Description
The ZP755HAV-2 is an addressable horn sounder/visual
indicator designed for use in Ziton analogue addressable fire
detection and alarm systems.
Note:
The visual indicator of this product does not comply with
EN 54-23 and must not be used in fire alarm installations
where fire notification beacons are required.
The device includes a volume control, an address-setting
switch, programmable tone settings, and a pair of jumpers to
select the operating power — from the analogue addressable
loop or an external supply. The device plugs into a base that is
purchased separately. See Table 1 for a list of model numbers.
Table 1: Models
Number
Description
Sounder:
ZP755HAV-2R
Horn sounder, red
ZP755HAV-2P
Horn sounder, polar white
Base:
SPB-2R
Base, red
SPB-2P
Base, polar white
Installation
To install the device;
1.
Wire the base
2.
Set the operating power
3.
Set the address
4.
Set the mode of operation
5.
Set the tone
© 2014 UTC Fire & Security. All rights reserved.
6.
Set the volume
7.
Mount the sounder/visual indicator onto the base
The details of each step are given below.
Wiring the base
Connect the loop wiring for the plug-in base as shown in
Figure 1. There is no wiring between the sounder and base.
The base is supplied separately.
Figure 1: Loop wiring for the base
6
5
1.
Ext. 24 VDC+ IN/OUT
2.
Ext. 24 VDC ground IN/OUT
5.
Loop+ IN/OUT
Setting the operating power
The sounder includes a pair of power selection jumpers, J1
and J2. To select the source of the sounder operating power,
position the jumpers as shown in Figure 2.
Figure 2: Power selection jumper configuration
1
J1
J2
1.
Loop powered
Note:
When using an external power supply, use only one that
is CE and EN 54-4 compliant to power all the sounders on the
same loop.
1 / 4
P/N 501-1780ZE-1-10 • REV 10 • ISS 16APR14
Loop − IN/OUT
6.
7.
Shield
2
J1
J2
2.
External 24 VDC
1
2

Advertisement

loading

Summary of Contents for Ziton ZP755HAV-2 Series

  • Page 1 The base is supplied separately. Figure 1: Loop wiring for the base Description The ZP755HAV-2 is an addressable horn sounder/visual indicator designed for use in Ziton analogue addressable fire detection and alarm systems. Note: The visual indicator of this product does not comply with EN 54-23 and must not be used in fire alarm installations where fire notification beacons are required.
  • Page 2 Setting the address Setting the operating mode The sounder includes a seven-segment DIP switch (SW1) for The device operates as a dedicated (stand-alone) sounder with assigning device addresses. Each switch segment has a its own unique loop address when SW2-7 is set to ON. decimal value as shown in Figure 3.
  • Page 3 Table 3: Tone settings SW2-6 device mode Device mode SW2 switch setting Mapping input type switch setting -1 -2 -3 Fast flash Steady Tone type Tone A primary/alert Tone B secondary/evac ZP755 Intermittent Continuous ZP755 Continuous Intermittent ZP755 Continuous Two-tone ZP755 Two-tone Continuous...
  • Page 4 Open and short circuit fault purchase of equivalent new equipment, or Sound output level Self test facility dispose of it at designated collection points. For more information see: Compatibility Ziton analogue addressable www.recyclethis.info. systems Addressing method 7-segment DIP switch Mounting Surface with plug-in base...

This manual is also suitable for:

Zp755hav-2rZp755hav-2p