MAINTAINED/NON-MAINTAINED (OPTIONAL) ILLUMINATION SIGNS WITH WHITE LEDs
TECHNICAL CHARACTERISTICS
FOR LED MODULE SPECS. see page 6
Mains voltage
Maximum power consumption
Battery (Ni-Cd)
Battery protection
Recharging time
Minimum emergency duration
Light source intensity (Mains / Emerg)
Degrees of cover protection
Class of cover protection
Produced in accordance with
Operation temperature range
Relative humidity
External panel's dimensions
External dimensions (LxWxH)
Construction material
Typical weight
Guarantee
Thank you for your trust in our products. Olympia Electronics - European manufacturer.
GENERAL
These sign illumination luminaires use a new
technology, friendly to the environment, with high
illuminated L.E.D.s. L.E.D. technology has very low
power consumption.
The edge illumination sign is used as a maintained
emergency lighting with indications symbols.
In this type of marking panels, the PVC overlay is
mounted on the marking panel with 4 plastic screws,
and it can be changed by change the PVC overlay in
accordance with the desired result.
Each model combines modern, aesthetics, together
with functionality. The exit illumination signs are used
in every public area where clear direction and good
appearance are important.
NON MAINTAINED OPERATION
By default the illumination sign operates as maintained.
The device has a possibility to operate as non
maintained. To change the maintained to non-
maintained operation follow the relative instructions on
page 6.
All models must be permanently connected to the
mains power supply as shown on page 2.
The legend is screened on to a clear acrylic sheet
which has the marking on the marking panel with the
light that comes from the top of the luminaire and
diffracts, giving light to the marking panel.
The luminaire has an indication (CHARGE) for the
charging of the battery and a (TEST) button to TEST
the emergency circuit and the LEDs for good operation
only when the luminaire is powered by the mains power
supply. The unit must be mounted in a clearly visible
area and can either be hung on a ceiling or mounted on
a wall depending on the requirements of the
installation. The package
materials for mounting on the wall or on the ceiling.
The pages 2,3 and 4 show
Page 1 from 6
MLD-28D/w
3W / 7.5VA
85lm/85lm
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
280x100mm
305x25x155mm
includes all the required
us
the
mounting
MLD-34D/w
220-240V AC/50-60Hz
3.6V/1Ah
Overcharging and deep discharging protection
class II
5-40 C
up to 95%
340x170mm
365x25x225mm
ABS/PC, Acrylic plate, PVC
520gr.
3 years (1 year for the battery)
methods.
WARNING !!
1. Read carefully this instruction manual.
2. Before service interrupt the mains power supply.
3. The device must be connected to the mains power
supply through a fuse dependent by the total amount of
the line's power load.
4. It is suggested to check every month the indication
LED for battery charging, and by pushing briefly the
TEST button to check the emergency circuit. The sign
should light for a few seconds powered by the battery
and then, will turn to normal operation
condition contact the installer.
5.
Every six months, a
carried out
by disconnecting the mains power supply
Count the autonomous duration of the luminaire and in
case of no correspondence to stated emergency
duration replace the battery The replacement of the
battery must be done using parts of the same type, by
the manufacturer or by a competent person.
6. In case of inactive use for a period greater than 2
months, disconnect the battery by pulling out the
battery's connector.
7 Replaced batteries must not be thrown into
.
trash bins. They must be returned to special
battery disposal points.
Do not incinerate.
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
A: Including test device G: Internally illuminated
safety sign.
180: 3 hour duration
(*) Maintained operation: The luminaire lights its
illumination source, when it is powered by the mains
power supply or not.
Non-Maintained operation: The luminaire lights its
illumination source, only in power supply's failure.
MLD-44D/w
3W / 8VA
24h
3h
105lm/85lm
IP40
ο
440x220mm
465x25x275mm
850gr.
1310gr.
. In the opposite
full
duration check should be
.
1: Maintained (*)
922504417_09_032
.

Advertisement

loading

Summary of Contents for olympia electronics MLD Series

  • Page 1 520gr. 850gr. 1310gr. Guarantee 3 years (1 year for the battery) Thank you for your trust in our products. Olympia Electronics - European manufacturer. GENERAL methods. These sign illumination luminaires use a new WARNING !! technology, friendly to the environment, with high 1.
  • Page 2: Mounting Methods

    Mounting methods Preparation procedure Connection of the included terminal block for ceiling mounting BROWN 230V AC BLUE Attention!!! Interrupt the mains power supply. Hanging installation on suspended ceilings using the special mounting brackets 1. Open the pre-etched knock out and pass the cable through.
  • Page 3: Electrical Box Installation

    Ceiling mounting MLD-28 S: 22cm MLD-34 MLD-44 37 5 . cm 5. Place the mounting accessories in the wall and tighten the mounting screw. 1. Place the plastic mounting part 2. Tighten the screw. 3. Pass the cable in the canal. 4.
  • Page 4: Wall Mounting

    Wall mounting 5. Place the mounting accessories in the wall and screw the mounting screws Flag mounted installation on a wall using the special mounting bracket contained 1. Open the pre-etched knock out and pass the cable in the package. through.
  • Page 5 Battery replacement process Before service interrupt the mains power supply. 1 Remove the plastic cover from each side. (figure 1, step 4). 2 Unfasten the mounting screws to unmount the illumination sign (figure 1, step 2). 3 You have to disconnect the power supply wires of the sign from the terminal block. 4 Unfasten the mounting screw of the bracket and remove it.
  • Page 6: Troubleshooting

    Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

This manual is also suitable for:

Mld-28d/wMld-34d/wMld-44d/w