S-Click CPD-360 Instruction Manual

Flush mount presence detector

Advertisement

Quick Links

OPTIMUM MOTION DETECTOR
CEILING FLUSH MOUNT VERSION
OS-365P / OS-365PA / OS-365S
OPTIMUM MOTION DETECTOR
FLUSH MOUNT
Installation and assembly of electrical equipment
PRESENCE
must be carried out by qualified electricians.
CEILING FLUSH MOUNT VERSION
DETECTOR
Contact a qualified electrician in the event of
OS-365P / OS-365PA / OS-365S
fault or break down.
Part No. CPD-360; CPD-360/2; CPD-360/2S
A circuit breaker (250VAC, 10A) type C according to
EN60898-1 of loadⅠshall be installed in the fixed wiring
for protection.
A circuit breaker (250VAC, 6A) type C according to
A circuit breaker (250VAC, 10A) type C according to
EN60898-1 of loadⅡshall be installed in the fixed wiring
AS/NZS60898.1
EN60898-1 of loadⅠshall be installed in the fixed wiring
for protection.
for protection.
Do not mount on conductive surface. Do not open the
A circuit breaker (250VAC, 6A) type C according to
enclosure frequently.
AS/NZS60898.1
EN60898-1 of loadⅡshall be installed in the fixed wiring
Turn off power when change the light sources.
for protection.
High in-rush current would be caused when bulbs of
Do not mount on conductive surface. Do not open the
certain brands burned which might damage the unit
enclosure frequently.
permanently.
TECHNICAL S PECIFICATIONS
Turn off power when change the light sources.
Disconnect power when changing the light sources.
High in-rush current may occur when lamps of certain
High in-rush current would be caused when bulbs of
R a t e d Vo l t a g e 2 3 0 V ~ ± 1 0 % 5 0 / 6 0 H z
1
brands burnout, this may permanently damage the
certain brands burned which might damage the unit
R a t e d L o a d
sensor.
PAC KAG E CONTENTS
permanently.
TECHNICAL S PECIFICATIONS
O S - 3 6 5 P
L o a d Ⅰ ( L ) f o r L i g h t i n g :
μ
R a t e d Vo l t a g e 2 3 0 V ~ ± 1 0 % 5 0 / 6 0 H z
( 2 C h a n n e l s )
Incandescent Lamp: Max. 2000W
OS-365P / OS-365PA
1
AC halogen Lamp : Max. 1000W
PAC KAG E CONTENTS
R a t e d L o a d
LV halogen Lamp : Max. 1000VA
Pattern
O S - 3 6 5 P
CPD-360/2
L o a d Ⅰ ( L ) f o r L i g h t i n g :
Fluorescent lamp
: Max. 900VA / 100μF
μ
( 2 C h a n n e l s )
Incandescent Lamp: Max. 2000W
(compensated)
CPD-360/2 / CPD-360
OS-365P / OS-365PA
AC halogen Lamp : Max. 1000W
Max. 1000VA
LV halogen Lamp : Max. 1000VA
(uncompensted)
Item
Pattern
Fluorescent lamp
: Max. 900VA / 100μF
PL Lamp
: Max. 600VA
(compensated)
L o a d Ⅱ ( D 1 - D 2 ) f o r H V A C ( P o t e n t i a l f r e e
Max. 1000VA
Quantity
c o n t a c t
f o r 2 5 0 V A C o r 3 0 V D C M a x ) :
M a x . 5 A
( c o s φ = 1 )
(uncompensated)
(uncompensated)
(uncompensted)
Item
<
Max. 2A (cosφ=0.4) for
PL Lamp
: Max. 600VA
250VAC
OS-365S (for optional pruchase)
M o t o r : 1 / 1 0 H P ( a p p r o x . 7 3 W )
L o a d Ⅱ ( D 1 - D 2 ) f o r H V A C ( P o t e n t i a l f r e e
Quantity
