Siemens FS-RU2 Installation Instructions & User Manual

Serial relay unit,serial relay extender.

Advertisement

Quick Links

INSTALLATION INSTRUCTIONS
Model FS-RU2 Serial Relay Unit
Model FS-RE8 Serial Relay Extender
The FS-RU2 Serial Relay Unit is an optional accessory for the FS-250 and FS-250C Fire Alarm System
Control Panels. The FS-RU2 includes a processor board and a relay board. The processor board receives
commands from the control unit for activating the relays and transmits supervision and control functions to
the control unit. The processor board can control up to 3 relay boards. Each relay board provides 8 relays
with Form C contacts. The control unit can address up to 8 Serial Relay Units and/or Serial Annunciator
Units. Auxiliary power supplies will be required to power units beyond the control unit capability.
FS-RU2 PARTS SUPPLIED
1
Processor Board Assembly
1
Relay Board Assembly
1
34 pin Cable Assembly, 3 1/2"
1
PCB Track, 14 1/2"
1
10 pin Cable Assembly, 6"
1
Screwdriver
3
Keps Nut, #6-32
1
Instruction Sheet
FS-RE8 PARTS SUPPLIED
1
Relay Board Assembly
1
34 pin Cable Assembly, 15"
1
34 pin Cable Assembly, 3 1/2"
1
PCB Track, 14 1/2"
3
Keps Nut, #6-32
1
Instruction Sheet
S1
P6
SW-1
FS-RU2 DIMENSIONS
S1
FS-RE8 DIMENSIONS
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
P/N 315-049308-6 (v12-14-09)
Step 1.) Installation is to be done by qualified personnel
who have thoroughly read and understood this
instruction sheet.
Step 2.) Disconnect BATTERY and AC prior to working on
equipment.
Step 3.) Mount enclosure that is UL Listed for Fire
Protective Signaling Use as required in a dry
protected environment.
Step 4.) Attach conduit and run wires as required in a dry
protected environment.
Step 5.) Set processor board dip switch (SW1) for proper
remote address (See FS-RU Address Setting).
Step 6.) Set each relay board dip switch (S1) for proper
relay set number on the relay board (FS-RE8).
NOTE: Relays are numbered from left to right:
Relay Set
TB1
TB2
(1-8)
1
2
3
(9-16)
9
10
11
(17-24)
17
18
19
Step 7.) Set jumper P6 for desired buzzer operation.
P6 – BUZZER ACTIVATION
REMOTE
LOCAL (Processor Board Buzzer)
NOTE: When "Local" is selected, the buzzer follows the sounder
on the panel. When "Remote" is selected, the local
buzzer does not activate, but the "Remote Buzzer Output"
pin of P2 follows the sounder on the panel.
Step 8.) Mount PCB Track(s) using #6-32 keps nuts and
snap in PCB assemblies.
Step 9.
Plug in the cable assembly(s) to the PCB
assemblies as required.
Step 10. Connect ground wire(s) to chassis ground using
#6-32 keps nut(s).
Step 11.) Connect IN wires from fire alarm system control
unit or previous remote as required.
Step 12.) Connect OUT wires to next remote or 120 ohm
E.O.L. Resistor Assembly (P/N 140-050008-1), if
last remote.
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada
TB3
TB4
4
5
6
7
8
12
13
14
15
16
20
21
22
23
24

Advertisement

loading

Summary of Contents for Siemens FS-RU2

  • Page 1 Model FS-RU2 Serial Relay Unit Model FS-RE8 Serial Relay Extender The FS-RU2 Serial Relay Unit is an optional accessory for the FS-250 and FS-250C Fire Alarm System Control Panels. The FS-RU2 includes a processor board and a relay board. The processor board receives commands from the control unit for activating the relays and transmits supervision and control functions to the control unit.
  • Page 2 Step 13.) Connect relay contacts, as required. Step 15.) Program control unit for required relay operation. Step 14.) Apply power to system. Step 16.) Check for proper operation of functions. FS-RU2 / FS-RE8 WIRING Programmable Relay Contacts (Shown in normal standby condition) 1A@28VDC max., Resistive...
  • Page 3 The P2 connector on the processor board assembly of the FS-RU2 allows the unit to be connected to an annuniator to display system status and ancillary control of the panel. NOTE: If used for ancillary control of the panel, it must be located in a locked enclosure.
  • Page 4 P/N 315-049308-6...