MAMAC SYSTEMS PR-274 Technical Information

Low pressure sensor

Advertisement

Quick Links

8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA
800-843-5116 • 952-556-4900 • Fax 952-556-4997
sales@mamacsys.com • www.mamacsys.com
For Additional Information See PR-274/275 Data Sheet

SPECIFICATIONS

Accuracy*: ±1% FS
Overpressure: 10 PSID
Supply Voltage: 12-40 VDC
12-35 VAC (VDC output units only)
Supply Current: VDC Units - 10 mA max.
mA Units - 20 mA max.
Enclosure: 18 Ga C. R. Steel NEMA 4 (IP-65) or Panel Mount Chassis
Finish: Baked on enamel-PMS2GR88B
EMC Conformance: EN 55022, 55024, 61000-3-3,
61000-4-2, 3, 4, 5, 6 & 11
Compensated Temp Range: 25°F-150°F (-4°C-65°C)
T. C. Error: ±0.0125%/°F (.02%/°C)
Operating Temp Range: 0°F-175°F (-18°C-80°C)
Media Compatibility: Clean dry air or any inert gas
Environmental: 10-90%RH Non-Condensing
Termination: Unpluggable screw terminal block
Wire Size: 12 Ga max.
Load Impedance: 1.6K ohms max. at 40 VDC (mA output units)
1K ohms min. (VDC output units)
Weight: Enclosure - 1.0 lbs. (.45 kg)
Panel Mount - 0.5 lbs. (.25 kg)
ORDERING INFORMATION
PACKAGING
274 (enclosure)
R1
0 TO 0.10 / -0.05 TO +0.05
("wc)
275 (panel mount)
R2
0 TO 1.0 / 0 TO 0.5 / 0 TO 0.25 /
("wc)
-0.5 TO +0.5 / -0.25 TO +0.25 /
-0.125 TO +0.125
R3
0 TO 5.0 / 0 TO 2.5 / 0 TO 1.25 /
("wc)
-2.5 TO +2.5 / -1.25 TO +1.25 /
-0.625 TO +0.625
0 TO 30 / 0 TO 15 / 0 TO 7.5 /
R4
-15.0 TO +15.0 / -7.5 TO +7.5 /
("wc)
-3.75 TO + 3.75
0 TO 25 / -12.5 TO +12.5
R5
(pa)
0 TO 250 / 0 TO 125 / 0 TO 62.5 /
R6
-125 TO +125 / -62.5 TO +62.5 /
(pa)
-31.25 TO +31.25
0 TO 1250 / 0 TO 625 / 0 TO 312.5 /
R7
-625 TO +625 / -312.5 TO +312.5 /
(pa)
-156.25 TO +156.25
0 TO 7500 / 0 TO 3750 / 0 TO 1875 /
R8
-3750 TO +3750 / -1875 TO +1875 /
(pa)
-937.5 TO +937.5
INSTALLATION
Inspection -
Inspect the package for damage. If damaged, notify the
appropriate carrier immediately. If undamaged, open the package and
inspect the device for obvious damage. Return damaged products.
RANGE
OUTPUT
mA
(4-20 mA
2-wire)
VDC
(0-5 VDC or
0-10 VDC field
selectable)
RoHS
LOW PRESSURE SENSOR
Enclosure Mount
Transducer
Requirements
Tools (not provided)
- Digital Volt-ohm Meter (DVM)
- Appropriate screwdriver for mounting screws
- Appropriate drill and drill bit for mounting screws
Appropriate accessories
Two #8 self-tapping mounting screws (not provided)
Training: Installer must be a qualified, experienced technician
Warning:
Disconnect power supply before installation to prevent electrical
shock and equipment damage.
Make all connections in accordance with the job wiring diagram
and in accordance with national and local electrical codes. Use
copper conductors only.
Caution:
Use electrostatic discharge precautions (e.g., use of wrist straps)
during installation and wiring to prevent equipment damage.
Avoid locations where severe shock or vibration, excessive
moisture or corrosive fumes are present. NEMA Type 4 housings
are intended for outdoor use primarily to provide a degree of
protection against wind-blown dust, rain, and hose-directed water.
Do not exceed ratings of the device.
Caution:
Condensate or moisture must not enter pressure sensor ports
Mounting
The PR-274/275 must be mounted as indicated by the arrows on
the enclosure. Refer to Figure 7 for mounting dimensions.
1. Remove the transducer cover using a Phillips head
screwdriver.
2. Select the mounting location.
3. Mount transducer on a vertical surface with two #8
self-tapping screws (not provided).
4. Transducer must be mounted above the pressure pick-up or a
J-Loop must be incorporated in the tubing to function as a
condensate trap.
5. Pull wires through bottom of enclosure and make
necessary connections.
6. Replace cover and make pneumatic connections.
Wiring
Use maximum 12 AWG wire for wiring terminals. Use flexible 1/4"
O.D. 5/32" I.D. tubing for the high and low pressure connections.
Refer to Figures 1, 2, 3, & 4 for wiring information and Figures 5 &
6 for switch designations.
(Wiring Instructions continued on pages 2 and 3.)
Model PR-274/275

Technical Information

TI.274/275-06
Panel Mount
Transducer

Advertisement

loading

Summary of Contents for MAMAC SYSTEMS PR-274

  • Page 1: Technical Information

    -2.5 TO +2.5 / -1.25 TO +1.25 / -0.625 TO +0.625 Mounting The PR-274/275 must be mounted as indicated by the arrows on the enclosure. Refer to Figure 7 for mounting dimensions. 0 TO 30 / 0 TO 15 / 0 TO 7.5 / -15.0 TO +15.0 / -7.5 TO +7.5 /...
  • Page 2 Shield/Ground Caution: If you are using grounded AC, the hot wire must be on the [+] terminal. Also, if you are using a controller without built-in isolation, use an isolation transformer to supply the PR-274/275. Caution: This product contains a half-wave rectifier power supply and must not be powered off transformers used to power other devices utilizing non-isolated full-wave rectifier power supplies.
  • Page 3 Model PR-274/275 Page 3 of 4 Technical Information TI.274/275-06 RoHS LOW PRESSURE SENSOR Figure 5 - Switch Selections for Low Pressure Transducers with mA Outputs Range Configuration: Bi-Directional Switch 1 (S1) Factory R1/R5 +/- 0.05 "wc / 12.5 pa Sealed mA Output R2/R6 +/- 0.5 "wc / 125 pa (default)
  • Page 4 LOW PRESSURE SENSOR CHECKOUT 1. Verify that the unit is mounted in the correct position. Figure 7 - PR-274/275 Low Pressure Transducer Dimensions shown in inches and millimeters (mm). 2. Verify appropriate input signal and supply voltage. Caution: Never connect 120 VAC to these transducers. Never 2.12"...