c o n t a c t
f o r 2 5 0 V A C o r 3 0 V D C M a x ) :
O S - 3 6 5 P A
F o r L i g h t i n g : μ
M a x . 5 A
( c o s φ = 1 )
Pattern
( 1 C h a n n e l )
Incandescent Lamp: Max. 2000W
<
Max. 2A (cosφ=0.4) for
250VAC
CPD-360/2S
OS-365S (for optional pruchase)
AC halogen Lamp : Max. 1000W
M o t o r : 1 / 1 0 H P ( a p p r o x . 7 3 W )
LV halogen Lamp : Max. 1000VA
CPD-360
O S - 3 6 5 P A
F o r L i g h t i n g : μ
Fluorescent lamp
: Max. 900VA / 100μF
Item
Pattern
( 1 C h a n n e l )
Incandescent Lamp: Max. 2000W
(compensated)
AC halogen Lamp : Max. 1000W
Max. 1000VA
Quantity
LV halogen Lamp : Max. 1000VA
(uncompensted)
Fluorescent lamp
: Max. 900VA / 100μF
Item
O S - 3 6 5 S
A n i n d e p e n d e n t d e t e c t o r w i t h 8 m s i g n a l
(compensated)
( f o r o p t i o n a l
c a b l e c a n b e c o n n e c t e d t o t h e p o w e r b o x
2
Max. 1000VA
o f O S - 3 6 5 P f o r t h e a p p l i c a t i o n o f
Quantity
p u r c h a s e )
PRODUCT DESCRIPTION
(uncompensted)
(uncompensated)
e x p a n d i n g d e t e c t i o n c o v e r a g e .
CPD-360/2S
O S - 3 6 5 S
A n i n d e p e n d e n t d e t e c t o r w i t h 8 m s i g n a l
A u t o O f f T i m e
2.1 Features
( f o r o p t i o n a l
c a b l e c a n b e c o n n e c t e d t o t h e p o w e r b o x
2
A d j u s t m e n t
p u r c h a s e )
o f O S - 3 6 5 P f o r t h e a p p l i c a t i o n o f
CPD-360/2
to expand detection area.
PRODUCT DESCRIPTION
OS-365P / OS-365PA is a ceiling flush mount motion detector for
e x p a n d i n g d e t e c t i o n c o v e r a g e .
O S - 3 6 5 P /
T i m e 1 ( f o r l i g h t i n g ) : A d j u s t a b l e f r o m 5 s e c
lighting and HVAC control. It can be widely used in small-scale
O S - 3 6 5 S
t o 3 0 m i n a n d t e s t &
1 S
A u t o O f f T i m e
office, warehouse, storeroom, kitchen, publicwashing room etc.
T i m e 2 ( f o r H V A C ) : A d j u s t a b l e f r o m 1 0 s e c
2.1 Features
A d j u s t m e n t
t o 6 0 m i n
OS-365P / OS-365PA is a ceiling flush mount motion detector for
CPD-360/2/
CPD-360/2 or CPD-360
High performance relay for connecting various lamps.
O S - 3 6 5 P /
T i m e 1 ( f o r l i g h t i n g ) : A d j u s t a b l e f r o m 5 s e c
O S - 3 6 5 P A
T i m e : A d j u s t a b l e f r o m 5 s e c t o 3 0 m i n a n d
lighting and HVAC control. It can be widely used in small-scale
O S - 3 6 5 S
CPD-360/2S
t o 3 0 m i n a n d t e s t &
Invisible ceiling flush mount type: Easy to be installed in
1 S
t e s t &
1 S
office, warehouse, storeroom, kitchen, publicwashing room etc.
storeroom, kitchen, public wash room etc.
different thickness of ceiling boards.
T i m e 2 ( f o r H V A C ) : A d j u s t a b l e f r o m 1 0 s e c
The detector of OS-365P and OS-365S can be paralleled
L u x
A d j u s t a b l e f r o m 1 0 L u x t o 2 0 0 0 L u x
t o 6 0 m i n
on one power box to enlarge detection coverage.
High performance relay for connecting various lamps.
