MODEL DESCRIPTION
Model
Power
4683-TTM-1F
115V AC ±10%
4683-TTM-2F
230V AC ±10%
4683-TTM-3F
24VAC ±10%
These devices are "rugged" RS-485 network repeaters used for
isolating network signals and extending communication
distances. Model 4683-TTM-xF units are similar to the
Acromag Model 4SCR-TTM-x models, but add field-selectable,
End-Of-Line (EOL) network terminations on board for both the
A and B sides, are UL/cUL approved, and work at higher baud
rates.
Operation is transparent to all other network devices and no
handshaking is required. Up to 32 RS-485 devices can be
driven. These repeaters are enclosed in a rugged aluminum
enclosure and come ready to mount on any base plate, or can
be installed into a NEMA enclosure for harsh environments.
Installation is as simple as mounting, setting the baud rate,
connecting and terminating the network, and connecting power.
FEATURES
Designed for use with Johnson Controls N2 or BACnet
MS/TP bus.
No handshaking & No extra control lines required.
Full I/O signal isolation.
Supports baud rates of 600, 1200, 2400, 4800, 9600,
19.2K, 38.4K, and 76.8K, switch-selectable.
Field-selectable, End-of-Line (EOL) network terminators on
both the A (input) and B (output) sides.
Transient protection installed to help protect connected
devices from destructive noise spikes and line transients.
Status LED's indicate transmission direction, RS-485 bus
fault conditions, and power.
115VAC, 230VAC, and 24VAC models supported (no
separate transformers are required for 24VAC models).
OPERATION
The Model 4683-TTM-xF network repeaters are used to isolate
and boost RS485 signals and extend network distance. Each
repeater will permit the addition of up to another 32 devices to a
network, and extend the communication distance another 4000
feet.
The repeater has two "sides" referred to as side A and side B.
Side A typically connects to the network towards the host (input
side). Side B connects to the extended network (output side).
Functionally, sides A and B are equivalent. Transient signal
protection is provided on both RS-485 sides. When both RS-
485 lines are idle, each side is in the receive mode. When a
one to zero transition is detected (signifying a start bit) on either
side, the opposite side's transmitter is enabled (half-duplex).
The transmitter stays enabled for one character's time (based
on the baud rate switch setting). The character received is then
passed through.
The repeater receives AC power through a three-screw terminal
strip. Input power is fused and isolated. Model 4683-TTM-1F
units require 115VAC, 4683-TTM-2F units require 230VAC, and
4683-TTM-3F units require 24VAC.
⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯
Acromag Incorporated, 30765 South Wixom Road • P.O. Box 437 • Wixom, MI • 48393-7037, USA
Phone: (248) 295-0880 • Fax: (248) 624-9234 • E-mail: sales@acromag.com • On-Line: http://www.acromag.com
Copyright 1990, Acromag, Inc. Printed in the USA.
INSTRUCTIONS: Model 4683-TTM-xF
AC-Powered RS-485 Network Repeaters
COMMUNICATION SPECIFICATIONS
Baud Rates: DIP switch settings on unit for 600, 1200, 2400,
4800, 9600, 19.2K, 38.4K, & 76.8K baud rates. Only one
switch must be closed according to baud rate required for
proper operation.
RS-485 Bus Loading: One unit load equivalent.
RS-485 Bus Drive: Complete RS-485 compliance for up to 32
unit loads (31 unit loads if a repeater is used).
End-of-Line Termination Network: Refer to Figure 1. The
EOL termination network is individually selected for both
the A and B sides by a pair of shorting clips. The A side
(input) is controlled by jumpers J1 & J2. The B side
(output) is controlled by jumpers J3 & J4.
The EOL network termination is enabled for the A side or
the B side when the associated pair of jumpers are
positioned over pins 1 and 2. The EOL termination is
disabled (removed from circuit) when the pair of jumpers
are positioned over pins 2 and 3.
Duplex: Half duplex only.
Data Format: Ten bits typical (1 start bit, 8 data bits, and 1
stop bit). Other formats are supported.
Status Indicators: Red power LED; red RS-485 bus fault
LED's, side A & B; green transmit LED's, A-to-B & B-to-A.
PHYSICAL SPECIFICATIONS
Operating Temperature: -25°C to 70°C (-13°F to 158°F).
Relative Humidity (RH): 10 to 95% RH (non-condensing), up
to 40° C (104° F).
Power: 115VAC ±10%, 50/60Hz, 0.05A (Model 4683-TTM-1F);
230VAC ±10%, 50/60Hz, 0.03A (Model 4683-TTM-2F);
24VAC ±10%, 50/60Hz, 0.18A (Model 4683-TTM-3F).
Power Line Fuse: 0.5A, 250V, 3AG type. Refer to Figure 1
for fuse location.
Isolation: Unit includes galvanic and optical isolation between
RS-485 side A, RS-485 side B, AC power, and chassis
ground. Common mode voltages of up to 250Vrms, or
354V DC (withstands a 1500V AC dielectric strength test
for 1 minute without breakdown), are permitted on a
continuous basis. This complies with test requirements
outlined in ANSI C39.5-1974 for voltage ratings specified.
RFI Resistance: Withstands RFI field strengths of up to 10V
per meter at 27MHz, 151MHz, and 467MHz with no digital
effect, per SAMA PMC 33.1 test procedures.
Line Noise Effects: Field and power line terminals withstand
ANSI/IEEE C37.90-1978 Surge Withstanding Capability
(SWC) Test with no component failures. Unit is tested to
a standardized test waveform that is representative of
surges (high-freq. transient electrical interference),
observed in actual installations.
Communication Connections: Network repeater – both RS-
485 connections use modular terminal blocks with screw
clamps. Wire range is 14 to 26 AWG.
Power Wire Connections: Network repeater terminal block.
See label on unit for power to be applied to unit.
Approvals: UL/cUL Listed, US & Canada, Energy
Management Equipment.
Shipping Weight: 3.0 pounds (1.4 kg) packed per unit.
8500-758-C08H015

