Download Print this page
olympia electronics KLD-30/ST/ADR Quick Start Manual

olympia electronics KLD-30/ST/ADR Quick Start Manual

Addressable self testing maintained emergency illumination signs

Advertisement

Quick Links

Legend installation-replacement
KLD-22/ST/ADR & KLD-30/ST/ADR
1
2
KLR-20/ST/ADR
1
2
3
4
Accessories for installation
(After request)
Α-2130: Accessory for ceiling (1m)
Α-2131: Accessory for ceiling (0,5m)
Α-2132: Accessory for ceiling (0,25m)
Α-2133: Accessory for wall mounting
Α-2136: Accessory for hanging installation (2,5m)
A-2520/PL/ST: Suspended ceiling base
Battery replacement
1. Disassemble the luminary.
2. Remove the battery connector and carefully remove the battery from its base.
3. Install a new battery of the same type and rating.
4. Assemble the luminary and power the device.
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
1: Maintained (*)
A: Including test device
B: Including remote test mode
C: Including inhibiting mode
E: With non-replacable lamp(s) and/or battery
F: Automatic test gear complying with IEC 61347-2-7 denoted EL-T
G: Internally illuminated safety sign
60: 1 hour duration
180: 3 hours duration
X 1
A B
C
E
F G
1
8 0
480: 8 hours duration
(*) Maintained operation: The luminary lights its illumination source, when it is powered by the mains power
supply or not.
Non Maintained operation: The luminary lights its illumination source, only in mains power supply's failure.
ATTENTION!!!
The light source of this luminary is not replaceable when the light source reaches its end of life the
whole luminary shall be replaced.
4
Technical Characteristics
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
SUPPLY CURRENT
U-OUT
Prated
Irated
MAX OPEN CIRCUIT VOLTAGE
EMERGENCY OUTPUT FACTOR (EoFx)
WIRE CROSS SECTION
MINIMUM POWER FACTOR
BATTERY (Ni-MH)
INSULATION BETWEEN SUPPLY & CONTROL TERMINALS
INSULATION BETWEEN SUPPLY & BATTERY CIRCUIT
BATTERY PROTECTION
MIN MAX. DISCHARGE VOLTAGE
MIN MAX. DISCHARGE CURRENT
MIN MAX. CHARGE CURRENT
TRICKLE CHARGE VOLTAGE/CURRENT
MAX CHARGE VOLTAGE
INDICATIONS
CHARGE TIME
MINIMUM DURATION
LIGHT SOURCE / OUTPUT MODE
LIGHT SOURCE LUMINOUS FLUX (MAINS / EMERGENCY)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
CONTROL GEAR MAX.TEMPERATURE: tc
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION (L x W x H)
WEIGHT
GUARANTEE
CONTROL GEAR WITH AUTOMATIC
TEST FUNCTION
LED Characteristics
MANUFACTURER
MODEL NUMBER
VOLTAGE RANGE
NOMINAL POWER
CONNECTIONS
TEMPERATURE
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of
warranty is specified in the official catalogue of Olympia Electronics and also in the technical
leaflet, which accompanies each product. This warranty ceases to exist if the buyer does not
follow the technical instructions included in official documents given by Olympia Electronics or if
the buyer modifies the goods provided or has any repairs or re-setting done by a third party,
unless Olympia Electronics has fully agreed to them in writing. Products that have been damaged
can be returned to the premises of our company for repair or replacement, as long as the
warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not
charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to
charge or not the buyer the transportation cost.
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
5
922502054_09_003
KLD-30/ST/ADR
KLD-22/ST/ADR
KLR-20/ST/ADR
220-240V AC / 50-60Hz
3.9W / 4.4VA
20mA
70V
1.5W
130mA
39V DC
1h: 3.4, 3h: 1.4, 8h: 0.2
0.08mm - 1.5mm
2
2
0.87
3.6V/1.5Ah
Basic insulation
Basic insulation
Deep discharge and overcharge protection / the control gear will recharge the battery normally after the test of 22.3
3 - 4.5V
1h (400-690mA), 3h (190-295mA), 8h (55-95mA)
20 - 120mA
4.4V / 40mA
4.9V
LED Charge, Lamp Fault LED, Battery Fault LED / Test Button
24 hours
1h / 3h / 8h Manually Selected (Default 3h)
LED / CONSTANT CURRENT
80lm / 1h: 250lm, 3h: 110lm, 8h: 15lm
IP54
EN 60598-1, EN 60598-2-22, ΕΝ 55015,
ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
o
5 to 40 C
o
58 C at BR1
Up to 95%
PC, Acrylic Plate
PC
310x35x216mm
260x35x180mm
260x35x170mm
955gr.
740gr.
560gr.
3 years (1 year for the battery)
KLD-30/ST/ADR
KLD-22/ST/ADR
KLR-20/ST/ADR
Olympia Electronics S.A.
2711195
11.2-13.2V DC
0.72
Built-in main board
45 °C max. across the board
Warranty
www.olympia-electronics.com
info@olympia-electronics.gr
922502054_09_003
European
manufacturers
KLD-22/ST/ADR
KLD-30/ST/ADR
KLR-20/ST/ADR
KLD-30/ST/ADR, KLD-22/ST/ADR
& KLR-20/ST/ADR
ADDRESSABLE SELF TESTING MAINTAINED
EMERGENCY ILLUMINATION SIGNS
M
ΝΜ
Duration
Light output
30m
22m
IP54
Maintained
Non
1h/3h/8h
250/110/15lm
maintained
Thank you for your trust in our products
Olympia Electronics - European manufacturer
ADR
20m
Addres-
sable

Advertisement

loading

Summary of Contents for olympia electronics KLD-30/ST/ADR

  • Page 1 F: Automatic test gear complying with IEC 61347-2-7 denoted EL-T Olympia Electronics reserves the right to repair or to replace the returned goods and to or not G: Internally illuminated safety sign 60: 1 hour duration charge the buyer depending on the reason of defection.
  • Page 2 Package contents After the desired installation follow the steps below Installation methods Luminaire Luminaire disassembly Insert the Wall mounting accessories power cable Ceiling mounting accessories >5mm Manual Set of Pictograms General These luminaries are used indoors (ta 40 C) where Automatic Autonomy Test emergency light is needed.

This manual is also suitable for:

Kld-22/st/adrKlr-20/st/adr