Chatsworth Products 025-712855 Series Installation Instructions Manual

Power strips, horizontal & vertical 125v, 15a or 20a

Advertisement

Quick Links

Safety Information
WARNING: Improper use of this product may lead to serious injury or
death. Read and understand all instructions for proper installation and
use of this product.
CAUTION: The input plug of this power tap is intended to serve as the
disconnect device, it shall be easily accessible and withdrawn.
CAUTION: Equipment connections to the power strip must adhere to the
nameplate ratings listed otherwise an overload condition may cause
damage to the protection circuitry and supply wiring.
.
Installation Guidelines
Overcurrent protection is an element accounted for during the building/room
design and installation. The PDU relies on adequate building overcurrent
protection. Insure that UL listed circuit breakers are utilized for overcurrent
protection.
Install the PDU using qualified installation and service personnel.
Do not inhibit cabinet airflow with the installation of the PDU.
Avoid uneven mounting which could develop into a hazardous condition.
Equipment plugged into this PDU should be grounded to a grounding bus
separate from the branch circuit grounding bus.
Insure that the outlet plugs on the PDU are easily and readily accessible for
interruption of service (disconnection). Do not block or obstruct access to the
outlets in any way.
ALWAYS disconnect all input and output power cords on the PDU before
servicing. Never install the PDU in a location where there may be a presence of
water.
Remove power to the PDU before removing existing or installing new equipment.
Installation Instructions
Power Strips, Horizontal & Vertical
125V, 15A or 20A
Notes
Elevated Operating Ambient-
rack assembly, the operating ambient temperature of the rack
environment may be greater than room ambient. Consideration should
be given to installing the equipment in an environment compatible with
the maximum rated ambient temperature of 45˚C (113 °F).
Reduced Air Flow –
such that the amount of airflow required for safe operation of the
equipment is not compromised.
Mechanical Loading –
be such that a hazardous condition is not achieved due to uneven
mechanical loading.
Circuit Overloading –
connection of the equipment to the supply circuit and the affect that
overloading of the circuits might have on overcurrent protection and
supply wiring. Appropriate consideration of equipment nameplate
ratings should be used when addressing this concern.
Reliable Earthing –
should be maintained. Particular attention should be given to supply
connections other than direct connections to the branch circuit.
Service Personnel –
access this equipment.
IIS-712855, 02/13/09, Rev.1 A. Taft
800-834-4969 • techsupport@chatsworth.com • www.chatsworth.com
This drawing contains proprietary and confidential information and is protected by U.S. and international law.
Unauthorized reproduction, disclosure or use of the drawing or the information therein is expressly forbidden
except as agreed to in writing by Chatsworth Products, Inc.
Page 1 of 2
If installed in a closed or multi-unit
Installation of the equipment in a rack should be
Mounting of the equipment in the rack should
Consideration should be given to the
Reliable earthing of rack-mounted equipment
Only service personnel should install and

Advertisement

loading

Summary of Contents for Chatsworth Products 025-712855 Series

  • Page 1 This drawing contains proprietary and confidential information and is protected by U.S. and international law. Unauthorized reproduction, disclosure or use of the drawing or the information therein is expressly forbidden except as agreed to in writing by Chatsworth Products, Inc. Page 1 of 2...
  • Page 2 Installation Specifications • 1. Mount PDU to rack/cabinet. Appropriate brackets are provided. Mounting screws UL 60950-1, CSA C22.2 60950-1-03 not included. • 125 Volt @15amp, 50/60Hz power strip de-rated to 12 amps 2. Ensure the rating of the PDU matches that of the branch circuit it is plugged into. •...

This manual is also suitable for:

025-712828 series12851 series12848 series12817 series12816 series12819 series ... Show all