GENERAL DESCRIPTION
The patented* No. 84370-Series Pressure Sensor
contains a weather-proof, snap-acting valve operated
by pressure variation around the integral sensing
element. Depending upon model used, it vents or
blocks a pneumatic signal when the setpoint is
reached and is available with either automatic or
manual reset. The sensor has adjustable differential
(auto reset versions only) and setpoint, provision for
piped vent operation, and is field reversible. Setpoint
is virtually unaffected by control pressure change or,
in the case of piped vent versions, vent backpressure
change. In the auto reset versions, reset differential
can be changed without shifting setpoint.
For correct operation, control pressure must be
provided thru a .032" (.81 mm) diameter or smaller
orifice.
*Patent 3.986,524
MODELS AVAILABLE
84370 -
Table 1
Table 2
TABLE 1
SUFFIX
A
Direct Acting - Vents on Increase
B
Reverse Acting - Closes Vent on
Increase
C
Direct Acting - Vents on Increase
TABLE 2
SUFFIX
1
2
See Page 2 for SPECIFICATIONS.
Form No. P-2347, Rev. B
DESCRIPTION
SETPOINT RANGE - psi (bar)
5 to 25 (.345 to 1.724)
15 to 65 (1.034 to 4.482)
84370-A, C Series
Vents on Increase
(Direct-Acting)
RESET
Auto
Auto
ORDERING INFORMATION
Specify:
Manual
1. Model
2. Control Pressure - If not specified, sensor is set
using 30 psi (2.068 bar).
3. Setpoint - If not specified, set at minimum.
4. Differential (Automatic Reset models only) - If
not specified, set at standard.
5. Tagging Information.
1
Sales Manual Section 335
PRODUCT SPECIFICATION 84370 SERIES
Pressure Sensor
No. 84370-Series
84370-B Series
Closes Vent on Increase
(Reverse-Acting)
J.I.C. Symbols

Advertisement

loading

Summary of Contents for Robertshaw 84370 Series

  • Page 1 Sales Manual Section 335 PRODUCT SPECIFICATION 84370 SERIES Pressure Sensor No. 84370-Series GENERAL DESCRIPTION The patented* No. 84370-Series Pressure Sensor contains a weather-proof, snap-acting valve operated by pressure variation around the integral sensing element. Depending upon model used, it vents or...
  • Page 2: Specifications

    SPECIFICATIONS CONSTRUCTION Valve Housing: ....Anodized Aluminum Alloy Spring Housing: ......316 Stainless Steel. Pressure Assembly Housing: ....Stainless Steel. Pressure Assembly: ....Stainless Steel Bellows. Springs: ..........Stainless Steel. Process and Reset Pressure Characteristics: O-rings: ......Fluorocarbon and Neoprene. Minimum Diaphragms and Gasket: ..Neoprene and Buna N Maximum Standard...
  • Page 3 INSTALLATION (See Figure 1) CONNECTIONS: The sensor has three 1/8" - 27 NPT connections - MOUNTING: The No. 84370-Series Pressure Sensor may be one for control pressure, one for vent pressure, and one for case relief pressure. mounted in any position, although vertical (upright) is recommended.
  • Page 4 OPERATION - See Figure 2 With the lowering of process pressure below set- In the direct-acting models, process pressure point, the range spring forces the stem and sleeve pushes the stem against the range spring. The bellows toward the bellows head. In the automatic reset head moves toward the range spring and compresses models, the bellows head is stationary at this time the bellows due to the inlet port (control) pressure.
  • Page 5 MAINTENANCE - See Figure 4 WARNING: USE CARE WHEN Direct- and Reverse-Acting DISASSEMBLING, SPRING FORCES PRESENT. CAUTION: Do not subject O-rings, gasket, or Remove remaining diaphragm clamp and diaphragm. Remove retaining ring (detail 32,), spring (detail 34), and diaphragms to cleaning fluid, acetone, or any halogenated hydrocarbons such as degrease liquids, sleeve.
  • Page 6 ADJUSTMENTS SETPOINT 1. Remove cap screw. port 2. Apply operating control pressure to inlet through a .032" (.81 mm) diameter or smaller orifice. Control pressure and orifice size must be the same as that used during normal operation. 3. Apply process pressure at desired setpoint to the process port.
  • Page 7: Parts List

    DET. PROD. DESCRIPTION PARTS LIST REQD PART NO. Cap Screw 33718-G0509 Washer 24425- A1 Spring Housing 84366-A1 Spring Seat 24557-B1 Name Plate See Tabulation Adjustment Screw 24558-A2 Range Spring 33980-A1 Screw 33713-G1109 Spring Seat 33968-A2 Diaphragm Clamp 33969-A1 Screw 33713-G 1309 Gasket 33971-A1 Flange...
  • Page 8: Usa And Canada

    U.S.A. and CANADA Robertshaw Industrial Products Division 1602 Mustang Drive Maryville, Tennessee 37801 Phone: (865) 981-3100 Fax: (865) 981-3168 http://www.robertshawindustrial.com Exports Invensys Appliance Controls 1701 Byrd Avenue P.O. Box 26544 Richmond, Virginia 23261-6544 Phone: (804) 756-6500 Fax: (804) 756-6561 Q-3592 (4/03)

This manual is also suitable for:

84370-a184370-a284370-b1 5084370-b284370-c184370-c2