T48/P48/TLA OUTPUT BOARD
INSTALLING AN OUTPUT BOARD
Caution: The bezel assembly contains electronic circuits that can be damaged by static electricity. Before removing the assembly, discharge static charge on
your body by touching an earth ground point. It is also important that the bezel assembly be handled only by the bezel itself. When handling a circuit board, be
certain that hands are free from dirt, oil, etc., to avoid circuit contamination that may lead to a malfunction.
1. Remove the controller from the case.
2. Lift up on the top bezel board latch while gently pulling out on the bezel/
display board assembly. Do NOT remove the display board from the
bezel.
3. Remove the output board by pulling it away from the other boards.
Replace the output board by aligning the board to board connector. Be
certain the connector is fully mated.
4. Connect the bezel/display board assembly by guiding the board ends into
the bezel latches. Slide the assembly on evenly until the display board
connector is completely engaged and bezel latches are fully seated onto
the boards.
Note: When replacing the output board, be certain to install a new output
board of the same type. Appropriate rewiring considerations must be given if
the output board type is changed.
DISPLAY
BOARD
CONNECTOR
% P
D V
M N
O 1
BEZEL BOARD
D
A 1
A 2
P
LATCH
BEZEL/DISPLAY
BOARD ASSEMBLY
SPECIFICATIONS & TYPICAL CONNECTIONS
Relay Connections
RBD48 Relay Outputs:
Type: Form-A (Shared common for the Alarms)
Contact Rating: 3 A @ 250 VAC or 30 VDC (resistive load)
RBDLA Relay Outputs:
Limit Relay Type: Form-C
Alarm 1 Relay Type: Form-A
Contact Rating: 5 A @ 250 VAC or 30 VDC (resistive load)
Life Expectancy: 100,000 cycles at max. load rating. (Decreasing load and/
or increasing cycle time, increases life expectancy.)
To prolong contact life and suppress electrical noise interference due to the
switching of inductive loads, it is good installation practice to install a snubber
across the contactor. Follow the manufacturer's instructions for installation.
Note: Snubber leakage current can cause some electromechanical devices to
be held ON.
3
0 7 8
E B
* MODEL NUMBER DEPENDENT
AL2/O2
AL1
O1
CPU BOARD
% P
D V
M N
O 1
D
A 1
A 2
P
POWER
SUPPLY
BOARD
Main Control Output
01
CONTROLLER
Alarm Outputs/Cooling
AL2/02
N.O.
COMM.
AL1
N.O.
RELAY
AL2/O2
OUTPUT
AL1
BOARD
O1
AL1
LIMIT
SECOND INPUT/RS485 BOARD *
3
0 7 8
E B
OUTPUT BOARD
OUTPUT BOARD
CONNECTOR
N.O.
COMM.
LOAD
FUSE
LOAD
LOAD
Bulletin No. RBD48-D
Drawing No. LP0347
Released 06/13
LOGIC/SSR DRIVE
OUTPUT BOARD
Form-C Relay
Output Board
#RBDLA210
FUSE
AC/DC
POWER
AC/DC
POWER

Advertisement

loading

Summary of Contents for Red Ion RBDLA

  • Page 1 Relay Connections RBD48 Relay Outputs: Type: Form-A (Shared common for the Alarms) N.O. Contact Rating: 3 A @ 250 VAC or 30 VDC (resistive load) COMM. RBDLA Relay Outputs: LOAD FUSE Limit Relay Type: Form-C CONTROLLER Alarm 1 Relay Type: Form-A...
  • Page 2 RBD48111 RBD48 NONE NONE RBD48200 RLY-A RLY-A RBD48211 RBDLA RLY-C RLY-A NONE RBDLA210 Do not dispose of unit in trash - Recycle Note: For units equipped with a single alarm, order a dual alarm replacement board. Note: RLY-A = Form-A Relay Output...

This manual is also suitable for:

Rbd48Rbd48200Rbd48100Rbd48111Rbdla210Rbd48211