Download Print this page
sauter AXM 117SSeries Manual

sauter AXM 117SSeries Manual

Motorised drive (with positioner) for unit valves

Advertisement

Quick Links

AXM 117S: Motorised drive (with positioner) for unit valves
How energy efficiency is improved
Automatic valve adjustment and intelligent cut-out enable maximum energy efficiency.
Areas of application
Actuation of through and three-way unit valves in the VUL, BUL, VXL and BXL series. For controllers
with continuous output in combination with intelligent unitary control systems.
Features
Pushing force 120 N
Fits onto valve with M30 × 1.5 thread
Stepping motor with control and electronic cut-off
Version with control action A or B or adjustable
Maintenance-free gearbox
Suitable for retrofitting existing installations using an appropriate adaptor
Operating status control using integrated LED display
Technical description
Two-part plastic housing, light grey (RAL7035)
Nickel-plated brass nut
Connecting cable, light grey 1.50 m long, 3 × 0.25 mm²
Running time for 4 mm stroke: 60 s
Installation position: vertical to horizontal, but not upside down
Type
Direction of
operation
AXM 117S F202
1
AXM 117S F302
2
AXM 117S F402
1 or 2
Power supply 24 V~
Power consumption on
starting
Control voltage
Control voltage F402
3)
Control current
Max. operating temperature
Accessories
0371235 001
Adaptor for fitting to Oventrop valves (M30 × 1)
0550393 001
Adaptor Danfoss RA2000, 22 mm
0371356 001
Adaptor for fitting to Beulco or Tobler underfloor-heating distribution stations (M30 × 1)
0550393 002
Adaptor Danfoss RAVL, 26 mm
0550393 003
Adaptor Danfoss RAV, 34 mm
0371361 001
Adaptor for fitting to Herz valves, type Herz-TS'90 (M28 × 1,5)
0371363 001
Adaptor for fitting to Tour & Andersson valves, type TA/RVT (M28 × 1,5)
1)
Direction of operation 1: rising 0...10V = drive retracts (VXL, VUL, BUL opens, BXL control passage closes).
Direction of operation 2: rising 0...10V = drive extends (VXL, VUL, BUL closes, BXL control passage opens).
2)
Pushing force: min. 100 N, max. 150 N
3)
The direction of operation and the setting of the control voltage can be set using jumpers
Operation
During commissioning (with valve fitted), the actuator moves to the two end positions and memorises
the number of steps taken to do so. The 0...10 V control signal is then linearly assigned to this effec-
tive stroke. The motor activates the valve and switches off as soon as the stroke position concurs with
the controller signal. In the end positions or in the event of an overload, the motor is switched off with-
in 2 minutes. If the control voltage has not changed for 2 hours (in the range 0...0,5 V), the motor –
after approx. 2 hours – runs briefly to the end positions and, if necessary, corrects its position
memory. A complete cycle is performed every 24 hours on the AXM117SF202 and F302 in order to
prevent the plug from jamming. The LED lights up when power is applied to the drive, and flashes
when the motor is running.
Running
Stroke
1)
time
s
mm
60
4
60
4
60
4
3)
± 15%, 50...60 Hz
5 VA
0...10 V; Ri = 20 kΩ
0...10 V; 5,2...10 V; 0...4,8 V
max. 0,5 mA
100 °C at valve
Thrust
Power
N
120
24 V~
2)
120
24 V~
2)
120
24 V~
2)
Ambient temperature
Ambient humidity
Type of protection
Protection class
Wiring diagram
Dimension drawing
Fitting instructions
Sauter Components
100 %
0 %
0 V
Weight
kg
0,15
0,15
0,15
–0...50 °C
< 75% rh
IP 40 (EN 60529)
III (IEC 60730)
A06147
M06146
MV 505456
55.011
M
Y07552
Output signal y
10 V
B07650
7155011003 07

Advertisement

loading

Summary of Contents for sauter AXM 117SSeries

  • Page 1 A complete cycle is performed every 24 hours on the AXM117SF202 and F302 in order to prevent the plug from jamming. The LED lights up when power is applied to the drive, and flashes when the motor is running. Sauter Components 7155011003 07...
  • Page 2 å rö d vi t zw a rt b la u w ro o d w it VUL / VXL B10 094 a M06146a Sauter Components 7155011003 07...
  • Page 3 Auto reset 0-10V 5,2-10V 0-4,8V input y no function Direction B09297a Printed in Switzerland Right of amendment reserved N.B.: A comma between cardinal numbers denotes a decimal point © Fr. Sauter AG, CH-4016 Basle Sauter Components 7155011003 07...

This manual is also suitable for:

Axm 117s f202Axm 117s f302Axm 117s f402