REGIS F – Access or time and attendance controller with integrated fingerprint reader
REGIS F – ACCESS or TIME AND ATTENDANCE
CONTROLLER with INTEGRATED FINGERPRINT
The Regis is a controller with built-in fingerprint reader, proximity
card reader and 3" LCD capacitive touch screen display. It is
designed for residential and business buildings, offices, shops, etc.
The controller can have 125kHz or 13.56MHz reading frequency.
The entire set-up procedure is carried out with the software. The
controller allows access for up to 500 fingerprints, 30000 users and
saves 100000 events. If you bought the controller in time and
attendance KIT, then inputs and outputs cannot be controlled.
The SDK is also available for this controller. If a user or software
producer wants to develop its own application, please contact us.
TECHNICAL DATA
REGIS F
REGIS F-1-B reading frequency
REGIS F-1-B reading distance
REGIS F-1-9 current consumption in
standby mode
REGIS F-3-B reading frequency
REGIS F-3-B reading distance
REGIS F-3-B current consumption in
standby mode
Dimensions (mm)
Protection
Operating voltage
Operating temperature
Display
Tamper
Display resolution
Humidity
Memory
Inputs
Outputs
Clock
Communication
Keypad
Sensor protection
Sensor usage
CONNECTOR DESCRIPTION
Contact
Description
1 - UIN
9-14V DC
2 - GND
GND
3 - CA
CA - RS485
4 - CB
CB - RS485
5 - O0
El. strike output
6 - O1
Alarm output
7 - I0
Door status switch input
8 - I1
Push button input
Black line
125kHz
Up to 10cm
200mA
13.56MHz
Up to 7cm
230mA
(WxHxD)
IP21
From 9V to 14V DC
From -20°C to 60°C
3" TFT - resistive touch
Accelerometer
400 x 240
10-80%, non condensing
500 finger prints
30000 cards or codes
100000 events
Door status
Push button
Transistor output for el. strike
0.5A
Real time clock, battery backup
(max. ten hours)
RS485
Ethernet
Configurable buttons and
selectable colors – with Keypad
Editor
> 15kV ESD protection
> 1 million wear cycles
Specification
Power supply
Ground
Communication line
Communication line
Max. 0,5A
When active = GND
When active = GND
Active when
connected to GND
Active when
connected to GND
ETHERNET
Contact
Description
9 - TXP
Ethernet
10 - TXN
Ethernet
11 - RXP
Ethernet
12 - RXN
Ethernet
Power supply
The controller need's external power supply to operate. The Spider
W40 power supply is sufficient to power two controllers and two
12V electric strikes or two 12V magnetic locks (0.5A). If you will
use it as a standalone controller and low consumption electric
strike (0.25A) you can use power supply Spider W5.
Voltage drops and cable signal interferences
When you connect the controller, use cable with a diameter of at
2
least 0.22mm
. If the cable length exceeds 25m, use one twisted
pair of UTP cables for the positive (+) pole and one for the
negative (-) pole. The cable length between power supply and the
controller should not exceed 50m.
Take into consideration that a 0.22mm
approximately 9 ohm per 100m. The power supply at the end of
cable should be a minimum of 9V. If you are using el. strike, it is
highly recommended that the voltage drop is calculated. At greater
distances, a thicker cable of 0.5mm
wherever possible.
If the load is, for example, 0.5A (with el. strike) then, on the
2
0.22mm
cable voltage drop will be 4.5V at 100m. For the device
with 60mA consumption, the voltage drop is 0.5V.
Reading distance depends on where the controller is installed. The
presence of metal or interferences can significantly reduce the
reading distance. DO NOT install the controller directly on metal
surfaces and/or cover it with a metal cover.
It is not recommended to install controllers closer than 30cm
from each other in any direction. Otherwise, it may result in
inaccurate readings or, indeed, in the controller not reading at
all.
For the Regis F-3-B to comply with EMC directives (CE), you
have to put ferrite core on the cable as close to the
controller as possible, making two turns!
Inputs, outputs and environment
Inputs:
Inputs are realized with opto-isolators. The input is active, when
pulled to ground with an open collector transistor or mechanical
switch, which is connecting the input pin of the controller to the
Ground.
Outputs:
Output has a pre-installed protection diode for an inductive load. It
is also protected from current overload. The best way is to use a
0.25A el. strike or a 0.5A el. magnet, which has to be connected to
the same positive pole (+) as the controller. Connect the negative
pole (-) to the door strike output (wire 3). When the output is
active it is pulled to ground. This can be changed with function 5 –
negate output (for el. magnet).
Reading range:
The controller has a program algorithm that, at power start, sets
parameters based on the installation environment, so as to ensure
an optimal reading range. DO NOT install the controller directly on
metal surfaces and/or cover it with a metal cover; it may stop
working/reading. If you plan to test the controller and move it onto
different surfaces, then you have to reset it (power off/on) on each
surface.
Specification
RJ45 connector
TXP
1 – white/orange
TXN
2 – orange
RXP
3 – white/green
RXN
6 - green
2
cable has a resistance of
2
or more should be used
www.jantar.si
9/2016