Installation Instructions:
All product(s) must be installed by a suitably competent electrician
Giving consideration to their intended use and in accordance with the
current edition of BS 7671 (IET Wiring Regulations).
The Electricity at Work regulations and the Health and Safety at Work Act
shall be complied with.
Only equipment and arrangements specified in Hager's technical
documentation / catalogue shall be used.
Install in the horizontal plane only.
Important notice:
To prevent potential overheating from loose connections the installer
shall check connections are tight to the torque levels stated in these
instructions prior to energizing this board. This check should include
factory made connections which may have loosened in transit.
Cable entry facilities:
Metalclad units are provided with knockouts for standard 20, 25, and
32mm conduit and large rear knockouts.
Rear cable entries should be scored along the weak point with a sharp
knife, and tapped sharply to remove.
Note: Only BASEC approved cable should be used
1.0mm
to 16mm
for outgoing cables
2
2
up to 35.0mm
for incoming live cables
2
Single conductors below 1.5mm² need to be doubled back in the terminal bar.
1
VC & VH Consumer Unit
GB
Instructions/Data Sheet
This Consumer Unit and Hager devices conform with the following standards:
Consumer Unit: BS EN 61439-3 including Annex ZB.
Switch-disconnectors: BS EN 60947-3.
Residual Current Circuit Breaker (RCCB): BS EN 61008-1
Residual current operated circuit breaker with integral overload (RCBO): BS EN 61009-1
Miniature Circuit Breaker (MCB): BS EN 60898-1
Tightening torque values to be applied (Nm)
Switch-disconnector's: 40A & 63A: 2.8 Nm
Switch-disconnector's: 100A: 3.3 Nm
RCCB's 40A & 63A: 2.8 Nm
RCCB's 80A & 100A: 3.3 Nm
MCBs: 2.8 Nm
RCBO's: 2.8 Nm
Earth & Neutral terminal bar connections: 2.0 Nm
Single conductors below 1.5mm² need to be doubled back in the
terminal bar
Front metal cover fixing screws: 2.0 Nm
Good workmanship and proper materials must be applied by the installer.
Insulated units are provided with breakouts for standard mini trunking.
Metal Unit - Removing and replacing the terminal rail for cabling:
Pull and lift the terminal bar support away from the unit resting the rail
supported by the earth strap. After fixing conduit/ cable glands, locate
the rail support and press down.
ZD0632 - Issue 5 03-15

Advertisement

loading

Summary of Contents for hager VC

  • Page 1 VC & VH Consumer Unit Instructions/Data Sheet This Consumer Unit and Hager devices conform with the following standards: Consumer Unit: BS EN 61439-3 including Annex ZB. Switch-disconnectors: BS EN 60947-3. Residual Current Circuit Breaker (RCCB): BS EN 61008-1 Residual current operated circuit breaker with integral overload (RCBO): BS EN 61009-1...
  • Page 2 This distribution board is offered with a 24 month warranty against defective material or manufacture. If a warranty claim is necessary, please call the technical support number given at the bottom of the page and we will be pleased to help. For dimensional information and weights please consult the Hager catalogue. Hager Technical Help Line: 01952 675 689 Hager Technical Fax: 01952 675 557 Website: www.hager.co.uk...
  • Page 3 Types of system earthing for which the ASSEMBLY is designed TNC-S, TN-S when installed in an electrical installation complying with BS 7671 Hager recommends for TT systems a 100A type S time delayed RCCB or a main switch with RCBO protection only on all outgoing circuits. Indoor use only...
  • Page 4 Blank RCCB RCBO (two module) RCBO Switch (one module) START Use circuit as Use circuit as normal tripped normal RCCB RCBO Does device What device Does device Try & reset device once Try & reset device once stay ON? stay ON? is it? Turn OFF all MCBs devices...

This manual is also suitable for:

Vh