Download Print this page

DANLERS HBA PIR ND DSIP Installation Notes

High bay pir occupancy switches with dsip dimming

Advertisement

Quick Links

Variants
Presence detection variants:
Each of these High bay PIR occupancy switches with DSIP dimming are also
available with presence detection (does not require a momentary (retractive)
wall switch).
Troubleshooting
The load will not switch on:
• The moving body is not emitting more IR than the background.
(Person wearing insulating clothing in a warm environment)
• Person is too far from the PIR switch, see detection diagram.
• Person is moving unusually slowly (perhaps when testing).
Precautions and Warranty
This product conforms to BS EN 60669-2-1. Product complies to Class 2 insulation.
Please ensure the most recent edition of the appropriate local wiring regulations are observed
and suitable protection is provided e.g. 6 amps over current, 1kV over voltage. Please ensure
that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
Please call for more information or a free catalogue, or visit our website.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
E-mail: sales@danlers.co.uk
Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
23/08/16
INS281 HBA PIR (xx) DSIP
High bay PIR occupancy switches with DSIP dimming
HBA PIR ND DSIP
HBA PIR SP DSIP
DANLERS High bay passive infra-red occupancy (absence detection) switches with
closed loop control can be used to control high frequency DSI dimmable ballasts.
They each incorporate a passive infra-red quad sensor to detect movement of a
warm body within their detection zone (diagram A) and a photocell to monitor the
ambient light level.
Each of the controls can be mounted directly onto solid ceilings or onto a range of
different mounting boxes.
The high bay controls are available in three types - each with a particular detection
pattern which is optimised for particular applications.
HBA PIR ND DSIP: Narrow Detection version is ideal for covering storage aisles.
HBA PIR SP DSIP: Spot Detection version is ideal for smaller areas, such as the
entrances to storage aisles.
HBA PIR WD DSIP: Wide Detection version is ideal for large open areas, such as
factories, sports halls and entrance halls.
Functions
When entering a zone of detection a momentary wall switch must be pressed to send a
signal to the PIR to switch the lights ON at maximum and start the closed loop control
to maintain the preset lux level value (LUX) between 30 and 1000 lux (default value
1000 lux). See diagram C.
NO BACKGROUND ILLUMINANCE RUN ON TIME SET: If no further movement is
detected the lights will switch OFF after the set PIR hold timer (TIME) has expired. This
time lag can be set via the TIME adjuster to 10 seconds, 20s, 40s, 80s, 2m30s, 5m,
10m, 20m or 40 minutes (default value 10 seconds). See diagram B. Alternatively, the
momentary switch can be pressed for more than 2 seconds to switch the lights OFF.
BACKGROUND ILLUMINANCE RUN ON TIME SET: If no further movement is detected
the lights will FADE to minimum after the set PIR hold timer (TIME) has expired OR
if the momentary wall switch is pressed for more than 2 seconds. The lights will then
stay at minimum until the background hold timer (RUN ON) has expired. The RUN
ON time can be set via the RUN ON adjuster to 0, 1, 2, 5, 10, 15, 20, 30 minutes or
infinite (default value is 0). See diagram C.
If the momentary wall switch is pressed for less than 2 seconds while the background
hold timer is counting down, the lights will switch ON at maximum and start the closed
loop control to maintain the set lux level value.
Loading
These PIR switches can switch up to:
6 amps (1500W) of dimmable fluorescent lamps.
2 amps (500W) of CFL, LED Drivers and LED lamps and fittings.
These controls have an integral DSI Power Supply Unit suitable for use with up to 12
DSI ballasts, assuming each ballast has a constant current output of 1mA.
Installation notes
HBA PIR WD DSIP

Advertisement

loading

Summary of Contents for DANLERS HBA PIR ND DSIP

  • Page 1 The high bay controls are available in three types - each with a particular detection pattern which is optimised for particular applications. HBA PIR ND DSIP: Narrow Detection version is ideal for covering storage aisles. HBA PIR SP DSIP: Spot Detection version is ideal for smaller areas, such as the entrances to storage aisles.
  • Page 2 The LUX adjuster spindle on the side of the PIR is used to regulate the automatic Optional wall switch DANLERS DSIP other load or rocker daylight linked dimming function lux level (see diagram C opposite). This should be High Bay control...

This manual is also suitable for:

Hba pir sp dsipHba pir wd dsip