INSTALLATION INSTRUCTIONS FOR COMBUSTION AIR INDUCER REPLACEMENT KIT
(22F08; LB-112090E) USED ON KG/SG/ZG/LGH024-090 GAS PACKAGED UNITS
Shipping and Packing List
Package 1 of 1 contains:
1- Combustion air inducer assembly
1- Transformer
Bag assembly containing:
1-Gasket
7- #10 Sheet metal screws
2- 1/4" QC Piggy-back terminals
1- 1/4" QC Terminal
3- Wiring diagrams
Application
This kit is used to replace 460V, 2-speed combustion air
inducers with 230V inducers. A transformer is required for
proper operation.
WARNING
Improper installation, adjustment, alteration, ser­
vice or maintenance can cause property damage,
personal injury or loss of life. Installation and ser­
vice must be performed by a licensed professional
HVAC installer or equivalent, service agency, or the
gas supplier
Install and Wire T3 Transformer
1. Disconnect all power and shut off gas supply to unit.
2. Open the control and heat section access panels.
See figure 1, 2, or 3.
3. Install the supplied T3 transformer as shown in figure
4, 5, 6, or 7.
4. Connect wiring as shown in each figure. If no space
is available on K1 contactor, re-terminate the
transformer leads using the supplied piggy-back
terminals.
CAUTION
As with any mechanical equipment, contact with
sharp sheet metal edges can result in personal in­
jury. Take care while handling this equipment and
wear gloves and protective clothing.
PACKAGED UNITS KITS
AND ACCESSORIES
COMBUSTION AIR INDUCER
508153-01
2/2021
HEAT SECTION
HEAT SECTION
CONTROL
BOX
CONTROL
BOX
Page 1
REPLACEMENT KIT
KG/LGH UNITS
COMPRESSOR
MULLION
SECTION
FIGURE 1
SG UNITS
OUTDOOR
SECTION
FIGURE 2
ZG UNITS
HEAT SECTION
FIGURE 3

Advertisement

loading

Summary of Contents for Lennox 22F08

  • Page 1 COMBUSTION AIR INDUCER 508153-01 2/2021 REPLACEMENT KIT INSTALLATION INSTRUCTIONS FOR COMBUSTION AIR INDUCER REPLACEMENT KIT (22F08; LB-112090E) USED ON KG/SG/ZG/LGH024-090 GAS PACKAGED UNITS Shipping and Packing List KG/LGH UNITS Package 1 of 1 contains: COMPRESSOR 1- Combustion air inducer assembly...
  • Page 2 INSTALL T3 TRANSFORMER - LGH NOTE - IF NO SPACE IS AVAILABLE ON K1 CONTACTOR, RE-TERMINATE THE K13-7 LEAD DISCONNECTED TRANSFORMER LEADS USING THE SUPPLIED PIGGY-BACK TERMINALS FROM K1-L1 BLACK LEAD RELAY WHITE LEAD TO K1-L2 LEAD TO K1-L1 CONTACTOR FIGURE 4 Page 2...
  • Page 3 INSTALL T3 TRANSFORMER - KG A3-CMB-L1 LEAD FROM THE A3 IGNITION CONTROL WAS DISCON­ BLACK NECTED FROM K1-L1 TERMINAL LEAD ON THE K1 CONTACTOR IGNITION CONTROL WHITE LEAD TO LEAD TO K1-L1 K1-L2 NOTE - IF NO SPACE IS AVAILABLE ON K1 CONTACTOR, RE-TERMINATE THE TRANSFORMER LEADS USING THE SUPPLIED PIGGY-BACK TERMINALS...
  • Page 4 INSTALL T3 TRANSFORMER - ZG A3-CMB-L1 LEAD FROM THE A3 NOTE - IF NO SPACE IS AVAILABLE ON IGNITION CONTROL WAS DISCON­ K1 CONTACTOR, RE-TERMINATE THE NECTED FROM K1-L1 TERMINAL TRANSFORMER LEADS USING THE ON THE K1 CONTACTOR SUPPLIED PIGGY-BACK TERMINALS IGNITION CONTROL BLACK...
  • Page 5 INSTALL T3 TRANSFORMER - SG RELAY K13-7 LEAD DISCONNECTED FROM K1-L1 BLACK LEAD NOTE - IF NO SPACE IS AVAILABLE ON K1 CONTACTOR, RE-TERMINATE THE TRANSFORMER LEADS USING THE SUPPLIED PIGGY-BACK TERMINALS LEAD TO K1-L1 WHITE LEAD TO K1-L2 CONTACTOR FIGURE 7 Page 5...
  • Page 6 6- Connect jack/plug to combustion air inducer. Install Combustion Air Inducer 7- Replace heat access panel and connect power 1- Disconnect jack/plug from harness routed to and gas. Start unit as shown in unit installation combustion air inducer. instructions. 2- Remove screws securing combustion air inducer COMBUSTION AIR INDUCER to flue box.

This manual is also suitable for:

Lb-112090e