CEP 6502GU Installation And Operating Instructions

Temporary branch power distribution unit with ground fault protection for personnel

Advertisement

Quick Links

C E P 6502G U/G T L, 6503G U/G T L
S P E C IF IC AT ION
These installation and operation instructions
apply to the following temporary power
branch distribution system components. Do
not discard these instructions, save for future
Reference.
P OR T AB LE P OWE R
DIS T R IB UT ION UNIT S
These units are rated either 20 or 30 amps,
125/250 VAC, Single Phase. The max. ampacity
for the 20 amp unit is 40A @ 120V, and the 30
amp unit is 40A @ 120V. The 20 amp, 120 volt
outlets are individually protected by circuit
breakers and GFCI circuit modules.
Model
Number(s)
6502GU,6503GU
99577,99577C
6502GTL, 6503GTL
INT R ODUC T ION
CEP temporary power distribution units equipped
with GFCI modules that will protect you from
electrocution hazards resulting from ground
faults. Ground faults are current leaks and can
result in electric shock. Currents of o
of an ampere can be fatal. The GFCI protection
provided by CEP temporary power distribution
temporary power distribution units,
Ph: 800-474-7570, 602-272-8128 Fax: 602-272-8014
www.BestMaterials.com Email: Sales@BestMaterials.com
Distributed by Best Materials® LLC
99577, 99577C
T emporary branch power dis tribution unit
with G round F ault P rotection for pers onnel
Installation and Operating Ins tructions
20 Amp
Receptacle
U-Ground
Twist Lock
nly 60/1000
which are UL listed as Class A, Group I
interrupters, respond to fault currents as low as
3-6 mill amperes , and will shut of the current
within 1/40
of a second. The temporary power
th
distribution unit is designed to provide protection
against electrical shock hazards due to line
ground faults. Although the GFCI module does
not eliminate the hazard of a shock, it does limit
the duration of t he shock to a period considered
safe for normally healthy persons.
GFCI modules will provide protection against
ground faults only. They will not protect against
overloads or short circuits. There is no known
device that will guard against the electrical s
hazard resulting from contact with both the "hot"
and neutral wires of the electrical circuit.
E LE C T R IC IT Y IS DANG E R OUS .
E V E N WHE N S AF E T Y DE V IC E S AR E
P R E S E NT , HANDLE WIT H C AR E AND US E
R E AS ONAB LE C AUT ION.
LE T C AUT ION P R E V AIL
The CEP temporary power
designed to be used on a grounded electrical
supply system. It will not operate when supplied
from a power source which is not grounded.
Over -current protection of the proper rating,
according to the National Electric Code, Article
240, must be used on the supply circuit feeding
the temporary power distribution units.
.
-to-
hock
distribution unit is
For more information
Or to buy this product
Click here

Advertisement

loading

Summary of Contents for CEP 6502GU

  • Page 1 INT R ODUC T ION The CEP temporary power distribution unit is CEP temporary power distribution units equipped designed to be used on a grounded electrical with GFCI modules that will protect you from supply system. It will not operate when supplied electrocution hazards resulting from ground from a power source which is not grounded.
  • Page 2 T E S T P R OC E DUR E NOT E : Tripping of a circuit breaker in these All Models models can only result from an overload or short Connect the temporary power distribution unit to circuit condition in its individual load circuit. an appropriate power source.
  • Page 3 IMMEDIATELY ! Do not modify these devices in any way. Replace worn or damaged components. Failure to do so could cause serious personal injury or death. 6502GU/GTL, 6503GU/GTL, 99 577, 99577C REPLACEMENT PARTS DESCRIPTION PART # 20 AMP 125V U-GROUND DUPLEX RECEPTACLE R...