A GUIDE TO THE INSTALLATION, OPERATION AND MAINTENANCE OF
FLOWMETERS IN AUTOMATIC SPRINKLER INSTALLATIONS
T
YPE
F
IRESURE
Contents:
1
1.1
1.2
1.3
2
2.1
2.2
2.3
2.4
3
3.1
3.2
3.3
4
4.1
4.2
IOM FS Iss 9; April 2012; ECR1269
M e a s u r e m e n t s L t d
Email: sales@influxmeasurements.com
FIRESURE
- F
IREGROOVE
F
T
LOWMETER
....................................................................................................................................... 2
...................................................................................................... 2
PECIFICATION
....................................................................................................................... 2
..................................................................................................................... 3
P
................................................................................................... 4
REPARATION
I
................................................................................................... 5
NDICATOR
........................................................................................................................... 6
............................................................................................................................... 7
................................................................................................................ 7
EADING
................................................................................................................................... 7
................................................................................................................ 8
NDICATOR
........................................................................................................................ 8
Cert No.464a/01-10
T
- F
YPE
IREFLANGE
T
- F
YPE
- A
YPES
PPROVED BY
LPS 1045.1
Quality Systems Certificate No. 464
Assessed to ISO 9001:2008
IREFLANGE
LPCB
Page 1 of 8
MANAGEMENT
SYSTEMS
Page

Advertisement

Table of Contents
loading

Summary of Contents for INFLUX MEASUREMENTS FIRESURE FIREGROOVE

  • Page 1: Table Of Contents

    M e a s u r e m e n t s L t d MANAGEMENT 1a Bennett House, The Dean, Alresford, Hampshire, UK. SO24 9BQ. SYSTEMS Tel: +44 (0)1962 736736 Fax: +44 (0)1962 736737 Email: sales@influxmeasurements.com Quality Systems Certificate No. 464 Assessed to ISO 9001:2008 A GUIDE TO THE INSTALLATION, OPERATION AND MAINTENANCE OF FIRESURE...
  • Page 2: Specification And Principle Of Operation

    Specification and Principle of Operation Firegroove and Fireflange Type Introduction The Firesure flowmeter is a direct reading flowmeter, approved for use under the LPCB rules for automatic sprinkler installations. These meters have been approved for installation with gauge glass in the vertical position. There must be at least five diameters of straight pipe upstream and downstream of the orifice plate.
  • Page 3: Installation

    Installation Pipe Line Configuration Firegroove Firegroove 90mm 100mm Size 200 Sizes 50-150 40mm Fireflange Optional Full Bore Control Isolation Valve Valve From Pump Return 464a/01, 464a/06 F3/1, F3/6 BS1387 464a/02, 464a/07 F3/2, F3/7 BS1387 464a/03, 464a/08 F3/3, F38 BS1387 464a/04, 464a/09 F3/4, F3/9 BS1387 464a/05, 464a/10...
  • Page 4: Main Orifice Carrier

    Main Orifice Carrier Preparation a) For Horizontal Pipe Work Mounting – Connect joggled connection pipes as shown White Flow Flow Direction Direction Left to Right to Left Right White b) For Vertical Pipe Work Mounting – Connect joggled connection pipes as shown Flow Direction Down White...
  • Page 5: Connecting The Bypass

    Connecting the Bypass Indicator Remove red plastic stop and retaining rod from top block. Remove retaining screw and assemble restrictor and bleed assembly to indicator top block with retaining screw in place. Rear view of indicator piping as supplied suitable for connection to main orifice carrier for horizontal flow right to left or vertical flow upward.
  • Page 6: Installation In-Line

    Installation In-Line White a) Ensure direction arrow is consistent with viewed direction of flow and position Fireflange between pipeline flanges concentrically. Concentricity can be achieved by ensuring the carrier outside diameter is central to the fixing bolts. b) Firegroove type should be fitted with approved couplings suitable for groove cut joints. c) When fitting Fireflange type, ensure that any sealing gaskets do not obstruct the pipe line or carrier bore.
  • Page 7: Operation

    Operation Flow Test Ranges The Firesure flowmeter is designed to test that the automatic sprinkler installation meets the required flow rate needs. Each size of flowmeter meets a particular duty as shown below. Size Flow Range 150-700 300-1600 500-3500 900-7900 2000-15000 Flow Testing and Reading Open...
  • Page 8: Maintenance

    Maintenance Changing Glass Indicator In case of breakage a glass tube indicator would be required. Refer first to the black printed Firesure model number F3/- on the carrier label or tube before ordering a replacement. NOTE: This model uses BLACK scaled tubes. These should not be replaced with RED scaled tubes which are used for the extended indicator model (Firesure X).