A d j u s t m e n t
O S - 3 6 5 P A
CPD-360
T i m e : A d j u s t a b l e f r o m 5 s e c t o 3 0 m i n a n d
High sensitivity with "no dead spot" zones in its 360 high
Invisible ceiling flush mount type: Easy to be installed in
M e t e r
A d j u s t a b l e f r o m a p p r o x .
t e s t &
1 m ( - )
t o a p p r o x .
Φ
1 S
different thickness of ceiling boards.
intensity of detection even for a small movement such as
A d j u s t m e n t
Φ 8 m ( + ) a t t h e h e i g h t o f 2 . 5 m
hand waving . To resolve dead angle of most current
L u x
A d j u s t a b l e f r o m 1 0 L u x t o 2 0 0 0 L u x
The detector of OS-365P and OS-365S can be paralleled
on one power box to enlarge detection coverage.
selling ceiling
A d j u s t m e n t
D e t e c t i o n
3 6 0 c o n e s h a p e , u p t o
o
8 m a t
i n s t a l l a t i o n
Φ
The detector head can be easily
R a n g e
h e i g h t o f 2 . 5 m
High sensitivity with "no dead spot" zones in its 360 high
M e t e r
A d j u s t a b l e f r o m a p p r o x .
1 m ( - )
t o a p p r o x .
Φ
and horizontally
intensity of detection even for a small movement such as
A d j u s t m e n t
RJ-12 plug
1 m s i g n a l c a b l e
Φ 8 m ( + ) a t t h e h e i g h t o f 2 . 5 m
hand waving . To resolve dead angle of most current
angle.
selling ceiling
Two relays for switching outputs of OS-365P: One relay for
D e t e c t i o n
O p e r a t i n g
3 6 0 c o n e s h a p e , u p t o
0
o
C t o + 4 5
o
o
C
8 m a t
i n s t a l l a t i o n
Φ
lighting and another voltage free relay for HVAC (Heating,
The detector head can be easily
R a n g e
T e m p e r a t u r e
h e i g h t o f 2 . 5 m
Ventilation, Air Conditioning).
and horizontally
RJ-12 plug
E n v i r o n m e n t a l
D e t e c t o r
1 m s i g n a l c a b l e
: I P 4 0
angle.
RJ-12 plug and socket for quick and easy connection.
P r o t e c t i o n
P o w e r b o x : I P 2 0
Two relays for switching outputs of OS-365P: One relay for
A built-in red LED is used as an indicator for easy test
O p e r a t i n g
0
o
C t o + 4 5
o
C
Installation and assembly of electrical equipment
operation and status of triggering.
lighting and another voltage free relay for HVAC (Heating,
T e m p e r a t u r e
must be carried out by qualified electricians.
Ventilation, Air Conditioning).
Unique design of knockout is applicable for connecting
E n v i r o n m e n t a l
D e t e c t o r
: I P 4 0
RJ-12 plug and socket for quick and easy connection.
cables with different dimensions.
Contact a qualified electrician in the event of
P r o t e c t i o n
P o w e r b o x : I P 2 0
Non-dropping caps of power box are convenient for
fault or break down.
installation.
AutoLearn Adjusting function to solve the false on and false off
Installation and assembly of electrical equipment
operation and status of triggering.
must be carried out by qualified electricians.
Unique design of knockout is applicable for connecting
cables with different dimensions.
Contact a qualified electrician in the event of
Non-dropping caps of power box are convenient for
AutoLearn Adjusting function to solve the false on and false
A built-in red LED is used as an indicator for easy test
fault or break down.
installation.
operation and status of triggering.
off problems
Unique design of knockout is applicable for connecting
AutoLearn Adjusting function to solve the false on and false off
cables with different dimensions.
problems.
CAUTION!
Non-dropping caps of power box are convenient for
installation.
2.2 Dimension (See FIG.1-A & FIG.1-B)
AutoLearn Adjusting function to solve the false on and false off
Detector
: Φ80 x 53mm
problems.
CAUTION - WE RECOMMEND
CAUTION!
