10 Zone Call Controller (NC910F, NC910S)
10 Zone Expansion Unit (NC910EF, NC910ES)
20 Zone Call Controller (NC920F, NC920S)
20 Zone Expansion Unit (NC920EF, NC920ES)
IMPORTANT NOTES:
This equipment must be installed and maintained by a suitably skilled and technically competent person.
The Call Controller is a piece of Class 2 equipment. However, any metal parts used during installation
(i.e. the metal back box) MUST be earthed.
Button (A)
Button (B)
10 or 20 Zone Call Controller
The 10 and 20 Zone Call Controllers are compatible with all 800 Series call points, ceiling pulls,
infrared ceiling receivers, monitoring points, overdoor lights and remote sounders. Depending
on how the Controller is configured and the devices connected to it, both Standard and
Emergency calls can be indicated at the Controller. Buttons (A) & (B) allow the user to Reset,
Mute or Accept standard calls, as detailed in the OPERATION section below.
OPERATION
STANDARD CALLS: when triggered by a calling device, the Controller's internal buzzer sounds
continuously and the relevant zone indicator(s) illuminate steady.
Pressing the Controller's Reset Button (A), if enabled, cancels all standard calls. Note: In certain
circumstances there is a specific requirement for standard calls to be reset at their point of
origin and in such applications this function should be disabled.
Pressing the Controller's Mute Button (B), if enabled, silences the Controller's internal buzzer.
However, if a new call (standard or emergency) is triggered anywhere on the system, the buzzer
will resound.
Alternatively, instead of muting calls, Button (B) can be configured as a Call Accept Button.
Pressing Call Accept sends a slow pulsing acknowledgement signal to overdoor lights and reset
points c/w sounder, wired as shown in Fig. 3, page 5. Should a new call (standard or emergency)
be triggered anywhere on the system, any zones in the acknowledgement state will revert to
a standard call.
EMERGENCY CALLS: when triggered by a calling device, the Controller's internal buzzer pulses
on and off and the relevant zone indicator(s) flash.
This level of call takes priority over standard calls and cannot be muted, accepted or reset at
the Controller. An emergency call can only be reset at the device from which it was triggered
or via a reset point, wired on the same zone.

INSTALLATION INSTRUCTIONS

10 and 20 Zone Call Controller Instructions • Approved Document No. DNU0920000 Rev 5
Call
Accept
Zone
names &
alarm
indicators
10 or 20 Zone Expansion Unit
1 of 7

Advertisement

loading

Summary of Contents for E&OE NC910F

  • Page 1: Installation Instructions

    10 Zone Call Controller (NC910F, NC910S) 10 Zone Expansion Unit (NC910EF, NC910ES) 20 Zone Call Controller (NC920F, NC920S) 20 Zone Expansion Unit (NC920EF, NC920ES) IMPORTANT NOTES: This equipment must be installed and maintained by a suitably skilled and technically competent person.
  • Page 2 Fig. 1 - Example System Overview and Typical Applications LEISURE CENTRES & SWIMMING POOLS DISABLED PERSONS TOILET ALARM (DPTA) WITH CALL ACCEPT RESET NC803M MAGNETIC Call Call NC802DEWS NC802DEWM RESET KEY NC806CS NC807C NC809DBB NC804DE SLAVE MASTER OVERDOOR LIGHT CEILING PULL BUTTON RESET POINT BUTTON RESET WATER RESISTANT...
  • Page 3: Installation

    INSTALLATION ALWAYS ENSURE THE MAINS SUPPLY IS ISOLATED BEFORE MAKING ANY CONNECTIONS. Location The Call Controllers (and Expansion Units, if applicable) must be sited indoors and must not be subjected to conditions likely to affect their performance. The ambient light and sound levels should allow the indicators to be clearly visible and the internal buzzer clearly heard.
  • Page 4: Mains Wiring

    Mounting Back Boxes The Controller is supplied with either a flush or surface mounted back box and must be securely fixed to a wall using the four (Ø4.7mm) mounting holes provided. The mounting holes are suitable for use with No.8 round head or countersunk screws. Assess the condition and construction of the wall and use suitable screw fixings.
  • Page 5 Fig. 3 - Example Wiring Connections to the Controller’s Main Control PCB EXAMPLE WIRING FOR ZONES REQUIRING CALL ACCEPT FUNCTION USING +V SW NEGATIVE (0V) SIGNAL (Z) +V SW Sig -Ve +Ve 1 -Ve Sig -Ve Sig -Ve +Ve RESET DO NOT power the PCB without connecting Earth tag to back box earth post!
  • Page 6: Expansion Unit

    Fig. 4 - Connection of Optional Battery Backed Power Supply to Call Controller(s) CONN12 CONN12 +12V +12V External PSU External PSU NC925B1 (12V 1A) CALL CONTROLLER CALL CONTROLLER An NC925B1 12V 1A PSU can be connected to CONN12 (shown above) to supply a maximum of two Controllers, depending upon the battery size.
  • Page 7: Technical Specification

    1 x plastic detachable lid and plastic bezel (all versions). RAL7035. Materials / RAL colour 1 x metal back box for flush mounting (NC910F, NC920F, NC910EF, NC920EF). RAL7035. 1 x metal back box for surface mounting (NC910S, NC920S, NC910ES, NC920ES). RAL7035.