Advertisement

loading

Summary of Contents for Acromag 4683-TTM-1F

  • Page 1 Shipping Weight: 3.0 pounds (1.4 kg) packed per unit. ⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯ Acromag Incorporated, 30765 South Wixom Road • P.O. Box 437 • Wixom, MI • 48393-7037, USA Phone: (248) 295-0880 • Fax: (248) 624-9234 • E-mail: sales@acromag.com • On-Line: http://www.acromag.com Copyright 1990, Acromag, Inc. Printed in the USA.
  • Page 2 B - A A - B 0.30 (7.62) 6.40 0.30 (162.56) (7.62) (177.80) FIGURE 1 MODEL 4683-TTM-XF REPEATER 2.10 (53.34) MECHANICAL DIMENSIONS - 2 - Acromag, Inc. Phone: (248) 295-0880 • Fax: (248) 624-9234 • E-mail: sales@acromag.com • On-Line: http://www.acromag.com...
  • Page 3 Controls systems customers should instead refer to the Metasys® Network Technical Manual for N2 Bus Communication, or the MS/TP Communication Bus Technical Bulletin for wiring connections using the 4683-TTM-xF repeater. - 3 - Acromag, Inc. Phone: (248) 295-0880 • Fax: (248) 624-9234 • E-mail: sales@acromag.com • On-Line: http://www.acromag.com...
  • Page 4 Metasys® Network Technical Manual for N2 Bus Communication, or the MS/TP Communication Bus Technical Bulletin for wiring connections using the 4683-TTM-xF repeater. - 4 - Acromag, Inc. Phone: (248) 295-0880 • Fax: (248) 624-9234 • E-mail: sales@acromag.com • On-Line: http://www.acromag.com...

This manual is also suitable for:

4683-ttm f series4683-ttm-3f4683-ttm-2f4683-ttm series4683-ttm-14683-ttm-2