1. DESCRIPTION
Anasol is a differential thermostat for solar heating with two sensors and one output for controlling a
water circulation pump. The controller also has protection functions that prevent water from overheating
or freezing in the solar collector. It can also be configured as a digital thermostat with control logic for
heating or cooling. The interface used allows the simple display of SAS information, such as: output
status (differential or thermostat), operation mode (automatic, manual or off), and sensor temperature.
2. APPLICATIONS
- Solar heating for swimming pool or thermal reservoir;
- Water heaters
- Air-conditioning;
3. TECHNICAL SPECIFICATIONS
Power supply
Operating temperature
Operating humidity
Sensors
Control Temperature
Resolution
Control output
Product size
4. INDICATION AND SCREEN
4.1 PRESENTATION
Manual pump
operating mode
Automatic pump
operation mode
Pump Mode Key
Up Key
ANASOL 115vac
ANASOL 230vac
DIFFERENTIAL THERMOSTAT FOR SOLAR
HEATING OR DIGITAL THERMOSTAT
Ver. 04
Anasol 115Vac: 115Vac ±10% (50/60Hz)
Anasol 230Vac: 230Vac ±10% (50/60Hz)
0 to 50°C
10 a 90% UR (without condensation)
Sensor T1: Solar Collector -
SB 59 Sensor, white cable, 1m
Sensor T2: Thermal Reservoir -
SB19 Sensor, black cable, 2m
Sensor T1: -20 to 200°C
Sensor T2: -20 to 105°C
0,1°C between -10 and 100°C and 1°C outside
that range
Relay output, max. 1HP at 220Vca
(½HP at 127Vca)
or 16A, resistance at 3500W at 220Vca
(1750W at 127Vca)
77 x 39 x 97mm
Indicates differential
control mode
Indicates thermostat
control mode
Display
digits
Set Key
Down Key
4.2 INDICATIONS
- Modo de operação da bomba automático.
- Manual pump operation mode.
Note: Both off - OFF: Pump operating mode off.
- Output on - Differential control mode.
- Output on - Thermostat control mode (heating or cooling).
4.3 KEY MAP
The controller has easy access to features relevant to the user. The controller's operating mode is
defined by parameter [F06] - Operating Mode. See a table and description below.
4.3.1 DIFFERENTIAL MODE (SOLAR HEATING):
- Short press: changes the pump mode (AUT - MAN - OFF).
- Short press: briefly displays the remaining time (in minutes) of the manual mode timer.
- Short press: changes the temperature display (T1-T2-DIF). After 10 minutes, the preferred
indication returns.
- Short press: set the pool / reservoir heating temperature.
- Long press (4 seconds): access advanced settings.
4.3.2 THERMOSTAT MODE:
- Short press: changes the output mode (MAN - OFF)
- Long press (4 seconds): changes the output mode (AUT - OFF)
Note: In the automatic mode: short pressing
parameters
- Short press: briefly displays the remaining time (in minutes) of the manual mode timer.
- Short press: set the thermostat temperature.
- Long press (4 seconds): access advanced settings.
5. USER OPERATIONS
5.1 POOL / RESERVOIR HEATING TEMPERATURE (SENSOR T2)
OR THERMOSTAT (SENSOR T1)
Set the comfort temperature (SP) of the pool or thermal reservoir (T2). The water pump will
switch off when this temperature is reached, avoiding thermal discomfort. In the thermostat
mode, it sets the operating temperature of the thermostat (T1).
To set this parameter, press the
SET
key. Use the
shortly the
SET
key and the value will be saved in the controller memory. This parameter can be
adjusted between the values defined in the advanced configuration [F09] - minimum value and
[F10] - maximum value
5.2 WATER PUMP OPERATING MODE
Using the
MMMM
it is possible to change the operating mode of the water pump. The water circulation
pump between the solar collector and the thermal reservoir can operate on three different modes.
Short Press
Note¹: When the MAN (MANUAL) mode is selected, the pump will operate in this state for the length of
time set by the [F08] function - The maximum length of time the output will remain on in manual mode.
After this, the controller switches to the AUT (AUTOMATIC) mode.
Note²: This operating mode is available when compatible [F06] = diF (Differential Solar Heating
Mode).
DDDD
activates the output considering the configured
UpP DOWN
or
keys to set the value. To confirm, press
AUT = Circulation pump in automatic mode,
operating in accordance with the set
parameters.
MAN = Circulation pump turned on
Warning: In this mode the pump is kept on, by
passing the protection functions (except the
protection: against thermal shock).
OFF = Pump always off

Advertisement

loading

Summary of Contents for Full Gauge Controls ANASOL 115vac

  • Page 1 3. TECHNICAL SPECIFICATIONS defined by parameter [F06] - Operating Mode. See a table and description below. 4.3.1 DIFFERENTIAL MODE (SOLAR HEATING): Anasol 115Vac: 115Vac ±10% (50/60Hz) Power supply Anasol 230Vac: 230Vac ±10% (50/60Hz) - Short press: changes the pump mode (AUT - MAN - OFF).
  • Page 2 F03- Defrost temperature (T1) required to switch on the pump: 5.3 THERMOSTAT OPERATING MODE When the temperature of the collectors (T1) is too low (e.g. winter nights), the pump is turned on, [F06] = [Hot] or [rEF] depending on the set temperature of this parameters, to prevent water from freezing in the solar collector and damaging it.
  • Page 3 01 (one) year from accredited retailers, starting from the consignment date on the sales invoice. After this year, the warranty will continue to be honored for purchases from retailers if the device is sent directly to Full Gauge Controls. This period is valid in Brazil.

This manual is also suitable for:

Anasol 230vac