Download Print this page
olympia electronics BS-685 Quick Start Manual

olympia electronics BS-685 Quick Start Manual

Waterproof lpg, natural gas-methane detector for conventional panels

Advertisement

Quick Links

BS-685 Waterproof LPG detector for conventional panels
BS-686 Waterproof natural gas-methane detector for conventional panels
Operation voltage
Average consumption
Sensitivity
Indicators
Degrees of cover protection
Produced in accordance with
Operation temperature range
Humidity
Dimensions
Sensor life time
Weight
Guarantee
OPERATION - USE
BS-685 and BS-686 detectors are used in
combination with gas panels to give us a
warning in case there is a natural gas or LPG
gas leak. The installation must be done by a
qualified personnel. Instructions must be read
before the installation.
Emergency Actions
It is recommended that the following advice
should be given in the event of an alarm
sounding or the smell of gas even without an
alarm:
Keep calm, and carry out the following actions,
not necessarily in the order given:
-extinguish all flames, including smoking
material.
- turn off all gas appliances.
- do not switch on or off any electrical equipment,
including the gas detection apparatus.
- turn off the gas supply at the gas main control
and/or ( with a LPG supply) the storage tank.
-open doors and windows to increase
ventilation.
- do not use a telephone in the building where the
presence of a gas is suspected.
If the alarm continues to operate, even after an
alarm resetting action where appropriate, and
the cause of the leak in not apparent and/or
cannot be corrected, vacate the premises and
IMMEDIATELY NOTIFY the gas supplier
order that the installation may be tested and
Page 1 from 5
TECHNICAL CHARACTERISTICS
BS-685
5-15 % L.E.L. Propane
Thank you for your trust in our products
Olympia Electronics - European manufacturer
10-30V AC- DC ( Powered by panel)
0,5W ( 12VDC 40mADC, 24VDC 20mADC)
alarm LED
IP 65
EN 50194-1, EN 50270
0 to 60 C
Up to 95% relative humidity
155 x 80 x 43 mm
5 years
150 gr
2 years
made safe, and any necessary repair carried out.
Placement
Depending on the monitored gas, the unit must be
placed with the sensor downwards, 30cm from
the ceiling (for methane, natural gas) or 30cm
from the floor (for propane, LPG). The horizontal
distance should not be more than 4 meters from
the probable gas leak point and the detectors
must not be placed in humid or drafty areas.
It is suggested that the detector is tested for good
operation every 6 months or if it is changed
position.
The unit must should not be sited:
- directly above cooking appliances
- directly above sink
- adjacent to extractor fans
- in any outside location
-where the environmental conditions are outside
the manufacturers operational specification.
Installation
In order to install the device you must first remove
the four srews (figure 1). Then with the
assisstance of figures 2 and 3 you can connect it
to the panel.
Connection with fire panel of Olympia
Electronics.
Terminals ΖΟΝΕ are used to connect to zone of
in
the gas panel, as shown in figure 2. A terminal
resistor (5,6KÙ) should be installed on the end of
BS-686
5-15 % L.E.L. Methane
o
921686000_09_017

Advertisement

loading

Summary of Contents for olympia electronics BS-685

  • Page 1 BS-685 Waterproof LPG detector for conventional panels BS-686 Waterproof natural gas-methane detector for conventional panels TECHNICAL CHARACTERISTICS BS-685 BS-686 Operation voltage 10-30V AC- DC ( Powered by panel) Average consumption 0,5W ( 12VDC 40mADC, 24VDC 20mADC) Sensitivity 5-15 % L.E.L. Propane 5-15 % L.E.L.
  • Page 2 Figure 1. Diagram of removing the plastic cover Terminal Resistor Relay resistance selection jumper Fire panel LED Alarm Olympia Electronics Jumper for programming alarm latch mode Figure 2. Connection diagram of a detector with a fire panel of Olympia Electronics Page 2 from 5 921686000_09_017...
  • Page 3 When the red LED is lit then the unit is in alarm mode. Alarm mode can be triggered from the sensor of the unit. Figure 4 shows a connection diagram between 4 BS-685 or BS-686 and a gas panel. Waterproofing of the device...
  • Page 4 BS-685-6 BS-685-6 BS-685-6 Terminal Resistance Figure 4. Connection of 4 gas detector BS-685 or BS-686 to a Olympia Electronics panel. The number of the devices connecting to a gas panel is depending only to the panel specifications. Button BS-690-1 Power LED...
  • Page 5: Warranty

    Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

This manual is also suitable for:

Bs-686