Motion Sensitive Acoustic Sensor
Model 5885
Installation Instructions
Wiring
Strip back the outer jacket on your wiring cable. This will
allow wires to flex in the case. Make sure the cable is slack in
the wall to avoid stressing the wires at their connections. The
unit should be connected to a UL listed power supply
capable of providing 4 hours of standby power.
Mounting
Ceiling Mount
1.
Mount unit in direct line of sight of windows to be
protected.
2.
Sensor can be mounted as close as 3.3 feet (1 m) from
glass and up to 12 feet (3.7 m) from glass.
3.
Select appropriate lens mask for field of view of PIR.
4.
Perform glassbreak and PIR walk test.
Note: When ceiling mounted, be sure to insert
"single spot" mask to reduce potential for false
alarms.
12'
Glassbreak
coverage
12'
PIR coverage
Ceiling Mount
ShatterPro Plus 5885
Plus
Microphone
Jumper J1 for
LED latch
Jumper J2 for
separate glassbreack
and PIR
Lens
Cover plate
Masking kit
-
Terminals for Power
9-16 VDC
Wall or Corner Mount
1.
Do not aim sensor directly at window - install so PIR
is covering the area of room you expect to have
occupied.
2.
Sensor can be mounted as close as 3.3 feet (1 m) from
glass and up to 12 feet (3.7 m) from glass.
3.
Select appropriate lens mask for field of view of PIR.
4.
Perform glassbreak and PIR walk test.
12'
PIR coverage
Wall Mount
Microphone
Jumper J1 for
LED latch
Jumper J2 for separate
glassbreak and PIR
PIR
GB
GB
PIR
+
NC
COM
NC
COM
Terminals for
Terminals for
PIR Relay
Glassbreak Relay
12' Glassbreak coverage
PIR coverage
Corner Mount