Download Print this page
ABB Stanilite Installation Manual
ABB Stanilite Installation Manual

ABB Stanilite Installation Manual

Dali emergency

Advertisement

Quick Links

Testing precautions
Once the fitting is permanently connected to the
mains supply, a commissioning discharge test as
required in AS/NZS 2293.2 must be carried out.
You will need to allow 24 hours for the battery to
fully charge prior to conducting this test,
presently (at the time of writing), the standard
requires that fittings operate in emergency
mode for a period not less than 2 hours for their
commissioning test and for not less than 90
minutes thereafter (it is required that 6 monthly
discharge tests be carried out). You will need to
keep the records for the commissioning test and
enter them into the building emergency services
logbook or via other recording methods as
allowed by AS/NZS 2293.2.
Trouble shooting guide
If you have installed and connected the unit as per the instructions listed earlier and it does not
function correctly, use the following table as a guide to fixing the problem. Look up the type of
fault in the left column and check the possible causes from the right column.
If the unit still does not work after checking these possible causes, contact ABB service in Australia
on 1800 60 20 20, Monday to Friday, 7.00am to 5.00pm (AEST) and ask for help. Our trained service
personnel will usually be able to take your call immediately and assist you in resolving your
difficulty. ABB is committed to providing valuable through-life support for its products.
No. Fault
1
LED light source and indicating LED not lit
2
LED light source is lit but indicating LED not lit
3
LED light source does not switch to emergency
mode when the test button is pressed
4
LED light source works momentarily on emergency
when the test button is pressed
ABB Australia Pty Limited
For enquiries
ABB contact centre: 1800 60 20 20
E-mail: AU-ABB-Stanilite@abb.com
www.stanilite.com.au
Construction sites
Continuously switching of the mains power
supply that is connected to emergency light
fittings during the construction phase of an
installation will cause these fittings to discharge
and charge their batteries many times over a
short period; this can shorten life of the battery.
ABB does not recommend such practices and
may not honour the warranty on batteries when
they are subjected to such harsh operating
conditions. Emergency light fittings are
designed to be discharge tested once every 6
months as per AS/NZS 2293.2, subjecting the
product to repeated discharge or charge cycles is
regarded as an abuse of the fittings.
Being a DALI Spitfire 'rest' feature is very useful
and can be used via DALI controller during the
construction phase of installaton.
Possible causes
AC supply not connected; or
AC supply turned off; or
Test switch damaged
Test switch damaged; or
Battery not connected or faulty
Test switch damaged; or
Battery not connected or faulty
Battery not yet charged (allow up to 24 hours)
© Copyright 2018 ABB. All rights reserved.
I N S TA L L AT I O N M A N U A L
Stanilite®
Spitfire® LED recessed
DALI emergency
Thank you for choosing ABB product
Please read this document thoroughly before
commencing installation and retain for future
reference. Contact ABB service in Australia on
1800 60 20 20 if you need any assistance. The
installation instructions were correct at the time
of print. To reflect changes in technology and
Australian standards; ABB reserves the right to
amend the instructions without notice. Updated
document can be found on the Stanilite website.
Safety warning
In Australia and New Zealand, only licensed
electricians are permitted by law to work with
240 volt electrical installations.
Do not attempt to install or connect this product
unless you are a licensed electrician.
Turn off and isolate the electrical supply before
connecting this fitting to the building wires.
Do not touch the terminals of the terminal block
when the light fitting is energised.
The only user-serviceable parts are the lamp
head assembly and battery pack. LED light
source is not user-servicable.
Do not attempt to service other parts of the
fitting as this will void the warranty.
As the installer, it is your responsibility to ensure
compliance with all relevant building and safety
codes, (ie: AS/NZS 3000, AS/NZS 2293). Refer to
the applicable standards for data and mains
This document covers
What's inside the box
Safety warning
Lamp head assembly
Installation instructions
Battery and control pack
Removal instructions
Accessory kit
Testing precautions
Installation manual
Trouble shooting guide
Warranty information
cabling installation procedures and
requirements.
The Spitfire recessed luminaire lamp head can be
installed with building insulation material. Such
insulation can abut sides of Spitfire lamp head.
Note: Not suitable for use with loose-fill
insulation.
The control pack and battery pack must be
installed above the insulation. No fire rated box
is required for the product.
Important: This product is designed for indoor
use only.
DALI (digital addressable lighting interface)
DALI is widely acknowledged as being an open
protocol as defined under IEC 62386 and is
designed only for communication in lighting
systems.
ABB exit and emergency luminaire with DALI
functionality comply with DALI standard IEC
62386.
The DALI Spitfire wiring consists of additional 2
control wires apart from the active and neutral
wires (4 cores) in a power cord supplied with
product.
Note: No mains or mains carrying cables are to
be connected to DALI terminals or 2 control
wires (white and black).
Doc no. 29-01163_1

Advertisement

loading

Summary of Contents for ABB Stanilite

  • Page 1 If the unit still does not work after checking these possible causes, contact ABB service in Australia reference. Contact ABB service in Australia on The Spitfire recessed luminaire lamp head can be on 1800 60 20 20, Monday to Friday, 7.00am to 5.00pm (AEST) and ask for help.
  • Page 2 Installation instructions 1. Note: The circuit supplying mains power to the fitting must not be energised until installaton of Power cable Main control unit the fitting is completed. 2. Mark and cut-out a hole in the ceiling to suit either small or large Spitfire head. The cut-out size for the standard lamp head is 50mm.

This manual is also suitable for:

Stanilite led recessed