detection version is ideal for large open areas,
such as factories, sports halls and entrance halls.
Loading
The controls are suitable for switching and dimming 1-10VDC ballasts. They can
control up to 20mA, eg. 20 ballasts at 1mA (varies according to make and model of
ballasts). They can also switch up to:
• 10 amps (3000W) of resistive loads
• 6 amps (1500W) fluorescent lamps, high frequency or switch start,
incandescent or mains halogen lamps (recommended with integral safety fuse)
• 3 amps (750W) of electronic or wire wound transformers.
• 2 amps (500W) of low energy lamps: CFL, LED, 2D etc.
• 1 amp (250W) of fans or most metal halide lamps.
Start-up and default settings
When the control is powered up, it will take 1 minute for the circuitry to stabilise
(detection LED flashing) and ensure the output is off, the control will then enter its
Default Operating Mode.
Please Note: When in the Default Operating Mode the control is set up as an
occupancy switch with a 20 minute turn OFF timeout (time lag) and photocell
disabled.
Installation notes
CZ HB WD 10VDC

Advertisement

loading

Summary of Contents for DANLERS CZ HB ND 10VDC

  • Page 1 These high bay controls are available in three types - each with a particular detection pattern which is optimised for particular applications. CZ HB ND 10VDC: Narrow Detection version is ideal for covering storage aisles. CZ HB SP 10VDC Spot Detection version is ideal for smaller areas, such as the entrances to storage aisles.
  • Page 2 NOTE: ALL settings are adjusted by ControlZAPP App as specified in the then join device to mounting holes or pre-drill above - knock out knock out side ControlZAPP App User Guide (downloadable from the DANLERS website) pilot holes. central mounting hole mounting hole plate via mounting clips including: MODE settings, SCHEDULER settings and photocell settings and intelligent photocell calibration procedure.

This manual is also suitable for:

Cz hb sp 10vdcCz hb wd 10vdc