Power box: 140 x 60 x 31.5mm
2.2 Dimension (See FIG.1-A & FIG.1-B)
Detector
: Φ80 x 53mm
Power box: 140 x 60 x 31.5mm
Φ80
which may permanently damage
Φ80
FLUSH M OUNT
PRESENCE D ETECTOR
OS-365 / OS-365A / OS-365S
Detector
Pow er bo x
Lens
FLUSH M OUNT
Manual
PRESENCE D ETECTOR
OS-365 / OS-365A / OS-365S
shield
3
OS-365P or OS-365PA
INSTALLATION AND WIRING
1
1
1
Detector
Pow er bo x
Lens
Manual
shield
3
CPD-360/2 or CPD-360
Please disconnect power completely and read the
OS-365P or OS-365PA
INSTALLATION AND WIRING
entire instruction manual carefully before installation.
1
1
1
FLUSH M OUNT
PRESENCE D ETECTOR
OS-365 / OS-365A / OS-365S
3.1 Select a proper location
Please disconnect power completely and read the
entire instruction manual carefully before installation.
3.1.1 It is recommended to install at the height of 2.5m. The
Lens
detection range can reach up to 8m diameter, and
OS-365S
Manual
FLUSH M OUNT
PRESENCE D ETECTOR
OS-365 / OS-365A / OS-365S
shield
detection angle (See FIG.2).
3.1 Select a proper location
1
1
1
3.1.1 It is recommended to install at the height of 2.5m. The
Side view
Lens
detection range can reach up to 8m diameter, and
CPD-360/2S
OS-365S
Manual
shield
detection angle (See FIG.2).
1
1
1
Side view
4m
2.5
0.75
0 0.75
2.5
4m
4m
2.5
0.75
0 0.75
2.5
4m
3.1.2 Pay attention to the walking direction in the test
proceeding. It is more sensitive to movement across the
Used in commercial office, warehouse,
detector and less sensitive to movement directly
towards to detector which will reduce the detection
3.1.2 Pay attention to the walking direction in the test
coverage (See FIG.3).
proceeding. It is more sensitive to movement across the
More sensitive of movement
o
detector and less sensitive to movement directly
walking across to detector
towards to detector which will reduce the detection
towards the detector, this will reduce the detection
CPD-360
CPD-360/2
coverage (See FIG.3).
detector
in the market.
More sensitive of movement
adjusted
vertically
30
o
o
walking across to detector
350
o
for u
ser to gain the desired detection
detector
in the market.
CPD-360/2:
adjusted
vertically
30
o
350
o
for u
ser to gain the desired detection
CPD-360/2
3.1.3 Helpful tips for installation
Since the detector is in response to temperature change,
please avoid the following conditions (See FIG.4-A &
FIG.4-B):
Avoid aiming the detector toward the objects which may be
swayed in the wind, such as curtain, tall plants, miniature
garden, etc.
Since the detector is in response to temperature change,
please avoid the following conditions (See FIG.4-A &
FIG.4-B):
3.1.3 Helpful tips for installation
Avoid aiming the detector toward the objects which may be
Since the detector is in response to temperature change,
swayed in the wind, such as curtain, tall plants, miniature
please avoid the following conditions (See FIG.4-A &
garden, etc.
FIG.4-B):
Avoid aiming the detector toward the objects whose
surfaces are highly reflective, such as mirror, monitor, etc.
Avoid aiming the detector toward the objects which may be
Avoid mounting the detector near heat sources, such as
swayed in the wind, such as curtain, tall plants, miniature
heating vents, air conditioning, vents as dryers, lights, etc.
garden, etc.
Avoid aiming the detector toward objects with highly reflective
Avoid aiming the detector toward the objects whose
surfaces, such as mirrors, monitors etc.
surfaces are highly reflective, such as mirror, monitor, etc.
Avoid mounting the detector near heat sources, such as
Φ65
heating vents, air conditioning, vents as dryers, lights, etc.
Φ65
FIG.4-A
FIG.1-A
3.2 Wiring
Connecting cables to terminals (See FIG.5) refer to wiring
diagrams (FIG.6 - FIG.11).
