GENERAL
Temperature variations are sensed by the liquid
filled bulb which hydraulically transmits motion
through a mechanism which rotates the indicating
pointer and actuates precision snap-acting
switch(es). Controller settings are made by
turning the adjustment knob(s). Thermometer
types T800 (with enclosure) and T800S
(skeleton) provide temperature indication only
with no control switches.
Part I - Installation
INSTALL UNIT WHERE SHOCK, VIBRA-
TION AND TEMPERATURE FLUCTUA-
TIONS ARE MINIMAL. ORIENT UNIT SO THAT
MOISTURE IS PREVENTED FROM ENTERING
THE ENCLOSURE. IT IS IMPERATIVE THAT
PROPERLY RATED EXPLOSION-PROOF SEAL-
ING FITTINGS BE USED FOR ELECTRICAL
WIRE ENTRY OR 820E AND 822E TYPE UNITS.
DO NOT MOUNT UNIT IN AMBIENT TEMPERA-
TURES EXCEEDING PUBLISHED LIMITS.
PREVENTATIVE MAINTENANCE / PERIODIC
TESTING (6 MONTHS OR SOONER AS DIC-
TATED BY THE ENVIRONMENT) IS NECESSARY
TO ENSURE OPERATION OF THE PRODUCT TO
SPECIFICATION. LUBRICATE ALL PIVOT POINTS
AND MOVING PARTS, TO PREVENT CORROSION,
WITH COMPATIBLE DRY LUBRICANTS OR LIGHT
GREASE.
DO NOT KNOCKOUT ANY PLUGS ON
EXPLOSION-PROOF TYPES 820E OR 822E
When mounting 800 or 802 type controls, it may be
necessary to remove adjustment knob and front cover.
The knob is secured with a 5/64" Allen Setscrew. The
cover is secured by four screws at the corners.
800 Series
Temperature Controllers and
Thermometers
Types 800, 800S, T800, T800S, 802,
802S, 802P, 802PS, 820E*, 822E*
*Explosion-Proof Class I, Groups B, C, D;
Class II, Groups E, F & G; Class III
Tools Needed
Screwdriver to secure
customer supplied screws
Screwdriver
5/64" Allen Wrench
U N I T E D
C O N T R O L S
Installation and Maintenance
Instructions
UE_TempControl_800_iom_DIM80003
MOUNTING
The controller may be mounted in any position to
either a surface or panel (1/4" thick maximum).
Locate it where vibration, shock and ambient
temperature fluctuations are minimal. It is recom-
mended that mounting the unit with the conduit
connection on the top be avoided.
To Flush Mount
(Not applicable to explosion-proof types)
Cut out the panel as shown in Figure 1A. Mount
to the panel using the two holes located on the
flange of the enclosure.
Clearance for #8 screw - (2) places
Figure 1A - Flush Mounting
To Panel Mount
(Skeletons)
Prepare the cut out, drilling the holes for the knob
shaft and the mounting holes per Figure 1B.
Clearance for #6 screw
(4) places (3/16 Max.
Panel Thickness)
Figure 1B - Panel Mounting (Skeleton)
IM800-03
E L E C T R I C

Advertisement

loading

Summary of Contents for United Electric Controls 800

  • Page 1 WITH COMPATIBLE DRY LUBRICANTS OR LIGHT GREASE. DO NOT KNOCKOUT ANY PLUGS ON EXPLOSION-PROOF TYPES 820E OR 822E When mounting 800 or 802 type controls, it may be necessary to remove adjustment knob and front cover. Clearance for #6 screw (4) places (3/16 Max.
  • Page 2 2 self-tapping screws. Mount to surface per Figure 1D. On dual switch Types 800, 802, 802P explosion-proof types requiring seal fitting, install the nipple and the seal fitting prior to sur- (Enclosed units) face mounting the controller.
  • Page 3 Part II - Adjustments Tools Needed 5/64th” Allen Wrench 5/16” Open End Wrench (2 required) Screwdriver 1/4” Open End Wrench Figure 2A - Dual Switch 9/16” Open End Wrench Switch Settings (Dual switch types only) The basic enclosed and skeleton dual switch controllers are furnished with a choice of individual or common adjustment of set points as described below.
  • Page 4 Adjusting Single Switch pointers and may be separated up to 100% of Types 800, 800S and 820E scale range apart. Move the set point Adjustment Pointer up scale To align either switch to the Adjustment beyond the brown Indicating Pointer.
  • Page 5 The set point of switch #1 is determined by the Part III - Replacements red Adjustment Pointer. The set point of switch #2 may be adjusted by up to 25% of the range span below the switch #1 set point by turning adjust- Tools Needed ment “D”...
  • Page 6 (5) Re-assemble switch bank assembly tension General Layout springs. (6) Install the two spacers and secure the pivot post mounting brackets. (7) Replace the scale, making sure that the scale mounting holes are properly fitted around the cast-in guides hidden by the screws.
  • Page 7 Dimensions 800 Series 820E, 822E...
  • Page 8: Limited Warranty

    RECOMMENDED PRACTICES AND WARNINGS Notes United Electric Controls Company recommends careful consideration of the following factors when specifying and installing UE pressure and temperature units. Before installing a unit, the Installation and Maintenance instructions provided with unit must be read and understood.