DANLERS COPD Installation Notes

Compact person detector, pir switch

Advertisement

Quick Links

Variants
As DANLERS design and manufacture in the UK, variants can be supplied,
coded by the following suffixes, applied in this order:
• 12V or 24V
12V or 24V (ac or dc) operation
• VF
Volt Free contacts
• NC or CO
Normally Closed or Change Over contacts
• G or LG
Gold or Logic Gold contacts
The details of these variants are covered by an enclosed addendum
installation note if applicable.
Trouble shooting
The COPD cannot be made to switch on during bright days
• The COPD XPH (no photocell) should be used.
The PIR does not detect
• Person is too far from the COPD switch, see detection diagram.
• Person is moving unusually slowly (perhaps when testing).
The PIR stops working
• Ensure the unit is mounted correctly so that no water can enter.
• If mounted on porch ceiling, ensure adjustment spindle point inwards.
The PIR False triggers
• Detector is exposed to air movement on breezy days.
Precautions and Warranty
This product conforms to BS EN 60669-2-1.
Please ensure the most recent edition of the appropriate local wiring regulations are observed
and suitable protection is provided e.g. 6 amps over current, 1kV over voltage. Please ensure
that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
Please call for more information or a free catalogue.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
E-mail: sales@danlers.co.uk
Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
06/04/11
Compact person detector, PIR switch
COPD
DANLERS Compact Person Detector can be surface mounted onto an
external wall. It incorporates a passive infra-red quad sensor to detect
movement of a warm body within the detection zone (diagram A) and
the COPD includes a photocell to monitor the ambient light level.
The detection range is about 10 metres over 120 degrees, the range
reduces to about 8m at the extremes to prevent nuisance switching.
On detecting movement, if the ambient light is dark enough, the
COPD will switch the load on. The ambient threshold can be set by
the user to between approximately 20 and 1000 lux via the external
LUX adjuster (diagram B). The COPD XPH version which does not
include a photocell or LUX adjuster will switch the load on regardless
of the ambient light level.
If no more movement is detected within a certain time, then the PIR
will switch off the load. The time can be set via the internal TIME
adjuster to between 2 and 20 minutes (diagram C).
Loading
The COPD should only be connected to a 230V 50Hz ac supply.
It can switch the following type of loads:
• 6 amps (1500W)
• 4 amps (1000W)
• 2 amps (500W)
• 1 amp (250W)
INS970 COPD
COPD XPH
Incandescent or mains halogen lamps
(recommended with integral safety fuse)
Electronic or wire wound transformers.
Fluorescent lamps (high frequency or soft start)
Compact fluorescent or LED lamps (about 50 lamps)
Metal halide discharge lamps or fans.
Installation notes

Advertisement

loading

Summary of Contents for DANLERS COPD

  • Page 1 On detecting movement, if the ambient light is dark enough, the The PIR does not detect COPD will switch the load on. The ambient threshold can be set by • Person is too far from the COPD switch, see detection diagram.
  • Page 2 Outside detector housing Inside detector housing For convenience, ensure that the TIME is set to minimum when setting Not applicable to COPD XPH up the LUX level. Afterwards set the TIME to a value suitable for the application. The LUX is best set up when the ambient light is at approximately the minimum desired level.