Vantage Hearth Q-ETS3 Installation

Thermostat communication station

Advertisement

Quick Links

V A N T A G E C O N T R O L S . C O M
1061 South 800 East • Orem, Utah 84097 • Telephone 801 229 2800 • Fax 801 224 0355
Overview
The Q-ETS3, WireLink™ and the STHERR101, RadioLink®
thermostat interface stations provide bi-directional
communication between a Vantage control system and the
HVAC system. Any button or time control using InFusion
Design Center or QLink software can be programmed to
change Setpoints, Operational Mode, Fan mode and
Occupied/Unoccupied settings on a Vantage thermostat.
Current set points, Indoor/Outdoor temperatures, Operational
Mode, Fan mode and Occupied/Unoccupied (status) may be
displayed on Vantage LCD TouchScreens. A Vantage Q-ETS3
or STHERR101 station and a Vantage thermostat are used
together, in a one-to-one ratio, to control HVAC systems.
Please completely read, the Vantage Communicating
Thermostat |Operating and Installation Manual in conjunction
with this instruction sheet. Click on the manual below:
Or visit:
http://dealer.vantagecontrols.com/
Note: Vantage Controls' Thermostat is warranted for one year.
This is in contrast with the 5 year warranty carried on most
Vantage products.
System Requirements
Each Vantage thermostat requires one Q-ETS3 or STHERR101
to interface with the Vantage Communicating Thermostat
Part # STAT.
Q-ETS3
Specifications
WireLink
3" x 1" x 0.375"
Dimensions HWD
76mm x 25mm x
10mm
0.8oz
Weight
23g
24V / 36V Station
Bus
Station Power
and
connections*
24Vac from
thermostat base
Station Count
0.36W on IC-24
Design Center
0.54W on IC-36
Station Count
1 WireLink Station
QLink
Status LED
Yes
Indicator
2C 16AWG, non-shield, <30pF per foot
Station Bus
Station Bus should be separated a minimum
Wiring
of 18" from other parallel communication
and/or high voltage runs.
Ambient
Operating
Temperature
Ambient
Operating
Humidity
STHERR101
RadioLink
4.5" x 1.5" x 0.75"
114mm x 38mm x 19mm
1.4oz
40g
24Vac from thermostat
base
1 RadioLink Station
1 RadioLink Station
Yes
32-95°F -or- 0-35°C
5-95% non-condensing
I N S T A L L A T I O N
Vantage Thermostat Communication Station— MODEL: Q-ETS3 & STHERR101
*CAUTION: 36V stations have a
Number sticker. Any Q-ETS3, not displaying this symbol,
should not be connected to a 36Volt Station Bus.
Software/Firmware
Vantage's Q-ETS3 & STHERR101thermostat interface stations
are compatible with InFusion Design Center software and
QLink software. NOTE: The Q-ETS3 requires QLink version 2.50
and Controller firmware version 5.70 or higher. The STHERR101
requires QLink version 4.0 - build 310 and Controller firmware
version 7.4 or higher. For new projects it is recommended that
firmware and software be kept to the most current release.
Station Connection
Installation of Vantage products should be performed or
supervised by a Certified Vantage Installer. The Q-ETS3
connects to the Vantage System Station Bus with the two
black wires labeled Station Bus. The Station Bus wire should
comply with the Vantage Station Bus wiring specification. The
STHERR101 connects to the Vantage System via a RadioLink™
enabled system.
Mounting the Q-ETS3 or STHERR101
The Q-ETS3 or STHERR101 may be mounted behind the
thermostat in a single gang box or may hang through a 1¾"
(4.44cm) hole in the wall. The Black wire X1 and Green wire
X2 attach to terminals labeled X1 & X2 of the thermostat sub
base. The Red wire 24V attaches to the R terminal (screw
terminals on right) of the thermostat sub base along with the
24V power source. The Q ETS3 or STHERR101 do not supply
power to the thermostat.
Please see the Vantage Communicating Thermostat |Operating
and Installation Manual for each of the following topics:
Configuration, Q-ETS3, WireLink™
Configuration, STHERR101, RadioLink®
Status LED Diagnostic Information for Q-ETS3 or
STHERR101
Thermostat Setup with InFusion
Thermostat Setup with QLink
External Sensors
Temperature Averaging
Globally Display Outdoor Sensor
In Design Center, click on Settings | Project Preferences |
Thermostat and the Global Sensor drop down list. Select the
thermostat that has the external sensor. In QLink Select Use as
the Globally Displayed External Sensor from the Thermostat
Station properties window. This will broadcast the value of the
external sensor to all other thermostats connected to the
Vantage System. If Use as the Globally Displayed External
Sensor is not checked, other thermostats on the system will
not display the outdoor temperature.
Occupied (formerly Auto(Day)) and Unoccuped (formerly
(Night)) Modes
Most Thermostat Functions only work when the thermostat is
in Occupied (formerly Auto(Day)) Mode. If the thermostat is in
Unoccupied (formerly Manual(Night)) mode, the thermostat
automatically changes to Occupied when a command is
received. However, it is possible to end any task with a
command to leave the thermostat in Occupied or Unoccupied
modes as desired.
symbol on the Serial

Advertisement

loading

Summary of Contents for Vantage Hearth Q-ETS3

  • Page 1 InFusion Design Center software and Current set points, Indoor/Outdoor temperatures, Operational QLink software. NOTE: The Q-ETS3 requires QLink version 2.50 Mode, Fan mode and Occupied/Unoccupied (status) may be and Controller firmware version 5.70 or higher. The STHERR101 displayed on Vantage LCD TouchScreens.