FIG.4-A
FIG.1-A
3.2 Wiring
Connecting cables to terminals (See FIG.5) refer to wiring
diagrams (FIG.6 - FIG.11).
140
31.5
FIG.1-B
FIG.5
140
31.5
3.2.1 Override function
FIG.1-B
The detector can be bypassed to keep the light(s) on if
required. When the connected manual switch (Manual SW)
FIG.5
is closed, the detector is overrided and the controlled load
3.2.1 Override function
stays on. Whereas the connected manual switch is opened,
the detector can resume to work normally. Please refer to
The detector can be bypassed to keep the light(s) on if
required. When the connected manual switch (Manual SW)
the wiring diagram (FIG. 6 & FIG.9) for the connection of
manual switch and detector for this function.
is closed, the detector is overrided and the controlled load
overridden
stays on. Whereas the connected manual switch is opened,
3.2.2 OS-365P
the detector can resume to work normally. Please refer to
360
o
3.2.2.1 OS-365P for standard application (See FIG.6).
the wiring diagram (FIG. 6 & FIG.9) for the connection of
L1
manual switch and detector for this function.
N
Top view
3.2.2 OS-365P
CPD-360/2
360
o
360
o
Load
CPD-360/2
3.2.2.1 OS-365P for standard application (See FIG.6).
Φ1. 5m
L1
Manual SW
Φ5m
N
Top view
Φ8m
360
o
Load
Φ1. 5m
Supply
Manual SW
Manual SW
Φ5m
voltage
A1
A2
Fan
Φ8m
M
FIG.2
Supply
Manual SW
voltage
Heater
Contactor
A1
A2
Fan
M
FIG.2
L2
L3
Heater
N
Contactor
Less sensitive of movement
FIG.6
L2
directly towards to detector
3.2.2.2 One load is controlled by two power boxes (See FIG.7).
L3
N
Less sensitive of movement
FIG.6
directly towards to detector
3.2.2.2 One load is controlled by two power boxes (See FIG.7).
L
FIG.3
N
FIG.3
N
Power box
L
L
N
L
N
Power box
N
objects which may be
L
D1
L
D2
N
N
Power box
D1
L
D2
L
.
N
Load
Power box
N
L
D1
L
D2
N
Load
N
FIG.7
D1
FIG.4-B
D2
3.2.2.3 OS-365P controls staircase timer switch (time 1
should be set to
) (See FIG.8).
FIG.7
L
FIG.4-B
N
3.2.2.3 OS-365P controls staircase timer switch (time 1
CPD-360/2
should be set to
) (See FIG.8).
Power box
L
L
N
L
N
L
Earth terminal
Load
μ
N
Power box
N
L
N
Push button
L
D1
(N.O. Type)
OUT IN
D2
L
Earth terminal
Load
μ
N
Staircase timer switch
N
Push button
FIG.8
D1
(N.O. Type)
OUT IN
D2
3.2.3 OS-365PA
Staircase timer switch
3.2.3.1 OS-365PA for standard
application
(See FIG.9).
FIG.8
L
N
3.2.3 OS-365PA
CPD-360
3.2.3.1 OS-365PA for standard
CPD-360
application
(See FIG.9).
Manual SW
Power box
L
L
N
L
Load
N
Power box
Manual SW
Power box
N
L
L
L
OS-365P
RJ-12
L
N
Load
socket
FIG.9
RJ-12
Power box
N
N
socket
N
L
D1
OS-365S
3.2.3.2 One load is controlled by two power boxes
D2
L
CPD-360/2
OS-365P
(option)
(See FIG.10).
RJ-12
N
socket
FIG.9
RJ-12
N
socket
L
D1
N
CPD-360/2S
OS-365S
3.2.3.2 One load is controlled by two power boxes
D2
(option)
(See FIG.10).
Power box
L
L
N
L
N
Power box
N
L
L
N
Power box
N
L
Load
L
N
Power box
N
L
Load
L
FIG.10
N
N
3.2.3.3 OS-365PA controls staircase timer switch (
should be set to
) (See FIG.11).
