olympia electronics BS-375/WP/A Manual

Waterproof gas detector with relay

Advertisement

Quick Links

BS-375/WP/A Waterproof ( IP65) LPG detector with relay
BS-376/WP/A Waterproof natural gas - methane detector with relay
II 3G
Ex ec IIA T6 Gc
OPERATION VOLTAGE
MAXIMUM CONSUMPTION
% L.E.L ALARM
SENSOR TYPE
MEASUREMENT RANGE
SENSOR LIFE SPAN
SENSOR STABILIZATION PERIOD
DURING STARTUP
RESPONSE TIME (Τ
)
90
REPEATABILITY
MAXIMUM DEVIATION (after calibration)
CHANGE
INDICATORS
OUTPUTS / CONNECTIVITY
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION AND STORAGE
CONDITIONS
CONSTRUCTION MATERIAL
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
(*) = (Ideal conditions) When the detector is exposed to cleaning agents, silicons and generally
in commercial and light industrial environments, it is recommended to be calibrated every year
and its sensor to be replaced every 3 years!
ATTENTION!! DO NOT USE LIQUID GAS (i.e. lighter gas) FOR SENSOR TESTING BECAUSE IT
CAUSES PERMANENT DAMAGE. Use calibration gas up to 50% L.E.L. for this purpose.
(**) = does not cover the gas sensor, if it is exposed to Si, H2S, Pb & halogenated hydrocarbon.
GENERAL
The BS-375/WP/A and BS-376/WP/A explosive
gas detectors are used to measure the
concentrations in % L.E.L. (Lower Explosive
L e v e l ) w h i l e s i m u l t a n e o u s l y p r o v i d i n g
autonomous notification/alarm operations in
case there is a leak of liquid on natural gas.
They are used in commercial and small
industrial areas such as professional kitchens
and burner rooms.
The installation must be done by trained
p e r s o n n e l t h a t h a s p r e v i o u s l y r e a d t h e
instruction manual.
In case on an alarm or gas leak:
Page 1 from 7
TECHNICAL CHARACTERISTICS
Thank you for your trust in our products
Olympia Electronics - European manufacturer
10-30V DC / 7.5-21V AC
Selectable at 10% and 20% L.E.L
60 seconds
<45 seconds
≤ ±1,5 L.E.L.
≤ ±1,5 L.E.L.
≤ ±4.5 L.E.L./year
Operation LED (green)
Alarm LED (red)
Fault LED (yellow)
Alarm relay (24VDC, 1A, N.C. & N.O.), latching/non-latching
Fault relay (24VDC, 1A, N.O.)
Connection terminal to fire alarm panel
EN 60079-29-1, ΕΝ 50270, ΕΝ 50271
-10 to 60 C
10 to 95% relative humidity (with no condensation)
1 atm ±10%
ABS/PC, PC
145 x 85 x 45 mm
Keep calm and follow the instruction below
independent of their order.
- Turn off all burning flames and anything that is
smoking.
- Close all gas appliances (kitchens - burners
cookers etc.)
- Close the central gas supply or canister.
- Open doors and windows in order to ventilate
the area.
Avoid :
-Turning on/off the wall switches or the detector.
-Using a mobile phone in the area that is
suspected to have the gas leak.
If the alarm continues then evacuate the building
3VA
catalytic
0-50 L.E.L.
5 years (*)
IP65
o
180gr.
2 years (**)
921375000_09_007

Advertisement

loading

Summary of Contents for olympia electronics BS-375/WP/A

  • Page 1 BS-375/WP/A Waterproof ( IP65) LPG detector with relay BS-376/WP/A Waterproof natural gas - methane detector with relay II 3G Ex ec IIA T6 Gc TECHNICAL CHARACTERISTICS OPERATION VOLTAGE 10-30V DC / 7.5-21V AC MAXIMUM CONSUMPTION % L.E.L ALARM Selectable at 10% and 20% L.E.L...
  • Page 2 - Silicones (e.g. insulation, glues, detergents) - Sulfuric compounds Dip-switches settings - halogenated hydrocarbon. The BS-375/WP/A and BS-376/WP/A detectors - Organic phosphoric compounds. (figure 5), have six dip-switches to adjust the operation mode. Installation Below you can see these mode settings and...
  • Page 3 4 screws Operation, Alarm and Fault Indicator Sensor head located downwards Figure 1. Interior access, cable entry and indicators Terminal resistor 8,2Κ Fire detection panel Olympia Electronics Figure 2. Connection with fire detection panel Olympia Electronics 921375000_09_007 Page 3 from 7...
  • Page 4 Terminal resistor 8,2Κ Figure 4. Connecting 4 gas detectors to an olympia electronics conventional panel. Apart from connecting the zone terminal blocks, the detectors must be powered using the 24V terminal blocks. The total number of detectors that can be connected to a panel depends on the current that the panel can supply.
  • Page 5 Alarm relay 20%). The LED is deactivated when the gas The alarm relay is activated when the concentration returns to normal levels. If concentration % L.E.L. of the sensed area the latching function has been selected via exceeds the alarm level (10% or 20%). The the S3 micro switch then the LED remains relay returns to normal operation when the active (blinks every second) even if the gas...
  • Page 6 -It is suggested to conduct the calibration 1. Ensure that the environment is clean an free test at least once every 12 months. from explosive gases. -During the calibration procedure, conduct 2.Remove the gland with the filter located on a clean air calibration and then a reference the sensor head (figure 1).
  • Page 7: Warranty

    Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

This manual is also suitable for:

Bs-376/wp/a