  • Page 1 Models TC0, TC1 and TC3 Installation Guide...
  • Page 2 Mounting Mount against a flat surface using four M5 screws. Topcat Screw Spacing Outside Dimensions Model Horizontal (A) Vertical Width (B) Height 89.5 mm 141 mm 112 mm 168 mm 121.5 mm 141 mm 143 mm 168 mm 184.5 mm 141 mm 206 mm 168 mm...
  • Page 3: Isolated Digital Inputs

    Isolated Digital Inputs General Description Inactive, LED off Active, LED on Maximum Resistance Positive voltage-activated 0~+1.8V +4.5~36.0V ±60V DC 12kΩ to GND D.INs CONTACTS (EG. RELAY CONTACTS SWITCHES) FIELD SUPPLY Digital Inputs Inputs 0~3 can be used for Pulse Counts. Max count rate <= 50Hz Analog Inputs General Description Inactive, LED off...
  • Page 4: Isolated Digital Outputs

    Isolated Digital Outputs Normally open contacts which close to rated at 6A for 230V AC and 30V DC. D.OUTs 6 A MAX PER OUTPUT LOAD LOAD FIELD SUPPLY Digital Outputs Security I/O The fail-safe alarm is an open collector, which can carry 50mA, up to 30V, and can drive a relay coil directly.
  • Page 5: Serial Ports

    Serial Ports Name Type Socket Typically used for… PORT 1 RS-232 RJ-45 Local connection to PLC, data logger, meter PORT 2 RS-232 RJ-45 Local connection to PLC, data logger, meter CONFIG RS-232 RJ-45 Laptop, Analog output module Name Connector pins 2 and 3 are not connected on PORT 1 sf...
  • Page 6 Speaker / Microphone Connections A suitable Speaker / Microphone connection is provided on units with an internal radio for monitoring and testing the radio channel. Pin Name Speaker Microphone RJ12 Speaker Mic Pins Communication Indicators indicators show communication between and the Telemetry COMMS Topcat Master.
  • Page 7 Notes IG-671-2.2-2015-Mar Installation Guide...
  • Page 8 Phone +64-4-385-6611 Fax +64-4-3856848 Document number IG-671-2.2-2015-Mar Products Covered TC0, TC1 and TC3 (all variants) Revision Number Revision date 15 March 2015 Topcat and the logo are trademarks of Abbey Systems Ltd, registered with the U.S. Patent and Trademark Office.