Magnetic Lock (DKML-S12-1, DKML-S12-1L, DKML-S12-1LT)
Mounting and Wiring Instructions
Armature Plate Mounting
1.
Follow
the
instructions
supplied
template
armature plate to a hollow metal
frame door.
Use the supplied
aluminum spacer as shown at right.
The armature plate mounts to the
door using 1 rubber washer between
2 steel washers as shown.
2.
If mounting the armature plate to a
solid wood door, follow the drilling
instructions for this type door as
shown at the right.
3.
Remember to insert the guide pins on
each side of the armature plate.
Magnetic Lock Mounting
1.
Remove the mounting bracket from
the magnetic lock.
2.
Using the supplied template, drill two
1/8 inch holes (4 ½ O.C.) and install
the mounting plate using two 5/8-inch
flathead screws. Note the type of
doorframe header and install spacer
bar or angle bracket as required to
provide
a
flat
illustrations).
3.
Adjust the mounting plate so that it
and the armature plate form a right
angle to each other.
4.
Use the mounting plate as a template
and drill the wire hole.
5.
Install four 1 ¼-inch flathead screws
through the mounting plate into the
header.
6.
Route wiring through the mounting
plate and install the lock using the
screws removed in step 1.
P/N DKML-065 REV C 5/02
on
the
to
mount
the
surface
(see
SOLID DOOR
STEP 1
Drill 5/16 through door.
STEP 2
Drill 7/16 from sexnut side
1 3/8 deep.
Insert 1 ¼ Screws
Insert 5/8 Screws
7/16 Hole for Wiring
MOUNTING BRACKET
HOLLOW METAL DOOR
STEP 1
Drill 5/16 through door.
STEP 2
Drill 11/16 from sexnut side
of door through this side only.
HEADER
MOUNTING BRKT
MAGNET
DOOR
ARMATURE PLATE
SPACER BAR
ANGLE BRACKET