TSR
Self-Regulating Pipe Tracing Heating Cable
Specification/Application Guide
READ CAREFULLY
PRINCIPLE OF OPERATION
Easy Heat TSR is a self-regulating heating cable that automatically
varies its heat output with changes in surrounding temperature.
Since this cable regulates its heat output with temperature,
a thermostat may not be necessary for some applications.
Easy Heat TSR cable can be used for pipe freeze protection or
temperature maintenance applications, in either ordinary or
hazardous (CID2) locations. TSR cable is also available with fluor-
opolymer overjacket for use in areas requiring enhanced chemi-
cal resistance. TSR cable with fluoropolymer overjacket is suitable
for maintaining grease and fuel lines at temperatures required for
flow conditions.
The TSR cable is available with power densities of 3, 5, 8 and 10
Watts per foot. This power is specified at a surrounding tempera-
ture of 50
F. At other temperatures, of course, the cable power
o
output will be considerably different. (See chart).
Nominal Power Output on
Metal Pipe
10
10
/
w
ft
8
8
/
w
ft
6
5
/
w
ft
4
3
/
w
ft
2
0
25
50
75
100
Pipe Temperature
©2008 Easy Heat
TSR SPECIFICATIONS/APPLICATION INFORMATION
Performance and Rating Data
Catalog
Number
TSR31J
TSR32J
TSR51J
TSR52J
TSR81J
TSR82J
TSR101J
TSR102J
Note: All above cables are also available with fluoropolymer over jacket (for enhanced
chemical resistance, change suffix J to F). *Lengths good for 208 & 277 VAC
Voltage Adjustment Table
Cable
(Suffix J/F)
TSR32
TSR52
TSR82
125
150
TSR102
o
F
Note:
1) Maximum maintenance temperature of all cables is 150
185
2) For applications in hazardous (classified) locations, all cables have a
T5 surface temperature identification number.
CONSTRUCTION DETAILS
poLyoLeFin
oVer
FLAMe retArdAnt
JAcKet
tpe oUter JAcKet
Because of the self-regulating feature of this cable, it can be
wrapped over itself (overlapped), if necessary, when installed on
pipes, valves or flanges.
Service
Voltage
120
240
120
240
120
240
120
240
Power Rating multiplier
208
220
VAC
VAC
0.85
0.91
0.87
0.92
0.88
0.93
0.89
0.94
o
F (85
o
C) maximum intermittent exposure temperatures.
www.easyheat.com
tpe inner
JAcKet
irrAdiAted SeLF-reGULAtinG
HeAtinG core MAteriAL
tinned copper
GroUnd
BrAid
Power Rating
Watts/ft
@ 50
F (10
C)
Single Run Length
o
o
3
325' (99m)
3
650' (198M)*
5
270' (82M)
5
540' (165M)*
8
210' (64M)
8
420' (128M)*
10
180' (55M)
10
360' (110M)*
277
VAC
1.13
1.09
1.08
1.05
16 AWG
BUS
tinned
WireS
copper
Maximum
o
F (66
o
C) with
40252-001 Rev. 5