United Electric Controls 120 Series Installation And Maintenance Instructions Manual

Explosion-proof temperature and indicating temperature switches and controls

Advertisement

Quick Links

Please read all instructional literature carefully and thoroughly before starting. Refer to the final page for the listing of
Recommended Practices, Liabilities and Warranties.
GENERAL
MIsuse of ThIs producT May cause explosIon and
personal Injury. These InsTrucTIons MusT be Thoroughly
read and undersTood before unIT Is InsTalled.
ThIs equIpMenT Is suITable for use In class I, dIvIsIon 1,
groups b, c and d; class II, dIvIsIon 1, groups e, f and g;
class III; or non-hazardous locaTIons only. enclosure
Type 4x, 7 & 9.
ThIs equIpMenT Is aTex cerTIfIed for equIpMenT caTegory
2. suITable for approprIaTe use In gas zone 1 & dusT
zone 21 applIcaTIons.
deMKo 09 aTex 0815573x
0539 Iecex ul 03.0001x
II 2 g ex d IIc T6 gb
II 2 d ex tb IIIc T85°c db Ip66
-40°c ≤ TaMb. ≤ + 75°c
These producTs do noT have any fIeld replaceable
parTs. any subsTITuTIon of coMponenTs May IMpaIr
suITabIlITy for class I, dIvIsIon 1.
To prevenT IgnITIon of hazardous aTMospheres,
dIsconnecT supply cIrcuITs before openIng. Keep cover
TIghT whIle cIrcuITs alIve.
The 120 series temperature switch utilizes either a liquid filled sens-
ing stem (immersion stem, direct mounting) or liquid filled sensing bulb
(bulb & capillary, remote mounting) to detect a temperature change. The
response at a pre-determined set point(s), actuates a spdT, dual spdT,
or dpdT snap-acting micro switch(es), converting the temperature signal
into an electrical signal. control set point(s) may be varied by turning
the adjustment hex (c120, f120) or the external knob(s) and pointer(s)
(b121, b122, e121, e122, e122p, 820e, 822e) according to the proce-
dures outlined (see part II - adjustments)
MaxIMuM TeMperaTure* sTaTed In lITeraTure and on naMe-
plaTe MusT never be exceeded, even by surges In The sys-
TeM. occasIonal operaTIon of unIT up To Max. TeMpera-
Ture Is accepTable (e.g., sTarT-up, TesTIng). conTInuous operaTIon
should be resTrIcTed To The desIgnaTed adjusTable range.
*Maximum Temperature - the highest temperature to which a sensing ele-
ment may be occasionally operated without adversely affecting set point
calibration and repeatability.
please refer to the product bulletins for product specifications. product
bulletin may be found at www.ueonline.com.
date code format on nameplate is "yyww" for year and week.
120 Series Explosion-Proof
Temperature and Indicating
Temperature Switches and
Controls
Local Mount Types B121, B122, C120
Remote Mount Types E121, E122, E122P, F120;
820E, 822E
Part I - Installation
– screwdriver/adjustable wrench to 1 1/2"
TOOLS NEEDED
MOUNTING
The connecTIon of The devIce shall be Made by cable
enTrIes or a sToppIng box cerTIfIed In Type of explosIon
proTecTIon flaMeproof enclosure 'd,' suITable for The
condITIons of use and correcTly InsTalled.
To prevenT IgnITIon, seal all conduIT runs wIThIn 18 Inches
of enclosure.
always hold a wrench on The TeMperaTure housIng hex
when MounTIng unIT. do noT TIghTen by TurnIng enclosure.
ThIs wIll daMage sensor and weaKen solder or welded
joInTs.
InsTall unITs where shocK, vIbraTIon and TeMperaTure
flucTuaTIons are MInIMal. MounT unIT To prevenT MoIsTure
froM enTerIng The enclosure. IT Is IMperaTIve To use
properly raTed explosIon-proof sealIng fITTIngs for elecTrIcal
wIre enTry. do noT MounT unIT In aMbIenT TeMperaTures ThaT
exceed The lIMITs on The naMeplaTe for The approprIaTe area.
c120, f120, 820e and 822e enclosures are provIded wITh
Two 3/4" npT elecTrIcal conduIT openIngs, eITher of whIch
or boTh can be used durIng InsTallaTIon. a 3/4" explosIon
proof plug* Is provIded for properly sealIng The unused conduIT
openIng. The explosIon proof plug MusT be properly sealed
durIng producT InsTallaTIon.
do noT KnocKouT any plugs on explosIon-proof Types 820e
or 822e
remote mount types e121, e122, e122p & f120 temperature controls
can be mounted vertically (temperature assembly facing down) or horizon-
tally. The conduit connection must be properly sealed (potted) for horizontal
installation. controls may be surface mounted via the four 1/4" screw clear-
ance holes on the enclosure or through the use of a mounting bracket (see
Mounting dimensions).
*plug is approved explosion-proof with the product as a full assembly and does not carry indi-
vidual markings.
IMT120-10
Installation and Maintenance
Instructions
IMT120-10

Advertisement

loading

Summary of Contents for United Electric Controls 120 Series

  • Page 1 Two 3/4” npT elecTrIcal conduIT openIngs, eITher of whIch or boTh can be used durIng InsTallaTIon. a 3/4” explosIon The 120 series temperature switch utilizes either a liquid filled sens- proof plug* Is provIded for properly sealIng The unused conduIT ing stem (immersion stem, direct mounting) or liquid filled sensing bulb openIng.
  • Page 2 Breather Drain Option M450: Types C120, F120 WIRING Mount with breather drain facing down (see figure 1). The conduit connec- tion must be properly sealed (potted) for this type of installation. fIeld wIrIng MusT be raTed 90°c MInIMuM. for aMbIenT TeMperaTures below -10°c, use suITable fIeld wIrIng.
  • Page 3: Tools Needed

    This permits checking the set point by moving the lever arm upward with a finger or tool simulating thermal assembly movement. connect test lights afTer coMpleTIng adjusTMenTs on all 120 serIes to indicate switch operation or listen for the switch to click. loosen adjustment TeMperaTure conTrols, be sure To re-InsTall adjusTMenT “a”...
  • Page 4 zONE hAzARDOUS LOCATIONS FLAMEPROOF GAP AND jOINT DETAILS 120’S activation plunger to adjustment screw hole gap joints: 1.140” min length by 0.0039” max annular gap plunger guide to enclosure through threaded joints: minimum 8 ½ fully engaged threads cover to enclosure through threaded joints: minimum 7 ½ fully engaged Figure 7: Indicating Enclosure Internals threads correct any difference between the Indicating pointer and the test...
  • Page 5 Dimensions External Set Point Adjustment, Types B121, B122, E121, E122, E122P Internal Set Point Adjustment, Types C120, F120 Dimension A Dimension A Model Inches 120,121 9.12 231,4 Immersion stem Model Inches 120,121 254,0 Immersion stem 1bs-8bs 8.47 214,8 bulb & capillary 2bs-8bs 237,0 bulb &...
  • Page 6: Limited Warranty

    RECOMMENDED PRACTICES AND WARNINGS United Electric Controls Company recommends careful consideration of the following factors when specifying and installing UE pressure and temper- ature units. Before installing a unit, the Installation and Maintenance instruc- tions provided with unit must be read and understood.