Autonomous natural gas-methane and lpg detectors

Advertisement

Quick Links

BS-691
Autonomous natural gas-methane detector
BS-690
Autonomous LPG detector
Operation voltage
Maximum consumption
Sensitivity
Indicators
Outputs
Degrees of cover protection
Produced in accordance with
Operation temperature range
Humidity
Dimensions
Fire detection zone
Sensor life time
Weight
Guarantee
GENERAL
BS-691 and BS-690 detectors are used to give
us a quick warning in case there is a natural gas
or LPG gas leak.
The installation must be done by a quilified
personnel. The instructions must be read first
before the installation.
Emergency actions
It is recommended that the following advice
should be given in the event of an alarm sounding
or the smell of gas even without an alarm:
Keep calm, and carry out the following actions,
not necessarily in the order given:
- extinguish all naked flames, including smoking
material;
- turn off all gas appliances;
- do not switch on or off any electrical equipment,
including the gas detection apparatus;
- turn off the gas supply at the gas main control
and/or ( with a LPG supply) the storage tank;
- open doors and windows to increase ventilation;
- do not use a telephone in the building where the
presence of a gas is suspected.
If the alarm continues to operate, even after an
alarm resetting action where appropiate, and the
cause of the leak in not apparent and/or connot
be corrected, vacate the premises and
IMMEDIATELY NOTIFY the gas supplier in order
that the installation may be tested and made safe,
and any necessary repair carried out.
Page 1 from 5
Technical characteristics
5-15 % L.E.L. Propane
Thank you for your trust in our products
Olympia Electronics - European manufacturer
BS-690
220 - 240V AC / 50-60Hz
32 VA
Power LED , alarm LED , fault LED
Relay (230VAC 5Α) and 12V DC
IP40
EN 50194, EN 60335, EN 61000-3-2, EN 61000-3-3
0 to 60 C
Up to 95% relative humidity
145 x 85 x 45 mm
No more than 5 detectors 12V
5 years
300gr.
2 years
Placement
Depending on the monitored gas, the unit must
be placed 30cm from the ceiling (for methane,
natural gas) or 30cm from the floor (for propane,
butane, LPG). The horizontal distance should
not be more than 4 meters from the probable
gas leak point and the detectors must not be
placed in humid or drafty areas.
It is suggested that the detector is tested for good
operation every 6 months or if it is changed
position.
The unit must should not be sited:
- directly above cooking appliances;
- directly above sink;
- adjacent to extractor fans;
- in any outside location;
- where the environmental conditions are outside
the manufacturers operational specification.
Installation
For the installation of the device first you must
remove the red plastic with a screwdriver as
shown in figure 1 and unscrew the screw in the
middle. Then with the help of figure 2 you can
connect the external devices.
Terminals +Z, -Z are used for a fire detection
zone. Up-to 5 conventional detectors can be
installed. The connection cable must be at least
2x1mm diameter and no more than 100m in
length. These detectors must operate with 12V.
Such devices are BS-655 (smoke detector) , BS-
660 (heat rise detector) and BS-668 (heat
BS-691
5-15 % L.E.L. Methane
o
921691000_09_016

Advertisement

loading

Summary of Contents for olympia electronics BS-690

  • Page 1 Olympia Electronics - European manufacturer GENERAL Placement BS-691 and BS-690 detectors are used to give Depending on the monitored gas, the unit must us a quick warning in case there is a natural gas be placed 30cm from the ceiling (for methane, or LPG gas leak.
  • Page 2 Sensitivity When the test button is pressed, the system is The BS-690 detectors are activated when the tested and restarted. During the test the internal content of gas (propane or butane), in the circuits are checked, the relay is activated and the monitored area, exceeds 5 - 15% of the lower internal buzzer sounds.
  • Page 3 Figure 3a and 3b shows the connection of multiple detectors in a network connection , for covering a larger area and using one 12VDC NO electro-valve or one 12VDC NC electro-valve Attention!! The position link of JMP1 set the relay status. If a link is set on A ( figure 3B ) the relay is energized (NO) in normal condition and on alarm or fault condition the relay is not energized.
  • Page 4 JMP1 JMP1 JMP1 E.V. 12VDC N.O. Figure 3B.Connecting multiple detectors in a network and using one electro-valve 12VDC N.O. Electro-valve ~230V JMP1 JMP1 BS-546 BS-546 ~230 V ~230 V E.V. ~230V N.O. E.V. ~230V N.C. Diagram with manual reset and Diagram with manual reset and normally open electro-valve normally closed electro-valve...
  • Page 5: Warranty

    Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.