I — INTRODUCTION
SCOPE OF MANUAL This Quick Start Guide covers
the installation and operation of the Kepco HSP Series of
voltage and current stabilized d-c power supplies. Full
specifications are listed in the applicable Operator's Man-
ual that can be downloaded from the Kepco web site at
www.kepcopower.com/support/opmanls.htm/#hsp
FACTORY DEFAULTS This guide covers only units as
shipped from the factory with the three DIP switches set to
default configuration (see Figure 1). For other configura-
tions, refer to HSP Operator Manual.
DESCRIPTION The HSP power supply (Figure 1-1) is
basically a voltage and current stabilized d-c source with a
relatively sharp crossover between voltage and current
mode operation.
HSP power supplies are nominally rated at either 1000 or
1500 Watts of output power, and include active power fac-
tor correction (PFC). HSP 1000W power supplies are
designed to operate over the universal a-c power mains
voltage range of 90-277V (47-63Hz), with operation from
125-420V d-c also available. HSP 1500W products provide
full power over the a-c mains range of range of 180-277V
a-c, and 1000W output power from 90-132V a-c; contact
Kepco for information on operation over other source volt-
age ranges. Cooling is provided via an internal d-c fan.
HSP permits adjustment of both output voltage (V
current limit (I
), either by internal (front panel pot) or
MAX
external (resistance or voltage) methods, selected via DIP
switches accessed through the top of the unit. Protection
against overvoltage, overcurrent and overtemperature fail-
ures is provided.
MODELS
1000W
1500W
NOTE: Options include suffix M or B: M for meter; B for battery charger.
KEPCO, INC.
131-38 SANFORD AVENUE
©2010, KEPCO, INC
Data subject to change without notice
KEPCO
PROGAMMABLE POWER SUPPLIES
TABLE 1. HSP SERIES MODELS
3.3V
5V
HSP 3.3-230R
HSP 5-200R
N/A
N/A
http://www.kepcopower.com
An ISO 9001 Company.
SINGLE OUTPUT
FIGURE 1. DIP SWITCH FACTORY DEFAULTS
The HSP power supply is specifically designed for use with
Kepco RA 60 or similar plug-in rack adapters as a hot
replaceable module in a redundant power system. Bench
top operation is also supported. Forced current sharing and
output blocking diodes enhance power system reliability.
Mechanical keying eliminates the risk of incorrect module
insertion. Tool-operated latches on the front panel guard
against casual removal of an operating module.
) and
OPTIONS M models include a digital meter which dis-
O
plays either voltage or current as determined by a front
panel switch. Another switch allows display of either
actual HSP Output or the setpoint. B models are intended
for battery charging applications, and include a Float/
Equalize switch to preset two different voltage values
using two separate front panel adjustment pots.
12V
15V
HSP 12-84R
HSP 15-66R
N/A
N/A
FLUSHING, NY. 11355 U.S.A.
email: hq@kepcopower.com
228-1706
HSP
1000W/1500W
24V
28V
HSP 24-42R
HSP 28-36R
HSP 24-60R
HSP 28-53R
TEL (718) 461-7000
FAX (718) 767-1102
48V
HSP 48-21R
HSP 48-30R
1

Advertisement

loading

Summary of Contents for CalPower Kepco HSP Series

  • Page 1 PROGAMMABLE POWER SUPPLIES I — INTRODUCTION SCOPE OF MANUAL This Quick Start Guide covers the installation and operation of the Kepco HSP Series of voltage and current stabilized d-c power supplies. Full specifications are listed in the applicable Operator’s Man- ual that can be downloaded from the Kepco web site at www.kepcopower.com/support/opmanls.htm/#hsp...
  • Page 2 II — INSTALLATION KEYING. The units are keyed by voltage at the factory. CONNECTIONS: Figure 2 shows proper connection Refer to the Operator Manual for details. of one or more loads using either remote or local sensing. If local or remote sensing is not configured, the unit MOUNTING THE POWER SUPPLY To insert in a will not work properly.
  • Page 3 does not lock when released, wait a few seconds 8. Verify that front panel indicators still appear as in step 4 before trying again. The circuit breaker is "trip-free" above. design; if overload exists, contacts cannot be held 9. Disconnect sense lines with power supply still operat- closed by actuator.
  • Page 4 Retaining Latches (2) Prevents inadvertent removal of unit from rack adapter. Adjust pot Used to adjust current limit from 3043522 front panel. FIGURE 4. COMPONENT LOCATIONS Via Acquanera, 29 22100 Como tel. 031.526.566 (r.a.) fax 031.507.984 info@calpower.it www.calpower.it...