L
FIG.10
Power box
N
L
L
OS-365P
Power box
RJ-12
N
L
N
socket
L
should be set to
) (See FIG.11).
L
N
3.2.3.3 OS-365PA controls staircase timer switch (
CPD-360
time knob
should be set to
) (See FIG.11).
OS-365P
Power box
RJ-12
L
L
N
socket
L
RJ-12
N
socket
L
Load
μ
N
OS-365S
RJ-12
socket
CPD-360/2
OS-365P
(option)
Power box
N
RJ-12
L
N
socket
L
OS-3 65PA
RJ-12
OUT IN
socket
Push button
L
(N.O. Type)
Load
μ
N
CPD-360/2S
RJ-12
OS-365S
Staircase timer switch
socket
(option)
N
OS-365P
FIG.11
RJ-12
OS-3 65PA
CPD-360
socket
OUT IN
Push button
RJ-12
socket
(N.O. Type)
3.3 Installation procedure
Staircase timer switch
OS-365S
CPD-360/2
OS-365P
(option)
NOTE
FIG.11
RJ-12
socket
RJ-12
socket
To secure correct wiring, please re-check it carefully after
3.3 Installation procedure
wiring.
CPD-360/2S
OS-365S
(option)
NOTE
3.3.1 To install the detector, please drill a hole with diameter
To secure correct wiring, please re-check it carefully after
of 65mm on movable ceiling board and keep the power
wiring.
cable outside. Please strip off 6-8mm of cable
sheathing for wiring (See FIG.12).
3.3.1 To install the detector, please drill a hole with diameter
of 65mm on movable ceiling board and keep the power
cable outside. Please strip off 6-8mm of cable
Φ=65
sheathing for wiring (See FIG.12).
OS-365P
6 - 8mm
RJ-12
socket
RJ-12
socket
Dri ll a hole with
Φ=65
OS-365S
OS-365P
CPD-360
6 - 8mm
(option)
Φ=65mm on th e
RJ-12
socket
ceiling
RJ-12
socket
FIG.12
Dri ll a hole with
CPD-360/2S
OS-365S
(option)
Φ=65mm on th e
ceiling
Φ=65
Φ=65
FIG.12
Max. 8m
Φ=65
FIG.13
Φ=65
Max. 8m
NOTE
FIG.13
During installation, all the requirement of mentioned
RJ-12
socket
standard must be fulfilled when installing, also insulation
and requirements of interconnection cord between power
NOTE
OS-365PA
box and detector shall be considered.
During installation, all the requirement of mentioned
requirements of mentioned
Please keep the installation distance between two
RJ-12
socket
standard must be fulfilled when installing, also insulation
standards
detectors within 8m (See FIG.13) if OS-365S is connected
and requirements of interconnection cord between power
to power box of OS-365P, and the thickness of ceiling
CPD-360
OS-365PA
box and detector shall be considered.
board is 5 - 20mm (See FIG.18).
Please keep the installation distance between two
3.3.2 Unscrew the screw on the left cap of power box with a
detectors within 8m (See FIG.13) if OS-365S is connected
CPD-360/2S
"+" type screwdriver, then open the cap on the two
CPD-360/2
to power box of OS-365P, and the thickness of ceiling
sides of power box with a "-" type screwdriver
board is 5 - 20mm (See FIG.18).
(See FIG.14-A). RJ-12 sockets are for detectors
connection and terminals are for load and power supply
3.3.2 Unscrew the screw on the left cap of power box with a
(See FIG.14-B).
"+" type screwdriver, then open the cap on the two
sides of power box with a "-" type screwdriver
RJ-12
socket
(See FIG.14-A). RJ-12 sockets are for detectors
connection and terminals are for load and power supply
OS-3 65PA
(See FIG.14-B).
Cap
RJ-12
socket
Cap
OS-3 65PA
CPD-360
RJ-12
Cap
socket
OS-3 65PA
Cap
FIG.14-A
RJ-12
socket
time knob
OS-3 65PA
CPD-360
FIG.14-A

Advertisement

loading