Download Print this page

Inbal Valves 700D Series Manual

Deluge valve, hydraulic actuation local resetting

Advertisement

Quick Links

Deluge Valve, Hydraulic Actuation
Series 700D/DG/DX - 04/14A 01
General Description
The Inbal Deluge Valve with Hydraulic
Actuation Trim is specifically designed
for fire protection systems actuated by a
fire detection and release system of wet
pilot sprinklers and/or hydraulic manual
control. The Inbal Automatic Water
Control Valve, which is used in this
deluge system, is a pressure operated,
sleeve actuated, axial valve designed for
use in fire protection systems.
The Inbal Hydraulically actuated
Deluge Valve is used for automatic or
manual operation. The wet pilot line
functions as a thermal detector equipped
with a fixed temperature release. When
one or more of the sprinkler heads,
located on the pilot line, fuses, or when a
manual release station is operated locally
or remotely, the Inbal Deluge Valve
opens and water flows from all open
sprinklers and/or nozzles on the system.
As soon as the releasing system and the
sprinkler piping are reset, the Inbal
Deluge Valve resetting is merely done by
activating the reset knob.
Mil Ltd
Model 799DG-04A01
The control trim includes all the pilot
valves, accessories, fittings, and gauges
to provide for proper operation in either
vertical or horizontal installation. The
standard material Inbal Deluge Valve is
rated to 300 psi (21 bar) and is available
in sizes 1½" (40 mm) to 12" (300 mm).
The valves have threaded, flanged,
grooved, or wafer inlet and outlet ends.
The only moving part in the Inbal
Deluge Valve, when it operates, is the
reinforced sleeve, which forms a drip-
tight seal with the corrosion resistant
core. It has a smooth opening to prevent
any water hammer in the piping system .
The unique design and variety of
materials and coatings make the Inbal
Deluge Valve ideally suitable for use in
brackish or sea water, similar to those
found in chemical and petrochemical
facilities or in offshore platforms. The
Inbal can also be used as a foam
concentrate control valve in foam/water
systems.
Local Resetting
Technical Data
Approvals
The Inbal Hydraulically Controlled
Deluge Valve series 700DG-04A is FM
approved to 300 psi (21 bar) in sizes 3",
4", 6", and 8" (80, 100, 150, and 200
mm). Consult the FM Approval Guide
for acceptable applications. Inbal
Deluge Valves have Lloyd's,
ABS Type Approvals for all sizes.
Model Numbers
Inlet End Outlet End
Threaded Threaded
Threaded Grooved
Flanged
Flanged
Flanged
Grooved
Grooved
Grooved
Wafer
Wafer
"DG" can be replaced with "D" or "DX" depends
on the Inbal Automatic Water Control Valve series
in use. See bulletins F02-01-01, F02-02-01, and
F02-03-01.
The above model numbers refer to fully trimmed
valves. For basic trim, replace "04" with "14".
(See also bulletin F01-03-01 for control trims "24"
& "34"). For example: 711DG-14A01 is a threaded
ends deluge valve with basic, hydraulically
actuated trim.
Sizes
Threaded End:
1½", 2", 2½",
3" (40, 50, 65,
&
Flanged and Grooved Ends:
1½", 2", 2½", 3", 4", 6", 8", 10", & 12"
(40, 50, 65, 80, 100,150, 200, 250, &
300 mm).
Wafer End:
3", 4", 6", 8", 10", & 12" (80, 100, 150,
200, 250, & 300 mm).
End Standards
Threaded End:
NPT or BSPT.
Flanged End:
ANSI B16.5 class 150 & 300 ;
ISO 7005 - PN10, 16
BS 10 Table D & E ;
AS 2129 Table D & E ;
Jis B 2212, 2213, 2214.
Wafer End:
Fits most of the above standards.
Grooved End:
ANSI/AWWA C606-87.
, and
DNV
Model no.
711DG-04A01
716DG-04A01
733DG-04A01
736DG-04A01
766DG-04A01
799DG-04A01
80 mm).
&
25 ;
&
F03-02-01

Advertisement

loading

Summary of Contents for Inbal Valves 700D Series

  • Page 1 Deluge Valve, Hydraulic Actuation Series 700D/DG/DX - 04/14A 01 Local Resetting Technical Data Approvals The Inbal Hydraulically Controlled Deluge Valve series 700DG-04A is FM approved to 300 psi (21 bar) in sizes 3", 4", 6", and 8" (80, 100, 150, and 200 mm).
  • Page 2 Pressure Rating Trim Shutoff Valve, Flow Test Valve, Operation and Drain Valve are quarter turn ball Maximum working pressure*: 300 psi valves. (21 bar). The Control Chamber of the Inbal Supply and System Pressure Gauges, Automatic Water Control Valve is the * standard material valve.
  • Page 3 Schematic Control Diagram 700DG- 04A01 Installation Refer to the Trim Chart applicable to the Inspector's specific Inbal Deluge Valve model in Test Valve use. To Water Motor Alarm 1. When the Inbal Deluge Valve is To Alarm To System Pressure delivered, carefully unpack and visu- Switch ally check that there has been no...
  • Page 4 Deluge Valve, Hydraulic Actuation Series 700D/DG/DX - 04/14 A 01 Trip Testing Wet Pilot Line - Design Data An annual Trip Testing is recommended. Performing the Trip Testing will cause water to flow from all open sprinklers and/or nozzles. Prevent damage by m H O ft H O taking necessary precautions.

This manual is also suitable for:

711dg-04a01716dg-04a01733dg-04a01736dg-04a01766dg-04a01799dg-04a01