Oppermann Regelgeräte SENSO-X VPX Manual

Volume flow indicator / monitor / transmitter

Advertisement

Quick Links

Volume flow indicator / monitor / transmitter
SENSO-X® VPX
Technical data
Housing:
high impact ABS
Front panel color:
antique white
Lower housing color:
anthracite
Protection class:
surface-mounted type (AP) IP 65
built-in type IP 54 /
built-in type with additional sealing
(accessory) IP64
Operating temperature: -20 °C to 65 °C
Storage temperature:
-20 °C to 70 °C
Relative humidity:
max. 95 % non-condensing
Front cover dimensions
- square:
182 x 140 x 21 mm [L x W x H]
- round:
143 mm Ø
Dimensions of
surface-mounted type: 165 x 71 mm [Ø x T]
Hose connection:
2x 6 mm Ø
Working and
measuring ranges:
see table
Working range:
adjustable via keys and NFC tool
Burst pressure:
20 kPa (VPX1000)
40 kPa (VPX4000)
Protection class:
II (IEC 60536)
Error margin:
+/- 1 % of measuring range
(@ -5 to 65 °C)
Power consumption:
24 V DC 41 mA
24 V AC 81 mA
Long-term stability:
≤ ± 0.5 % FS/a
Supply voltage:
13.5 – 36 V DC or
13.5 – 30 V AC at 50/60 Hz
Output analog:
linear 0 – 10 V (max. 0.1 mA) or
4 – 20 mA (max. load 600 Ω).
Output digital:
relay (250 V AC 6 A, 30 V DC 5 A),
changeover switch, closed-circuit
principle, freely selectable limit value.
Modbus optional.
Cable gland:
M16
Cable connection:
Spring terminals 0.2 – 1.5 mm²
Large LCD display
Volume flow up to 99,999 displayed in
numerals or as an indicator bar in any of the
following units: m³/h, l/s, ft³/min
Limit displayed up to max. volume flow
Working range displayed (Range max)
Three-color LED: red for limit value undershoot,
yellow for fault and green for overshoot
Temperature / Absolute pressure transducer
NFC parametrisation of limit, range max,
signal range for analog output, K-factor and
air density ρ
Optional Modbus output
Power supply: 24 V AC at 50 / 60 Hz or 24 V DC
Available in two built-in and one surface-
mounted versions
Types
Type
Type
Measuring
Measuring
Working range
Working range
range
range
(output signal)
(output signal)
VPX1000
0 – 1,000 Pa
0 – 99,999 m³/h
freely adjustable in
1 m³/h-increments
VPX4000
0 – 4,000 Pa
0 – 99,999 m³/h
freely adjustable in
1 m³/h-increments
* analog output 0 – 10 V or 4 – 20 mA linear depending on selected working range and unit of
measure.
Installation
All work (such as installation, electrical connection, startup, ope-
ration, and maintenance) must only be performed by sufficiently
qualified tradesmen. The respectively applicable local rules and
regulations (e.g. national building codes, electrical/VDE regula-
tions, etc.) must be observed. Installers and operating entities
are required to sufficiently familiarize themselves before startup.
Read the product description before operating the equipment.
Verify that the product can be used for the relevant application
without restrictions. We are not liable for printing errors and
changes after printing. Appropriate use implies compliance with
operating and installation instructions. We are not liable for losses
due to inappropriate use. Unauthorized or inappropriate mani-
pulations or modifications of the device render the operating
permit, the product warranty and warranty claims null and void.
Sensors PG1 | Data sheet No. 13170 | Version 03-2020 | 1 | 6
Units of
Units of
Limit value
Limit value
measure /
measure /
monitoring
monitoring
output*
output*
m³/h, l/s,
Freely selectable.
ft³/min
LED/bar -indicator +
switching output for
undershoot
m³/h, l/s,
Freely selectable.
ft³/min
LED/bar -indicator +
switching output for
undershoot

Advertisement

loading

Summary of Contents for Oppermann Regelgeräte SENSO-X VPX

  • Page 1 Volume flow indicator / monitor / transmitter SENSO-X® VPX • Large LCD display • Volume flow up to 99,999 displayed in numerals or as an indicator bar in any of the following units: m³/h, l/s, ft³/min • Limit displayed up to max. volume flow •...
  • Page 2: Operating Principle

    Volume flow indicator / monitor / transmitter SENSO-X® VPX Operating principle Built-in version Mill a 115 mm Ø hole in the sandwich plate or cabinet door and push the functional part through the opening from the The measured differential pressure is transmitted via flexible front.
  • Page 3: Electrical Connection

    Volume flow indicator / monitor / transmitter SENSO-X® VPX ches the setting back and forth between m³/h, l/s and ft³/min. Save (OK) The volume flow is displayed in numerals and as an indicator bar. The indicator bar serves to visualize the measured volume After 10 s without a keystroke the set values are saved flow in % in relation to the set working range (Range max).
  • Page 4: Modbus Rtu

    Volume flow indicator / monitor / transmitter SENSO-X® VPX Note: Installation example: Floating switch contacts “CO, “NC” and “NO” may only be used for 230 V AC or 24 C AC/DC . Disconnection or electrical protection equipment must be provided by the customer.
  • Page 5 Volume flow indicator / monitor / transmitter SENSO-X® VPX 7 (0x07) 40008 unit of measure unsigned 16 4, 5 or 6 4: ft³/min 5: l/s 6: m³/h 8 (0x08) 40009 range max 0 to 65,535 Set limit value in selected unit (low word) of measure, see register 7, e.g.
  • Page 6 Volume flow indicator / monitor / transmitter SENSO-X® VPX Overview of the SENSO-X® PPX in its built-in version Wing nut 3 keys Built-in versions Square front type ... 00 Round front type ... 01 Housing base (Functional part in the built-in version) Surface mounted housing Oppermann Regelgeräte GmbH | Im Spitzhau 1 | 70771 Leinfelden-Echterdingen, Germany...

This manual is also suitable for:

Senso-x vpx1000Senso-x vpx4000